Cast CA454A/W Installation Instructions

Base mount voice range addressable voice sounders & vads c

Advertisement

Quick Links

Supplementary Specification
Part Number:
CA454A/W
CAST Base Voice Sounder with
Description:
isolator
EN 54-3 (Sounders)
Relevant Standards:
EN 54-17 (Short-circuit isolators)
Communication Protocol:
Supply Voltage:
24 to 40 Vdc (sounder)
Quiescent Current (Typical):
Active Current (Typical):
+15 mA *
Power:
600 mW
Environment Type (EN 54-3/23):
Type A (EN 54-3)
VAD Category (EN 54-23):
N/A
VAD Temporal Pattern:
N/A
Coverage Volume (C-Class):
N/A
Flash Rate / Colour:
N/A
Peak SPL at Vmax:
Indicator:
Dimensions:
Weight:
160 g
Mounting Type:
Body Material / Colour:
Polycarbonate / White
IP Rating (EN 60529):
Operating Temperature:
Humidity:
** ± 3 dB(A)
*
@ maximum volume level & brightness;
Dimensions of O-Class VAD (O-R-3-2.5-18)
O = O-Class; R = Rectangular Cuboid; 3 m Height; 2.5 m Width; 18 m Length.
VAD is mounted with lens pointing directly along the length of the corridor, centre of the
ceiling (9 m either side length and 1.25 m either side width).
3 m
2.5 m
E&OE. No responsibility can be accepted by the manufacturer or distributors of these units for any misinterpretation of this
instruction, or for the compliance of the system as a whole. The manufacturers policy is one of continuous improvement
and we reserve the right to make changes to product specifications at our discretion and without prior notice.
4 of 4
Approved Document No. DFU4545000 Rev 2 01/11/22
CA455A/W
CA457/W
CAST Base Voice Sounder
CAST Base Voice Sounder VAD
VAD with isolator, O-Class
with isolator, C-Class
EN 54-3 (Sounders)
EN 54-23 (VADs)
EN 54-17 (Short-circuit isolators)
CAST (C-TEC)
24 to 40 Vdc (sounder)
27 to 40 Vdc (VAD)
470 µA
+26 mA *
1040 mW
Type A (EN 54-3 & EN 54-23)
O-R-3-2.5-18
C-3-8
0.5 Hz synchronised (50 ms ON)
135 m
3
170 m
0.5 Hz / White
89 dB(A) @ 1 m **
Polling LED
112 mm diameter; 46 mm deep (with cap fitted)
170 g
Ceiling
Polycarbonate / Clear
IP21C
-10
o
C to +55
o
C (Type A)
Max. 95% RH (non-condensing)
VAD
CAST Base Mount Voice Range
Base Mount Voice Range
Addressable Voice Sounders & VADs
Product Description
The CAST Base Mount Voice range of addressable, loop-powered bases includes voice sounders
and combined voice sounder visual alarm devices (VADs). Their purpose is to visually and audibly
alert building occupants of a fire alarm. They are designed for use with C-TEC's CAST XFP/ZFP
panels and other `CAST' compatible fire panels.
The following variants are available:
Part Number
Description
CA454A/W
Addressable Ceiling Voice Sounder Base with isolator, white (CAST)
3
CA455A/W
Addressable Ceiling Voice Sounder VAD Base with isolator, white, O-Class (CAST)
CA457A/W
Addressable Ceiling Voice Sounder VAD Base with isolator, white, C-Class (CAST)
All CAST base devices can be optionally used as either:
-
a stand-alone base using a separately available locking white cap (BF330CTLIDW) /
red cap (BF330CTLIDR) / black cap (BF330CTLIDB), or
-
a combined, base device and CAST detector (CAST detectors are separately available).
The devices offer low current consumption, high sound output, high efficiency VADs, four
selectable volume levels, six selectable messages with tones and built-in short-circuit loop
isolators. Please note the volume levels and messages/tones can be changed using the panel's
programming tools.
The sounder and VAD on the combined devices (CA455A/W and CA457A/W) can be set to operate
independently of each other (panel dependent function).
The devices are designed to comply with all relevant sections of the fire alarm device standards
EN 54-3 (Sounders), EN 54-23 (Visual alarm devices - VADs) and EN 54-17 (Short-circuit isolators).
Mounting the Base Device
THE SYSTEM MUST BE COMPLETELY POWERED DOWN BEFORE INSTALLATION
Ensure the base devices are installed in accordance with applicable local or national regulations.
All bases are designed for ceiling mounting, indoor use only. Do not mount bases on uneven
surfaces.
CA454A/W and CA457A/W may be mounted in any orientation, whilst 'O-Class' CA455A/W must
be mounted with its lens pointing directly down the length of the corridor.
The base device has screw terminals for the loop cable (see `CAST Loop Connections΄ section) and
includes rear mounting slots for standard electrical termination boxes. Securely fix the base device
to a ceiling using two screws in the mounting slots provided.
Note: A Quick Connect Plate (Part No. BF431QCP) may be used as an accessory to assist with
cabling to the base device (refer to BF431QCP Document No. DFU4310020 for details).
CAST Base Mount Voice Range
Installation Instructions
CAST Compatible
Approved Document No. DFU4545000 Rev 2 01/11/22
1 of 4

Advertisement

loading
Need help?

Need help?

Do you have a question about the CA454A/W and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Cast CA454A/W

  • Page 1 Supply Voltage: 24 to 40 Vdc (sounder) 27 to 40 Vdc (VAD) alert building occupants of a fire alarm. They are designed for use with C-TEC’s CAST XFP/ZFP Quiescent Current (Typical): 470 µA panels and other `CAST’ compatible fire panels.
  • Page 2 Inspection and maintenance of the system should only be carried out by a competent person the link wires), then back out to the next CAST device on the loop. Note that loop cable screens with specialised knowledge of fire detection and alarm systems. This is normally a third-party fire should be terminated to ensure continuity of the screen to and from the panel.

This manual is also suitable for:

Ca455a/wCa457a/w