INSTALLATION INSTRUCTIONS FOR THE MODEL ASBL7 ADDRESSABLE SOUNDER BASE
The information contained in this installation instruction is a quick reference guide. For detailed system information refer
to the panel manufacturer's installation manual. This instruction will not address specific programming procedures.
GENERAL DESCRIPTION
This instruction applies to the model ASBL7 addressable low frequency
(520Hz) sounder base, which is to be connected to a DCP Signaling Line
Circuit (SLC). The ASBL7 is to be used only with detector models ACA-V,
ACC-V, ACD-V, ACE-V, AIE-EA, ALG-V, ALK-V, ALK-V2, ALN-V, ALO-V,
ATG-EA, ATJ-EA. The ASBL7 provides an audible
the immediate vicinity. Typical applications are "sleeping areas in hotels,
apartments, etc."
WIRING AND ADDRESSING
NOTE: All wiring must conform to local codes, ordinances
and regulations.
1) Connect wiring to terminals as shown. Do Not loop wire under
terminals. Break wire run to provide supervision of connections.
2) Install base wiring in accordance with the applicable drawings
and appropriate wiring diagram (see following page).
3) "The address of the ASBL7 will automatically be set as the host
sensor's address + 127. For example, if the address of the
attached host sensor is 3, the address of the ASBL7 will be
automatically set as 130 (3 + 127) with no loop power applied or
the loop wires disconnected."
Model
DCP Voltage Range
DCP Loop Idle Current
DCP Loop Low Frequency Alarm
Current
Aux. Power Supply Voltage
Range
Aux. Power Supply Voltage
Range FWR
Auxiliary Idle Current
Auxiliary Low Frequency Alarm
Current
Auxiliary Low Frequency Alarm
Current FWR
Sound Pressure Level at 10ft.
Maximum Humidy
Operating Temperature Rang
Storage Temperature
Base Diameter
Base Height (without sensor)
Weight
Compatible Sensors
HOCHIKI AMERICA CORPORATION
7051 VILLAGE DRIVE SUITE 100
BUENA PARK, CA 90621-2268
, low-frequency
SPECIFICATIONS
ASBL7
17 - 41VDC
250uA
250uA
24VDC (16 - 33VDC)
24VDC (16 - 33VDC)
2.26mA
140mA @ 16VDC
95mA @ 24VDC
72mA @ 33VDC
203mA @ 16VFWR
149mA @ 24VFWR
92mA @ 33VFWR
85dB
93%RH (non-condensing)
32°F (0°C) - 100°F (38°C)
-22°F (-30°C) ~ 158°F (70°C)
6.6"
1.34" (not including terminal block)
0.455lb
ACA-V, ACC-V, ACD-V, ACE-V,
AIE-EA, ALG-V, ALK-V, ALK-V2,
ALN-V, ALO-V, ATG-EA, ATJ-EA
MOUNTING REQUIREMENTS
BASE
alarm in
ALL MODELS
FEATURES
Command selectable evacuation codes - Continuous, March or
Temporal Code 3 and Temporal Code 4 patterns.
Program activation by General Event Type, by Zone,
by Cause and Effect or a combination between the three.
High sound pressure level (85 dB SPL at 10 feet).
Low frequency (520Hz) alarm in compliance with NFPA
requirements for sleeping areas.
CAUTION !
To ensure proper operation
connect this base to a
compatible Fire Control
Panel only. Refer to panel
instructions for proper
connection and
compatibility.
Install the bases in this instruction in accordance with
applicable NFPA standards, local codes, and the
authorities having jurisdiction. Failure to follow these
instructions may result in failure of the sensor and
bases to initiate an alarm condition. Hochiki America
is not responsible for sensors that have been
improperly installed, tested, or maintained.
For testing and cleaning information refer to NFPA-72
for Automatic Fire Detectors for installation guidelines,
testing, and maintenance.
Use "3M" Weatherban # 606 nonflammable sealing
compound to seal field wiring conduit openings in the
mounting back box. Compliance with this request may
reduce the occurrence of the "STACK EFFECT".
* SEE SHEET 2 OF 2 FOR SPECIFIC BACK BOX REQUIREMENTS
BOX MOUNTING
3" OCT
4" OCT
4" SQR*
NO
NO
YES
CAUTION !
If this base will be installed in
an existing operational
system, inform the operator
and local authority that the
system will be temporarily out
of service. Disconnect power
to the control panel before
installing the base.
CAUTION
DWG. # HA-06-450
(PG 1 of 2, 03/22)
PART# 1700-12710