REFERENCE; Reference to other sections in the operating instructions Intended use The MW40 is a mobile heat pump that is not suitable for private use. It was designed for commercial use on construction sites, in workshops, storage rooms, etc. and must not be used for room heating...
Another prerequisite for the warranty is regular maintenance in accordance with these instructions, which must be carried out at least once a year. The general warranty period for the MW40 is 12 months after delivery. The invoice date is decisive.
Never switch on the system if housing parts have been removed from the system! Only install the MW40 outdoors and only operate it with outside air as a cooling and heating source! The air ducting sides must not be narrowed or blocked!
Page 6
The regional noise protection regulations must be observed! The following A-weighted sound pressure levels result depending on the distance: Table 4-2: Sound pressure level Distance [m] Sound pressure level [dB(A)] 66,5 64,5 Original operating instructions MW40 [302522-07] V02 / Technical changes excepted / Sept. ‘24...
Figure 4-2: Illustration MW40 left side 1200 ⌀ 525mm Intake ⌀ 525mm Blow-out Condensate drain Figure 4-3: View of the MW40 from the front (left image) and from behind (right image) Original operating instructions MW40 [302522-07] V02 / Technical changes excepted / Sept. ‘24...
Operating Instructions Functions of the system The MW40 is a fully automatic air-to-air heat pump that guarantees independent operation after presetting and activation. The operating parameters can be set via a browser-based visualisation (see Figure 4-5) General view of the WEB-Visu in Figure 4-8 .
Page 9
2. Regardless of the control limit, the compressor runs for at least 2 minutes (except for safety shutdown). Safety shutdown Pressing the emergency stop button shuts down the system immediately. A restart is only possible after the system has been disconnected. Original operating instructions MW40 [302522-07] V02 / Technical changes excepted / Sept. ‘24...
Page 10
Operating Instructions Figure 4-6: Operating range – heating outside air temperature (°C) Original operating instructions MW40 [302522-07] V02 / Technical changes excepted / Sept. ‘24...
3 times automatically. (see 10 error messages) Lamp red (alarm) The system is in error mode. Error The system does not restart automatically. (see 10 error messages) Original operating instructions MW40 [302522-07] V02 / Technical changes excepted / Sept. ‘24...
Page 12
This provides a good overview of the processes in the system as well as input and output values. Figure 4-8: General view of WEB-Visu (example : MWK 40) Original operating instructions MW40 [302522-07] V02 / Technical changes excepted / Sept. ‘24...
Lifting from the front or rear can cause damage to the system and is explicitly not recommended! 1100 Forklift mounts 1150 Figure 5-1: Position of the centre of gravity Original operating instructions MW40 [302522-07] V02 / Technical changes excepted / Sept. ‘24...
Page 14
The centre of gravity is not in the middle, but towards the front of the system! Wrong Figure 5-2: Transport sides and correct pick-up with the forklift truck Original operating instructions MW40 [302522-07] V02 / Technical changes excepted / Sept. ‘24...
When installing on sealed surfaces, ensure that the condensate is drained! Otherwise, there is a risk of slipping due to frozen condensate in cold temperatures! Original operating instructions MW40 [302522-07] V02 / Technical changes excepted / Sept. ‘24...
The power connection for the MW40 is located in the connection box on the left-hand side (next to the indicator lights). It is a CEE plug 32 A (3 ~ 400 V AC, N, PE).
IP range of the system: 192.168.135.xxx. The addresses 1, 2 and 3 must not be used for the xxx at the end. 3 Dynamic Host Configuration Protocol Original operating instructions MW40 [302522-07] V02 / Technical changes excepted / Sept. ‘24...
The target fill level is 2.6 litres of Bitzer lBSE 32 refrigerating machine oil. 5. Pressure and leak test of the refrigeration circuit. 6. Cleaning the registers, the fans and the condensate drain. Original operating instructions MW40 [302522-07] V02 / Technical changes excepted / Sept. ‘24...
Low refrigerant level / loss of refrigerant (800): This error can only be reset by the manufacturer (via master password or from the source code) • Emergency stop (700): Only electrically disconnecting the system will help here. Original operating instructions MW40 [302522-07] V02 / Technical changes excepted / Sept. ‘24...
Page 20
Evaporation below see 610 see 610 application limit Expansion valve driver or control Inspection by qualified Overheating too low defective, electrician and air Poor regulation conditioning specialist Original operating instructions MW40 [302522-07] V02 / Technical changes excepted / Sept. ‘24...
Page 21
External gas in the system (nitrogen, air, etc.) Inspection by air conditioning specialist Register iced up Start defrost function A list of the spare parts to be purchased can be found in the spare parts list. Original operating instructions MW40 [302522-07] V02 / Technical changes excepted / Sept. ‘24...
The refrigerant is about -40 °C cold when it escapes! Components must be disposed of separately according to material and returned to the material cycle! Original operating instructions MW40 [302522-07] V02 / Technical changes excepted / Sept. ‘24...
– original – Kroll Energy GmbH Eduard-Breuninger-Straße 67, 71522 Backnang, Germany We, Kroll Energy GmbH, declare that the machine described below, heat pump MW40, article number 301531 complies with all relevant requirements of the EC Machinery Directive 2006/42/EC. also complies with the following additional EC/EU directives and regulations: The machine Directive 2014/68/EU...
Page 29
• Call up the desired machine by clicking on it • Enter the desired temperature in the "External temperature" field • The room thermostat can also be activated and deactivated via the web app Original operating instructions MW40 [302522-07] V02 / Technical changes excepted / Sept. ‘24...
Page 31
Many and/or tight kinks in the condensate hose can impair the drainage of the condensate. Ideally, the condensate should be able to drip off from a height of approx. 10 cm at the end of the condensate hose. Original operating instructions MW40 [302522-07] V02 / Technical changes excepted / Sept. ‘24...
Operating Instructions 15 Service documentation Date of reported fault Cause Measure / Person Use of materials Original operating instructions MW40 [302522-07] V02 / Technical changes excepted / Sept. ‘24...
Page 33
Operating Instructions Date of reported fault Cause Measure / Person Use of materials Original operating instructions MW40 [302522-07] V02 / Technical changes excepted / Sept. ‘24...
Page 34
Operating Instructions Date of reported fault Cause Measure / Person Use of materials Original operating instructions MW40 [302522-07] V02 / Technical changes excepted / Sept. ‘24...
Page 36
версии, поставленной изготовителем, приводит к тому, что любые гарантии теряют силу. Кроме того, действуют наши „Условия продаж и поставки“. В изделие могут без уведомления вноситься технические модификации, направленные на усовершенствование изделия. Kroll Energy GmbH Eduard-Breuninger-Straße 67 D-71522 Backnang Phone: +49 (0)7191 / 9070 200...