I N S T R U C T I O N S
Solenoid Valve for Refrigerant
Type
RPV
PREFACE
Failure to read and follow all instructions carefully before installing or operating this solenoid valve
could cause personal injury and/or property damage. Save these instructions for future use.
NOTE FOR SAFETY
Warning
・When removing the solenoid coil from the valve body, be sure to cut out the power supply
as the coil may burn.
・Do not apply the different voltage from the voltage marked on the coil label.
It may cause burning or failure.
・While power is on, do not touch the housing cover as personal injury may be caused.(Coil heats up to 90℃)
・Do not apply excessive force and/or any impact to the coil as it may cause valve, burn-out and leakage
trouble due to deformation.
・Do not heat up the solenoid coil as the coil might be burn-out.
・Do not put any inflammable thing around the coil as it could catch fire due to the coil heat.
SPECIFICATIONS
(As for the following specification, there is a case different from indication of a product.)
・Water test Press.
: 6.5 MPa
・Max. Working Press. : 4.3 MPa
・Min. Operating Press. Diff. : 0 MPa(port size 3,6mm)
・Fluid Viscosity :
Use this unit within the working range of the 〔pressure difference - fluid viscosity〕 graph shown below.
・Ambient Humidity : 95%RH or less
・Fluid : R22、R134a、R404A、R407C、R410A(When using in other fluorinatid refrigerant, water, oil,
it is recommended to contact us. It is not available in air, nitrogen, oxygen, hydrogen line.)
・Fluid Temp. : -40 to +125℃
・Allowable voltage variation ±10%
・Degree of protection. : Lead wire type coil
IP67
*
*
(
IP65 and IP67 testing methods are specified by IEC 60529. When the unit is always exposed
to rain water, etc. it is subject to dew condensation, or it is used outdoors, it is not
guaranteed. The unit cannot be used under a submerged condition.
・Protection against electric shock : classⅠappliance.
・As explained in NOTE For SAFETY, coil may burn out at an abnormal condition. Use a suitable fuse as shown in beloew table.
Rated Voltage
Frequency
Running Current
Wattage
AC 24V
521/396 mA
AC100V
125/ 95 mA
50/60Hz
6/4.5 W
114/ 86 mA
AC110V
AC200V
50Hz
63 mA
AC200-208V
60Hz
48-53 mA
6 W
AC220V
50Hz
57 mA
4.5-5 W
AC220-230V
60Hz
43-48 mA
50Hz
48-54 mA
4.8-6 W
AC220-230V
60Hz
41-46 mA
4.5-5 W
AC230-240V
50Hz
46-52 mA
AC230-240V
5.2-6 W
60Hz
AC240V
40 mA
4.5 W
INSTALLATION
<Before Installation>
・Ensure the supply voltage to conform with the electrical ratings specified on coil cover
or coil housing.
・Use the refrigerant oil having a viscosity within the working range of
the [pressure difference - fluid viscosity] specified in the specifications.
If it is used outside the working range, an operation failure occurs.
Be careful with the selection of the oil.
It causes the disconnection.
・Do not carry the valve with the lead wire.
・Be careful to scratch flared part and/or
brazing point as it might cause leakage trouble.
・Remove any foreign material or dust in the pipe as it may cause failure of the
solenoid valve.
・If the solenoid valve is not equipped with any strainer, mount a strainer
(80 to 100 mesh) on the inlet side.
・Mounting position should be in the following range.
・Install the space for the maintenance work above the coil.
・Earthing is required at a suitable position on the unit.
COIL
The coil cannot be
used by downward.
BODY
・Airtight Press. : 4.3 MPa
・Max. Operating Press. Diff. : 3.6 MPa
/0.005 MPa(port size:8,10,12,16mm)
・Thermal Class : Class 130(B)
・Ambient Temp. : -30 to +50℃
/ Connector type coil
IP65
Proper Current Fuse
PRESSURE DIFFERENCE - FLUID VISCOSITY
2.0 A
50
0.5 A
Working
range
20
0
0.2 A
Pressure difference〔MPa〕
Before and behind the solenoid valve
when the valve is closed.
Lead wire type coil
Coil cover
Housing
Tube
Plunger
Piston
Body
Inlet
Connector type coil
Housing
min. 50㎜
min. 50㎜
<Installation>
・When installing the solenoid valve, confirm the arrow shown in the valve body in the direction of the flow.
(Be sure to correctly locate outlet and inlet side.)
・If there is a reduced diameter part just in front of the solenoid valve, there is a possibility that operation become unstable.
In that case, please make sure that the entire system functions normally.
・Special attention is required not to apply back pressure. Inner parts of valve may be deformed and may cause leakage trouble.
・Do not install a check valve at the inlet side as it may cause liquid sealing condition on the pipe inside and may cause
damage due to excessive pressure.
・Make sure to fix the valve body and piping firmly. It may cause to be damaged the connection part by piping vibration.
・Conduct airtight inspection after piping work.
・When brazing connections, maintain the temperature below 120℃ at the valve body by using wet clothe or so.
Also prevent the valve body from direct flame during brazing work.
・When brazing, valve inside should be filled with inactive gas (N and CO , etc.) to prevent generation of scale.
・Be sure to firmly tighten a flare nut.
The proper tightening torque is as follows.
It will be recommended to use the proper size spanner for
tightening flare nuts.
・When using a monkey wrench, select a proper size wrench.
Do not contact the wrench to the coil housing.
・When tightening flare connection, hold the square
part of connection on the piping work side,
with another wrench.
・When tightening flare connection, do not hold coil
with hand, or contact the wrench to the coil part.
・Do not apply excessive force to any other part than
connection part, or it may cause to be occurred
operation failure by the coil housing,
plunger tube, valve body etc. are damaged.
・Hold square part and flare nut firmly with wrench.
Flare nut
Wrench
)
・Do not add abnormal power of compression, the pull, and the twist to the main body. It causes the failure.
・Prevent moisture inside piping. It may cause to be operation failure by icing and rust.
・After putting the solenoid coil to the valve body and/or changing the coil direction, be sure to tighten the screw firmly.
Proper tightening torque : 2 N・m
・Loosen the lead wire so that tensility should not add to the lead wire of the coil, when wiring to the coil.
・The protection grade of the connector type coil has been confirmed by our company based on the IEC standard 60529
testing method after mounting an optional socket normally. Confirm the protective performance according to the actual
working environments and conditions of use in advance.
・When you use the optional socket, please make a connection to the socket with a 3-conductor sheathed cable.
(outer diameter of 6~8φ)
・Fasten the mounting screws (M3) of the socket with the torque of 0.4 ~ 0.5N・m.
<Operation>
・Before removing the solenoid coil from the valve body, be sure to cut the power supply. If energizing the coil itself while it
2.5
3.6
is not assembled into the valve body, the coil may cause burn-out.
MAINTENANCE/INSPECTION
・In case of disassembling or inspection, please contact Saginomiya.
・Before making a maintenance or inspection for the valve, be sure to cut the power supply.
OPERATION CHECK
・Install the product correctly and then check its operation to confirm correct function of the whole system.
Housing screw
LIMIT ON APPLICATION
Coil
The product is not designed and manufactured for such equipment or system that is intended to be used under such circumstance
as to relate to human life. For application requiring specially high reliability, please contact the Company first.
SCOPE OF WARRANTY
Lead wire
Unless otherwise agreed by the parties, warranty period of the product shall be one year after delivery.
In case of failure attributable to the Company within such period, the product shall be repaired or replaced,
provided that any one of followings are out of the warranty.
①Unproper handling or application by user
②Modification or repair by other than the Company
Outlet
③Any failure to be caused by acts of God, fire, storm or the like, war,riot or the like and other causes beyond the control
of the parties concerned.
Warranty described in this paragraph means the warranty for the product itself and does not include warranty for any
consequential damage arising out of or occasioned by a defect or failure of the product.
INQUIRY
Coil
Power
terminals
Earthing terminal
2
2
RPV-
RPV-F
RPV-/RPV-F
303BYF
302BYF
302BYF
1005BYF
804BYF
Type
603BYF
602BYF
602BYF
1004BYF
1205BYF
803BYF
Torque N・m
18
29
38
55
75
1606BYF
110