TM
H800HV
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
• Follow safe electrical work practices. See NFPA 70E in the USA, or applicable local codes.
• This equipment must only be installed and serviced by qualified electrical personnel.
• Read, understand and follow the instructions before installing this product.
• Turn off all power supplying equipment before working on or inside the equipment.
• Use a properly rated voltage sensing device to confirm power is off.
DO NOT DEPEND ON THIS PRODUCT FOR VOLTAGE INDICATION
• Only install this product on insulated conductors.
Failure to follow these instructions will result in death or serious injury.
NOTICE
• This product is not intended for life or safety applications.
• Do not install this product in hazardous or classified locations.
• The installer is responsible for conformance to all applicable codes.
• Mount this product inside a suitable fire and electrical enclosure.
WIRING EXAMPLE
POWER
SOURCE
Z201590-0F
PAGE 1
Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Veris, and the Veris 'V' logo are trademarks or registered trademarks of Veris Industries, L.L.C. in the USA and/or other countries.
CURRENT MONITORING
BUILDING AUTOMATION
CONTROLLER
DI
DI
POWER
SOURCE
UNIT VENT HEATER
©2011 Veris Industries
INSTALLATION GUIDE
Split-Core Current Switch,
Fixed Trip Point
Installer's Specifications
Sensor Power
Insulation Class
Frequency Range
Temperature Range
Humidity Range
Output
Amperage Range
Terminal Block Maximum Wire Size
Terminal Block Torque (nominal)
Agency Approvals
The product design provides for basic insulation only.
INSTALLATION
Disconnect and lock out power to the enclosure containing the
conductor to be monitored.
1. Locate a mounting surface for the removable mounting bracket that will allow
the monitored conductor to pass through the center window when it is installed
and that will keep the device at least 1/2" from any uninsulated conductors.
Determine cable routing for the output connection, allowing wiring to reach the
mounting location.
2. Drill holes to mount the bracket to the chosen surface using the included screws.
3. Wire the output connections and relay between the sensor and the controller
(solid-state contact) and external power supply.
4. Route the conductor through the sensor's center window and slip the assembly
into the mounting bracket.
5. Secure enclosure and reconnect power.
DIMENSIONS
Removable/Adjustable Mounting Bracket
ø 0.7"
(18 mm)
(43 mm)
0.4" x 0.2"
Slot (x2)
(58 mm)
800HV
TM
Induced from monitored current
600VAC RMS (UL)
-40° to 50°C (-40° to 122°F) (to 200A);
-40° to 75°C (-40° to 167°F) (to 100A & 0.25A output)
10-90% RH, non-condensing
N.O. 500mA@250VAC/DC, polarity insensitive
0.75-200A Continuous
4 in-lbs (0.45 N-m)
UL 508 open device listing
0.9"
(23 mm)
2.8" *
(71 mm)
1.7
1.1" *
(27 mm)
2.3"
50/60 Hz
14 AWG
09112