Advertisement

Quick Links

P a g e
| 1
Euromag MC608 Output Guide
This document explains the various outputs that are available for both the MC608
powered by internal battery pack (MC608B) or powered by an external power
source.
It outlines how each of the outputs can be configured, wired and tested along with
links to accompanying technical data and information videos.

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the EUROMAG MC608 and is the answer not in the manual?

Questions and answers

Summary of Contents for BERMAD EUROMAG MC608

  • Page 1 P a g e Euromag MC608 Output Guide This document explains the various outputs that are available for both the MC608 powered by internal battery pack (MC608B) or powered by an external power source. It outlines how each of the outputs can be configured, wired and tested along with...
  • Page 2: Table Of Contents

    Contents 1. Programming guide for MC608 1.1 Programming Overview 1.2 How to Read and Configure the MC608 - Video 1.3 Euromag MC608 Programming Guide 2. Pulse output 2.1 Configuring the Pulse Output 2.2 Information Video 2.3 Wiring the Pulse Output 2.4 Testing the Pulse Output...
  • Page 3: Programming Guide For Mc608

    P a g e 1. Programming of the MC608 1.1 Programming Overview The programming of all the outputs can be done via the four front push buttons of the MC608. Above each button lists the action that can be performed. Pressing the far- left button ‘menu’...
  • Page 4: Euromag Mc608 Programming Guide

    P a g e 1.3 Euromag MC608 Programming Guide...
  • Page 5 P a g e...
  • Page 6: Pulse Output

    P a g e 2. Pulse output Available with both the MC608 battery and externally powered meters. 2.1 Configuring the Pulse output The two parameters that are used for configuring the pulse output is the PULSE QUANTITY (volume of water per pulse) and PULSE T ON (pulse width). As per the aforementioned programming guide these parameters can be accessed via the front push buttons: MENU >...
  • Page 7: Testing The Pulse Output

    P a g e 2.4 Testing the Pulse Output The pulse output can be simulated for testing purposes. This can be performed on the bench or after being installed. First check the FULL SCALE FLOW RATE value. By default, this is set to 10m/s. So, for a 250mm flow meter the FULL SCALE FLOW RATE is set to 490 l/s.
  • Page 8: 20Ma Output

    P a g e 3. 4-20mA output: Only available with the MC608 externally powered meters. Configuring the 4-20mA output The 4mA setting if fixed on 0 l/s (no flow) and the 20mA setting can be adjusted by changing the FULL SCALE FLOW RATE value through the front push buttons: MENU >...
  • Page 9: Modbus Rs485 Communication

    Stop bits: One Parity: None Drop number: 1 Click on the below image to watch the information video on how to configure the ModBus settings: The following links are to download the holding registers for the Euromag MC608: https://www.bermad.com.au/wp-content/uploads/2017/09/MC-608-ModBus-registers- CMD03-e-CMD16.pdf https://www.bermad.com.au/wp-content/uploads/2017/09/MC-608-ModBus-registers- CMD04.pdf...
  • Page 10: Wiring The Modbus Communications

    See fig_914_1 on page 34 of the following instruction manual: https://www.bermad.com.au/wp-content/uploads/2016/11/MC608-Manual- Highres.pdf Testing the ModBus communications All the ModBus registers can be polled at any time once the meter is powered up. Contact Bermad Water Technologies if you require any additional assistance: Phone: 03 9464 2374 Email: damian@bermad.com.au...
  • Page 11: Programmable Alarm Output

    P a g e | 11 5. Programmable alarm output: Available with both the MC608 battery powered and MC608 externally powered meters. Configuring alarm output The alarm (PROG. OUT) is default set to ‘DISABLED’ though can be configured to a number of different parameters: •...
  • Page 12: Testing The Alarm Output

    They are located adjacent to the wiring terminal strip. See fig_914_1 on page 34 of the following instruction manual: https://www.bermad.com.au/wp-content/uploads/2016/11/MC608-Manual- Highres.pdf The following video demonstrates what happens when the ‘Excitation failure’ alarm is triggered: https://youtu.be/5Pn-7KlVsLk?t=288 Contact Bermad Water Technologies if you require any additional assistance: Phone: 03 9464 2374 Email: damian@bermad.com.au...

This manual is also suitable for:

Euromag mc608b

Table of Contents