Eco4847P
Installation and
Operation Manual
Your complete installation guide
for Eco4847P batteries

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the Eco4847P and is the answer not in the manual?

Questions and answers

Summary of Contents for Power Eco4847P

  • Page 1 Eco4847P Installation and Operation Manual Your complete installation guide for Eco4847P batteries...
  • Page 2: Table Of Contents

    6.3.3. Primary Charging Source ........................ 20 6.3.4. Secondary Charging Source ......................20 6.3.5. Primary Charging Source with Secondary Charging Source Example ........... 20 6.3.6. Power Conversion Equipment (PCE) Settings ................20 6.3.7. Compatibility with PWM charger ..................... 20 6.4. Calibration to 100% ............................ 20 6.5.
  • Page 3 10. Capacity Testing the Battery ........................25 11. Compatible Grid-Connect Hybrid Inverters ..................... 25 12. End of Life .............................. 26 13. Warranty ..............................26 PowerPlus Energy Pty Ltd Eco4847P Installation and Operation Manual 23/09/2024 | V1.0 Page 2 of 26 •...
  • Page 4: Introduction

    PowerPlus Energy designs and manufactures Lithium Ferro Phosphate (LiFePO4 or LFP) batteries in Australia, to operate in some of the world’s harshest operating environments. The Eco4847P battery is a simple, safe, flexible, and reliable energy storage component that is designed to be easily integrated with most inverter and charger combinations.
  • Page 5: Safety

    Eco4847P battery is a member of the Eco series of batteries and has a nominal operating voltage of 48V. This battery uses high grade cylindrical Lithium Ferro Phosphate (LiFePO4 or LFP) cells which are robust and reliable when operated in higher ambient temperatures.
  • Page 6: Basic Safety

    3.2. BASIC SAFETY WARNING Serious injury or damage to property may result from careless handling of the Eco4847P battery. The following precautions should be observed: • The battery must not be exposed to temperatures above or below the temperature ratings specified in Section 4.4 (Operating Temperature Range).
  • Page 7: Life Support

    LIFE SUPPORT PowerPlus batteries should not be used in critical medical or life support applications where failure of the Eco4847P batteries can reasonably be expected to cause failure of the life support equipment or effect operation of such equipment. 3.6.
  • Page 8: Product Information

    4.1. INTRODUCTION The PowerPlus Energy Eco4847P is a ‘self-managed’ battery in that it doesn’t require communication with external Power Control Electronics (PCE) to operate. Each battery module has an internal BMS which is designed to protect it from adverse and incorrect operating conditions such as: •...
  • Page 9: Eco4847P Specifications

    Specifications correct at time of publication and subject to change. Refer to website for latest information. 1. Voltages are specified at the battery terminals 2. The usable capacity is measured under specific conditions of 0.25C Table 1 (Specifications) PowerPlus Energy Pty Ltd Eco4847P Installation and Operation Manual 23/09/2024 | V1.0 Page 8 of 26 •...
  • Page 10: Charging And Discharging

    4.5. CHARGING AND DISCHARGING 4.5.1. CHARGING/DISCHARGING CURVES Figure 1 (Voltage/Current Curve during Charging) Figure 2 (Voltage/Current Curve during Discharging) PowerPlus Energy Pty Ltd Eco4847P Installation and Operation Manual 23/09/2024 | V1.0 Page 9 of 26 •...
  • Page 11: State Of Charge Vs Discharge Voltage

    The integrated non-polarised DC Circuit Breaker is dual pole and a K curve type. The table below outlines the trip times based on current. Figure 3 (Characteristic K Graph) PowerPlus Energy Pty Ltd Eco4847P Installation and Operation Manual 23/09/2024 | V1.0 Page 10 of 26 •...
  • Page 12: Installation

    Section 4.4 (Operating Temperature Range). The Eco4847P battery is designed to be installed in PowerPlus Energy rack mount and slimline cabinets, 19” data racks, or an electrical or custom cabinet of your choice. The external rack assembly or electrical enclosure is considered outside the scope of the battery product certification.
  • Page 13: Battery Installation

    BESS under the battery. If the guidance above cannot be followed, the battery must be removed from the BESS and shipped in the original manufacturer’s packaging. PowerPlus Energy Pty Ltd Eco4847P Installation and Operation Manual 23/09/2024 | V1.0 Page 12 of 26 •...
  • Page 14: Battery Installation In Motorhomes, Rv's, Trailers, Vehicles, Trucks, Buses Or Similar

    If multiple batteries are being used in parallel, the battery cables shall all be of the same length to retain equal impedance of each battery and cable set. PowerPlus Energy Pty Ltd Eco4847P Installation and Operation Manual 23/09/2024 | V1.0 Page 13 of 26...
  • Page 15: Main Dc Connections

    Ensure all loads and charging sources are removed from the battery before disconnecting the battery connectors. 5.3.3. CASE EARTHING The Eco4847P battery case is designed to be electrically floating and isolated from all internal battery connections and in most installations will not require earthing.
  • Page 16: Battery Alarm Output

    Battery daisy chain connector lead (30cm) COM003A Battery Comms Cable (2m) COM020A Battery Comms Cable (5m) COM050A Battery Comms Cable (10m) COM100A Battery Comms Cable (15m) COM150A PowerPlus Energy Pty Ltd Eco4847P Installation and Operation Manual 23/09/2024 | V1.0 Page 15 of 26 •...
  • Page 17 Figure 5 (Specific examples of how to use alarm contacts)
  • Page 18: Battery Operation

    Finally, it is also used to safely and easily isolate the battery from the DC bus inside the rack or the Battery Energy Storage System (BESS). IMPORTANT If the power system has been shut down or charging source has been removed, the battery should have its circuit breaker switched to the OFF position within 7 days. PowerPlus Energy Pty Ltd Eco4847P Installation and Operation Manual 23/09/2024 | V1.0...
  • Page 19: Battery System Startup

    The battery system should be started following the startup procedure supplied with the system. The Eco4847P battery does not provide an output voltage until it is turned on. In most cases powering on the battery will be one of the first steps of starting your power system.
  • Page 20: Charging And Discharging

    Battery string balancing is achieved by: 1. The battery terminal voltage being over 55.4V, and 2. The recommended charger settings being applied. See website for Custom Charger Settings. PowerPlus Energy Pty Ltd Eco4847P Installation and Operation Manual 23/09/2024 | V1.0 Page 19 of 26 •...
  • Page 21: Primary Charging Source

    In the absence of custom settings, Table 2 (Connected PCE Programming Requirements) provides generic settings suitable for most PCE when using Eco4847P. 6.3.7. COMPATIBILITY WITH PWM CHARGER The Eco4847P is not compatible with PWM chargers including solar, wind or micro hydro. Contact PowerPlus Energy for more information. 6.4.
  • Page 22 3. Ascertain from PCE manufacturer the accuracy of the SoC calculator. If a higher more accurate shunt can be used with the PCE to monitor system SoC, then this should be considered. PowerPlus Energy Pty Ltd Eco4847P Installation and Operation Manual 23/09/2024 | V1.0 Page 21 of 26...
  • Page 23: Troubleshooting

    Available Monday to Friday, 9 AM to 5 PM [AEDT] During normal operation of the Eco4847P battery, whilst the DC Circuit Breaker is in the ON position, there will be a voltage present across the terminals of the battery.
  • Page 24: Under Voltage Battery Recovery

    In the event of an under-voltage shutdown the battery will last up to 3 months before potentially reaching a critical under voltage shutdown, please see Section 7.1.5. The battery will not deliver power to a load from its DC terminals until the battery module exceeds the under-voltage shutdown threshold.
  • Page 25: Extreme Cold

    For further assistance contact your installer or PowerPlus Energy. 8. MAINTENANCE The Eco4847P is designed to require no regular maintenance from users. However, as part of your overall system maintenance, some checks can be carried out at least yearly. •...
  • Page 26: Capacity Testing The Battery

    3 ∗ 100 ��ℎ Ah = Amp Hour Capacity 0.5 = 0.5C constant load discharge 100 = Conversion to % Example: Eco4847P Ah Capacity = 92Ah Battery time to discharge under test = 1.85hrs ("#∗%.')∗).*' " ∗ "# = 92.5% It is recommended to repeat the above test two to three times and average the results.
  • Page 27: End Of Life

    Due to the stability and longevity of LFP cylindrical cells, returned batteries will be refurbished and checked so they can be repurposed for low power applications and made available for community, education, and charity projects. Any batteries not suitable for repurposing will be sent to a licensed recycling facility, where all ferrous and nonferrous metals are separated and then forwarded to our recycling partners.