Summary of Contents for Chubb PEFS F3N

  • Page 1 Part Number TBA Draft...
  • Page 2: Preface

    Original This manual is an uncontrolled document. Chubb Fire & Security Pty Ltd (“Chubb”) reserves the right to alter this manual at any time in accordance with our policy of continuous development. Chubb welcomes feedback regarding this manual and associated equipment.
  • Page 3: Table Of Contents

    Electric Solenoid Valve Assembly ........................................34 Actuation System Fittings ..........................................35 Monitoring Components ......................................36 Pressure Switches ............................................36 Identification & Instruction Labels ..................................37 APPENDIX .................................... 38 Version 1.0, Oct 2020 © Copyright 2020 Chubb Fire & Security Pty Ltd...
  • Page 4 Maintenance Manual SDS – Chubb PEFS F3N Foam Concentrate ................................38 AS2337 Cylinder Visual Inspection Damage Limits ..............................45 Version 1.0, Oct 2020 © Copyright 2020 Chubb Fire & Security Pty Ltd...
  • Page 5: About This Manual

    The Customer is entitled to a replacement or refund for a major failure and to compensation for any other reasonably foreseeable loss or damage. The Customer is also entitled to have the PEFS F3N System repaired or replaced if the PEFS F3N System fails to be of acceptable quality and the failure does not amount to a major failure.
  • Page 6: Intended Use

    Intended use The PEFS F3N System is a fire suppression system, installed as part of an overall fire risk reduction strategy, as defined in the fire system specifications and or risk assessment outcomes. As such, it is designed to suppress a fire occurring in the specified risk area only within the documented coverage area of each installed nozzle.
  • Page 7: Introduction

    PEFS F3N systems consist of pressurised cylinders containing fluorine free foam solution, actuation devices to initiate discharge and a discharge network which includes aspirating spray nozzles to direct the foam spray onto the hazard. PEFS F3N systems may be configured for both manual and automatic operation.
  • Page 8: Maintenance

    The presence of salts in water that is used to fill PEFS F3N cylinders may have an impact to the firefighting performance of the foam, can clog the pressure indicator, bind the valve actuation mechanism, inhibit the removal of the cylinder valve and or lead to pitting corrosion of the cylinder.
  • Page 9: System Defects

    The figures shall be not less than 3mm high, and the markings shall be such that the figures are legible. When a new service label is provided, the label shall be applied adjacent to the completed label so that the previous service history is not obscured. Version 1.0, Oct 2020 © Copyright 2020 Chubb Fire & Security Pty Ltd...
  • Page 10: Recommended Tool List

    Loctite 577 pipe thread sealant or Loctite 569 hydraulic thread sealant Molykote 111 lubricant or equivalent silicon-based o-ring lubricant. Loctite C5-A Anti-Seize Lubricant Table 1 – Recommended Tool List Version 1.0, Oct 2020 © Copyright 2020 Chubb Fire & Security Pty Ltd...
  • Page 11: Service Schedule

    The following maintenance schedule is based on the schedule detailed in AS5062 and those requirements applicable to all the hardware and design features detailed in the PEFS F3N Design, Installation and Commissioning manual. The maintenance schedule is ordered in the recommended sequence of maintenance activities for the PEFS LOP System and does not follow the order given in AS5062.
  • Page 12 (iii) check hoses, LOP tubing, fittings and supports are secure ✓ Actuation system – (a) test pneumatic circuits for leaks Pneumatic (b) check hoses, manifold blocks, fittings and supports are secure Version 1.0, Oct 2020 © Copyright 2020 Chubb Fire & Security Pty Ltd...
  • Page 13 Complete review of system to confirm it is in accordance with the approved design and no changes have been made which would impair performance. Table 3 – Six-monthly and Yearly Service Schedule Version 1.0, Oct 2020 © Copyright 2020 Chubb Fire & Security Pty Ltd...
  • Page 14: Six Monthly Service Instructions

    Clamps are adequately secured to the equipment and firmly hold the discharge hoses and or tubing in place. Nozzle brackets (where fitted) are adequately secured to the equipment and firmly holds the nozzle kit fittings. Version 1.0, Oct 2020 © Copyright 2020 Chubb Fire & Security Pty Ltd...
  • Page 15 Maintenance Manual Version 1.0, Oct 2020 © Copyright 2020 Chubb Fire & Security Pty Ltd...
  • Page 16: Actuation System (Item 4)

    8. Leak Test all connection points (refer figure below) with a liquid leak detection solution. If actuator shows any signs of leakage, carry out service on actuator. Figure 2 9. Re-fit housing cover and ensure it is securely bolted on and label is intact and readable. Version 1.0, Oct 2020 © Copyright 2020 Chubb Fire & Security Pty Ltd...
  • Page 17: Detection System (Item 6)

    2. Ensure control panel (where fitted) is reset to its normal operation mode and is no longer in its “Isolation / Test” mode. 3. Complete routine service records in accordance with AS5062 4. Stamp Service Tag with the number “1” in the corresponding Year/Month location. Version 1.0, Oct 2020 © Copyright 2020 Chubb Fire & Security Pty Ltd...
  • Page 18: Yearly Service Instructions

    Yearly Service Instructions Discharge Test [Optional] (Item 9) An annual discharge test can be used to confirm the complete PEFS F3N system operates and performs as that intended as when originally commissioned. Please refer to the Chubb PEFS F3N Foam Concentrate SDS prior to carrying out the Discharge Test. Discharge of foam solution must be handled according to national or local waste regulations.
  • Page 19: Cylinder Valve - Service (Item 11)

    12. Inspect and clean Pressure Indicator (13) and Schrader Valve (14). Replace if faulty or damaged. Use Loctite 577 or Loctite 569 on threads 13. Re-install cylinder valve (4) to cylinder. Version 1.0, Oct 2020 © Copyright 2020 Chubb Fire & Security Pty Ltd...
  • Page 20 4. Inspect and clean oring (20) and check valve oring (21). Replace if they show signs of wear or damage. Do not lubricate check valve o-ring (21). 5. Re-fit retainer (18) using Loctite 569 or Loctite 577 on thread. Figure 5 Version 1.0, Oct 2020 © Copyright 2020 Chubb Fire & Security Pty Ltd...
  • Page 21: Cylinder Refilling (Item 12)

    Cylinders must only be filled with clean potable water (chloride ion content <150ppm). The fill quantities for each size cylinder are detailed in the table below. Please refer to the Chubb PEFS F3N Foam Concentrate SDS prior to handling the foam concentrate. Cylinder Size...
  • Page 22: Manual Actuators - Service (Item 14)

    Prior to servicing any LOP actuators ensure the system is depressurised by depressurising the PEFS F3N cylinders using the Schrader valve fitted to the cylinder Filler Plug Assembly. Ensure pressure indicators on manual actuator reads zero pressure.
  • Page 23: Detection System - Pneumatic (Item 15)

    Prior to replacing any LOP detection tubing ensure the system is depressurised by depressurising the PEFS F3N cylinders using the Schrader valve fitted to the cylinder Filler Plug Assembly. After having depressurised the PEFS F3N system: 1.
  • Page 24: Detection System - Electrical [Where Fitted] (Item 18)

    Leak test burst disk Leak test all ports on the LOP Valve assembly d. Leak test cylinder welds. 11. Remove caps from discharge ports and re-fit distribution hoses. Version 1.0, Oct 2020 © Copyright 2020 Chubb Fire & Security Pty Ltd...
  • Page 25: After Maintenance Activities

    1786 1816 1847 1878 Table 5 - PEFS F3N cylinder charging pressure versus ambient temperature After Maintenance Activities After the Yearly maintenance activities have been completed: 1. Ensure all pressure indicators are reading in the green zone. 2. Ensure all labels are in good condition (refer 6 monthly service item 8) 3.
  • Page 26: Maintenance Report

    Maintenance Manual MAINTENANCE REPORT Inspection and Maintenance Report for PEFS F3N Vehicle Fire Suppression System Work Order Number: Date: Client Information Customer Name: Contact Name: Customer Address: Telephone: Mobile: Fax: Equipment Information Equipment Type: Equipment Make: Equipment Model: Equipment Serial No.:...
  • Page 27: Spare Parts

    Label – Blue Identification Band C23 & C65 Cylinders 60330 Label – Blue Identification Band C106 Cylinder 66141 Label – Main PEFS F3N Cylinder Label Table 7 – Cylinder Assembly Parts Version 1.0, Oct 2020 © Copyright 2020 Chubb Fire & Security Pty Ltd...
  • Page 28: Lop Cylinder Valve

    C106 51019 Table 10 – Fill Kits Over-fill Tubes Cylinder Part Number Length (mm) Size 36210 36211 36212 36213 C106 36214 Table 11 – Over-fill tube details Version 1.0, Oct 2020 © Copyright 2020 Chubb Fire & Security Pty Ltd...
  • Page 29: Cylinder Brackets

    Figure 14 – C106 Cylinder Bracket (part number 128737) (part number 128738) Bolt HT CL8.8 91323 Spring Washer 94247 Washer 94246 Bracket Weld Lug 128759 Figure 15 – Bracket Weld Lug Assembly Version 1.0, Oct 2020 © Copyright 2020 Chubb Fire & Security Pty Ltd...
  • Page 30: Lop Valve Actuation Bypass Kit (Optional)

    Figure 17 – Nozzle assembly incorporated shroud Part Number Description 46128 Nozzle brass ¼” BSP 1-piece c/w Foil Cap 46129 Replacement Foil Cap Table 14 Nozzle Parts Version 1.0, Oct 2020 © Copyright 2020 Chubb Fire & Security Pty Ltd...
  • Page 31: Nozzle Kits

    Nozzle kit ¼” BSP for Bracket (part number 115815) Nozzle kit 3/8” BSP for Bracket (part number 130104) Nozzle bracket (part number 104592) [supplied separately] Figure 18 – Standard nozzle kits Version 1.0, Oct 2020 © Copyright 2020 Chubb Fire & Security Pty Ltd...
  • Page 32: Discharge Hose And Tube Fittings

    ¾” JIC (m) x ¾” JIC (m) x 1 1/16” JIC (m) Tees 72013 ¾” JIC (m) bulkhead 72014 1 1/16” JIC (m) bulkhead 72008 3/4” JIC (m) x 3/4” JIC (m) x 1/4” BSP (f) Version 1.0, Oct 2020 © Copyright 2020 Chubb Fire & Security Pty Ltd...
  • Page 33 Bolt on Base to suit 132823 Blocks Size Spacing 130073 Double ½” Tube 130074 Double ¾” Hose Table 15 – PEFS F3N discharge hose & tube fittings Version 1.0, Oct 2020 © Copyright 2020 Chubb Fire & Security Pty Ltd...
  • Page 34: Actuation Components

    LOP Actuator Service Kit Table 16 – LOP Manual Actuator Part Numbers Electric Solenoid Valve Assembly 12V DC10W solenoid Figure 20- LOP solenoid valve assembly (part number ES9014-D) Version 1.0, Oct 2020 © Copyright 2020 Chubb Fire & Security Pty Ltd...
  • Page 35: Actuation System Fittings

    45° 7/16” JIC (m & f) swv Elbow 72043 7/16” JIC (m) x 1/8” NPT (m) 118551 1/8” NPT Plug 119568 1/4” NPT Nipple 72010 7/16” JIC Bulkhead Version 1.0, Oct 2020 © Copyright 2020 Chubb Fire & Security Pty Ltd...
  • Page 36: Monitoring Components

    Use with P-Clip 103198. M8 Weld Lug c/w bolt and washer for mounting P- Weld Lug 129578 Clips Table 17 – PEFS F3N pneumatic actuation hose and tube fittings Monitoring Components Pressure Switches • “Cylinder low pressure”, 1450kPa NO Blue (part number 87067) •...
  • Page 37: Identification & Instruction Labels

    66534 part number 66535 part number 66536 part number 66537 part number 66556 part number 66137 part number 66557 Table 18 - Identification & instruction labels Version 1.0, Oct 2020 © Copyright 2020 Chubb Fire & Security Pty Ltd...
  • Page 38: Appendix

    Maintenance Manual APPENDIX SDS – Chubb PEFS F3N Foam Concentrate Version 1.0, Oct 2020 © Copyright 2020 Chubb Fire & Security Pty Ltd...
  • Page 39 Maintenance Manual Version 1.0, Oct 2020 © Copyright 2020 Chubb Fire & Security Pty Ltd...
  • Page 40 Maintenance Manual Version 1.0, Oct 2020 © Copyright 2020 Chubb Fire & Security Pty Ltd...
  • Page 41 Maintenance Manual Version 1.0, Oct 2020 © Copyright 2020 Chubb Fire & Security Pty Ltd...
  • Page 42 Maintenance Manual Version 1.0, Oct 2020 © Copyright 2020 Chubb Fire & Security Pty Ltd...
  • Page 43 Maintenance Manual Version 1.0, Oct 2020 © Copyright 2020 Chubb Fire & Security Pty Ltd...
  • Page 44 Maintenance Manual Version 1.0, Oct 2020 © Copyright 2020 Chubb Fire & Security Pty Ltd...
  • Page 45 NOTE: Burns may result from contact with an heat affected regions but no evidence of surface damage, treat as fire damaged as specified in ‘Fire damage’ below. electric arc or an oxygen-acetylene flame. Version 1.0, Oct 2020 © Copyright 2020 Chubb Fire & Security Pty Ltd...
  • Page 46 (b) free of significant damage; (c) free of burrs; (d) free of cracks; and (e) free of other significant imperfections that would affect the integrity of the connection. Version 1.0, Oct 2020 © Copyright 2020 Chubb Fire & Security Pty Ltd...