Do you have a question about the Varifan ECS-5C and is the answer not in the manual?
Questions and answers
Summary of Contents for Monitrol Varifan ECS-5C
Page 1
MANUAL ECS-5C Installation / User’s Guide ATTENTION ELECTRICIAN SEE WIRING DETAILS ON PAGES A-3 TO A-6 AND ADDITIONAL INFORMATION IN SECTION B www.monitrol.com...
ECS-5C, including the alarm system and backup devices, after installation, after changes to the installation and every month after that. Fuse verification and replacement, as well as the proper setting of control values shall be the responsibility of the owner of this equipment. Section A-2 ECS-5C www.monitrol.com...
ENDS. NEVER CONNECT BOTH ENDS OF THE SHIELD TO GROUND PLATE . THE USE OF A SHIELD FOR ALL PROBES IS MANDATORY. REFER TO THE DIP-1C MODULE USER’S MANUAL FOR ADDITIONAL DETAILS ON DIP-1C MODULE AND INLET WIRING. Section A-6 ECS-5C www.monitrol.com...
Shielded two-wire twisted pair cable, AWG #22 (used for communication) see electrician note for capacitance selection. 4 screws (to hang the unit onto the wall). Screwdrivers. Soldering iron kit or approved sealed connectors. Drill and hole saw kit. Section B-8 ECS-5C www.monitrol.com...
All cable connections must be soldered or done with approved sealed connectors. Probe cables must be 500’ (150m) or less. Communication cables must be 820’ (250m) or less. It is prohibited to use overhead cables outside the building. ECS-5C Section B-9 www.monitrol.com...
The bracket slots also serve to adjust the position of the controller. Once you have adjusted the controller position, tighten the four mounting screws. FIGURE NO. 1 Mounting Position and Devices Section B-10 ECS-5C www.monitrol.com...
It should also be protected from physical damage. FIGURE NO. 2 Typical Temperature Probe Wiring PROBE SHIELD FIGURE NO. 3 Typical Relative Humidity Probe Wiring MODULES LINE 230V ECS-5C Section B-11 www.monitrol.com...
FIGURE NO. 4 Typical Power Backup Wiring DISTRIBUTION DISTRIBUTION PANEL PANEL LINE LINE 230 VAC 230 VAC source 2 source 1 NO 2 COM 2 NC 2 COM 1 NC 1 NO 1 8 PIN RELAY DPDT (OMRON model MK2EP-UA-AC120) Section B-12 ECS-5C www.monitrol.com...
3 to 5 degrees above the fan’s relative set point or 3 to 5 degrees under the heater relative set point. FIGURE NO. 5 Typical Thermostat Backup Wiring on Relay RELAY T15WD L2(N) ECS-5C Section B-13 www.monitrol.com...
/or auto-dialer. The relay will activate 6-8 seconds after an alarm is triggered. FIGURE NO. 7 Typical Alarm Connection Wiring TEMP. PROBES MODULES ALARM 30V/1A ALARM SYSTEM / AUTO DIALER ECS-5C Section B-15 www.monitrol.com...
Verify all Connections Seal all cable entry holes. Hermetically Close the ECS-5C Close the front panel. Put the power on Secure the front panel with a lock Section B-16 ECS-5C www.monitrol.com...
(MMX) and place it in the bottom part of the enclosure or in another safe location. Once the MMX Chip is removed, the ECS-5C starts up and executes the configuration. Note: During this procedure, some components are live and can be dangerous if touched. ECS-5C Section B-17 www.monitrol.com...
(MMX) and place it in the bottom part of the enclosure or in another safe location. Once the MMX Chip is removed, the ECS-5C will continue to execute the configuration. WARNING: During this procedure, some components are live and can be dangerous if touched. Section B-18 ECS-5C www.monitrol.com...
DIP-1C (Digital inlet positioner) Computer interface NET-IN2 Communication Module (Module inserted into the controller to communicate with the computer interface) RF-IN Communication Module (Module inserted into the controller for a wireless communication with the computer interface) ECS-5C Section B-19 www.monitrol.com...
Page 21
1 foot (30 cm) apart. If low-voltage and high-voltage conduits must be crossed, the crossing must be at a 90-degree angle. All wiring must be made by a certified electrician and conform to local electrical regulations. ECS-5C Section B-21 www.monitrol.com...
ECS-5C is not powered. Make sure the control is Flat cable between the powered. main and top boards of the Make sure the fuse is ECS-5C is disconnected. correct. Make sure the flat cable is connected. Section B-22 ECS-5C www.monitrol.com...
ECS-5C USER’S GUIDE Control Description Varifan ® ENVIRONMENT CONTROL SYSTEM 5 stages MIN SPEED 73.3 TIMER 11 12 1 MIN SPEED ECS-5C Section C-24 ECS-5C www.monitrol.com...
Page 25
This button is used to access to secondary function of a parameter group (appears in green around the parameter dial). 6. SET/CLR Button This button is used to acknowledge a function, set a value (clock, curves) or to clear values (min/max). ECS-5C Section C-25 www.monitrol.com...
Configuration Versions Version Date Min. Proc Modification Version. 11/27/2008 New. 03/30/2010 Update for official release. 05/05/2011 Add wireless communication support. Add DIP-1C support. 10/25/2012 Add Load Delay. 07/08/2014 Add maximum speed on variable stages 1 and 2. Section C-26 ECS-5C www.monitrol.com...
An alarm check will be made to check for high/low temperature and defective probes. The outside temperature may increase the high alarm threshold. The alarm will also activate if the difference between any two inside probes is too great. ECS-5C Section C-27 www.monitrol.com...
Then select the point to adjust using the F2 button and adjust it with the adjustment knob. See the Additional information on parameters section for more information on the growth curve. This parameter is adjusted in 1% increments from 12% to 100%. Section C-28 ECS-5C www.monitrol.com...
This parameter is used to establish the minimum speed of variable stage 2. Variable stage 2 will be activated at this speed when Average Temperature is equal to the Main Set Point+ Relative Temperature Variable 2. This parameter is adjusted in 1% increments from 12% to 100%. ECS-5C Section C-29 www.monitrol.com...
2 will activate when the average temperature of the probes selected in Heater 2 Probe {1-4} is equal to or below Main Set Point + Relative Temperature Fan 4 / Heater 2. This parameter is adjusted in 0.1° increments from -20.0°F to 20.0°F (-11.1°C to 11.1°C). Section C-30 ECS-5C www.monitrol.com...
ECS-5C was powered up or since this parameter was last cleared. To reset this value to 0, press the SET/CLR button. The Heater 1 Record is displayed to the nearest minute from 0 to 32760 minutes. ECS-5C Section C-31 www.monitrol.com...
When Average Temperature is below the Main Set Point + Relative Temperature Low Alarm, a low temperature alarm condition will occur. This parameter is adjusted in 0.1° increments from -40.0°F to -0.5°F (-22.2°C to -0.3°C). Section C-32 ECS-5C www.monitrol.com...
Temperature since the ECS-5C was powered up or since this parameter was last cleared. To reset this value to the actual Average Temperature, press the SET/CLR button. The High Average Temperature Record is displayed to the nearest 0.1° from -58.0°F to 140.0°F (-50.0°C to 60.0°C). ECS-5C Section C-33 www.monitrol.com...
DIPSW3 is set to the ON position (see DIP Switches and Slide Switches Table page 45). The Probe 3 temperature is displayed to the nearest 0.1° from -58.0°F to 140.0°F (-50.0°C to 60.0°C). Section C-34 ECS-5C www.monitrol.com...
See the Additional information on parameters section for more information on the growth curve. If this parameter is set to OFF, the Minimum Speed Variable 1 will not be affected by its growth curve. ECS-5C Section C-35 www.monitrol.com...
COOL , output 5 will activate when the Average Temperature is high. If this parameter is set to HEAT , output 5 will activate when the average temperature of the probes selected in Heater 1 Probe {1-4} is low. Section C-36 ECS-5C www.monitrol.com...
1 will follow. This parameter will appear only if Logic Out 5 is set to HEAT , DIPSW4 is set to the ON position and DIPSW5 is set to the OFF position (see DIP Switches and Slide Switches Table page 45). ECS-5C Section C-37 www.monitrol.com...
Point + Relative Temperature Fan 3 / Mist, fan 3 / mist will be activated for a percentage (Fan 3 / Mist Cycle Time) of this period. This parameter is adjusted in 1% increments from 0% to 100%. Section C-38 ECS-5C www.monitrol.com...
Average Temperature is above Outside Probe + Relative Outside Temperature Alarm. Setting this parameter to OFF will deactivate the outside temperature’s influence on the high alarm threshold. This parameter is adjusted in 0.1° increments from 0.5°F to 40.0°F, OFF (0.3°C to 22.2°C, OFF). ECS-5C Section C-39 www.monitrol.com...
This parameter is used to select the identification number that will be used when communicating with the remote access software. This parameter may be adjusted to any value from 1 to 250. Tech Param Display TPDIS This parameter is reserved for the manufacturer’s technical support personnel. Section C-40 ECS-5C www.monitrol.com...
This parameter displays the version of the processor actually used. (POS 12) System Parameters SYSTM This parameter indicates that the ECS-5C is in system parameter mode. Communication Filter FILTR This parameter is reserved for the manufacturer’s technical support personnel. ECS-5C Section C-41 www.monitrol.com...
Heater 2 (-11.1 to 11.1°C) FAN 4/HEATER 2 [F2] – – Differential Fan 4 / DIFF 2.0°F (1.1°C) 0.5 to 20.0°F (0.3 to 11.1°C) Heater 2 [F2] – – Heater 2 Record — 0 to 32760 min Section C-42 ECS-5C www.monitrol.com...
Page 43
TEMPERATURE RECORD and [F2] – – Relative 12.0°F (6.7°C) 0.5 to 40.0°F (0.3 to 22.2°C) ALARM Temperature High Alarm 100.0°F -40.0 to 119.9°F, OFF [F2] – – Critical High Alarm CRIT (37.8°C) (-40.0 to 48.8°C, OFF) ECS-5C Section C-43 www.monitrol.com...
ON = Outside / OFF = Inside (DIPSW6) – Humidity Probe* ON/OFF (DIPSW7) – DIP-1C* ON/OFF (DIPSW8) – Future Use — — If DIP SWITCHES 6 and 7 are both ON, the controller will use the DIP-1C logic. ECS-5C Section C-45 www.monitrol.com...
Select the ramping parameter (ex: Main Set Point, Minimum speed, etc.). Make sure the Growth day is set to OFF. Press the SET/CLR button. At this moment, the first day of the growth curve will be displayed. ECS-5C Section C-47 www.monitrol.com...
Page 48
1, 8, 20 and 60 and the value points are 80°F, 79°F, 75°F and 70°F. 10. Once the last value point is entered, press the SET/CLR button. You should now be back to a point where the LED display is flashing a temperature value. Section C-48 ECS-5C www.monitrol.com...
Page 49
This characteristic may be useful to users unwilling to use all 4 “preset” ramping points. The following illustration shows how users can stop the curve without entering the last point. ECS-5C Section C-49 www.monitrol.com...
DIP Switches and Slide Switches Table ............. 45 Motor Curve ......................46 Additional information on parameters ..............47 Time of Day (time clock) ..................... 47 Growth Day......................... 47 Ramping ........................47 TABLE OF CONTENTS Section D Limited Warranty ....................53 Section D-52 ECS-5C www.monitrol.com...
Need help?
Do you have a question about the Varifan ECS-5C and is the answer not in the manual?
Questions and answers