RS485 and Dial Capture. For compliance with EN alarm signalling Grade 2, 3, 4, BS 8418 for CCTV monitoring Emizon TCD is the always on, Dual-path, Alarm and CCTV communications monitoring device for Broadband, GPRS and PSTN networks. This guide contains a step-by-step guide to the installation and commissioning of the TCD, the gateway to the Emizon IP service.
Page 3
Kentec Fire Syncro / Solo Orisec CP Range...
IP address can be assigned via Emizon Online Maintenance. A static IP can also be assigned by calling the CSL Technical Support if the GPRS path is up. LED 202 indicates the GPRS path is up. We will require IP, Subnet mask and Gateway details.
Each TCD has a unique Serial Number located on the white lid - you will need this number during the ARC commissioning process. The Serial number or the E M number will also be required when contacting the CSL Technical Support.
CSL will refurbish or replace, at our discretion, any Stand-Alone TCD developing a fault within 5 Years. All returns must be accompanied with a CSL Returns Number, this can be obtained by calling the CSL Technical Support as detailed in the procedure below.
COMPLIANCE Emizon TCD is suitable for installation in systems complying with EN 50131- 1 and is available to comply with EN Grades 2, 3 and 4. Emizon TCD is tested and certified for EN50136-1:2012, EN50136-2:2013, 50130-4/2011 and 50130-5/2011. As a transmission system it is certified to EN50136-1:2012 for ATS Categories SP1, SP2,...
Page 8
• Parallel inputs - Max 3 mtr. Network Interface Monitoring operation EN50136-2:2013: Encrypted polls to the service-platform with timed acknowledgements and timed intervals so SPT, Platform and RCT monitors operation. Information Security - All connections between SPT, Service-platform and RCT are at least AES128 encrypted.
Page 9
Emizon TCD Step 1 - Commissioning Fit the TCD in the alarm Control panel. The TCD can be connected using Pin inputs, RS 232/485 or Dial Capture. USING PIN INPUTS Carefully observing the correct polarity, connect the TCD pin inputs to the panel. The default is +Ve removed.
Page 10
USING UDL WITH PSTN Wiring for TCD Connection to the PSTN line for alarms and upload and download from Panel via GPRS. Please be aware: Dial capture of alarms is not possible with a PSTN connection. Unscrew and remove the Dial Capture Lid •...
Page 11
Emizon TCD Step 2 - Connecting Paths For IP (Broadband) For IP/GPRS connections, connect the Ethernet Port to the network connection Router in the customer’s premises using Cat5 or higher “unshielded Cable. Connect the GPRS antenna. For GPRS/PSTN Connect the GPRS antenna or the High Gain Antenna. For a PSTN connection remove the Dial Capture lid and connect the PSTN line to Terminals T1 and R1.
Emizon TCD Step 3 - Connecting Relays The three changeover relays are rated at 30 Volts DC @ 1A. All 3 relays are Non- Latching. The line fault relay will be in the N/O position when there is no line fault and fall back the N/C position when there is a line fault or other fault which would prevent the TCD from operating normally.
To assign a static IP address, a Laptop is required. A network connection is not required. The minimum firmware must be 1.5.4. THE TCD MUST BE DE-ACTIVATED EITHER BY THE ARC OR BY CSL PRIOR TO ASSIGNING A STATIC IP ADDRESS.
Page 14
Emizon TCD Step 4 - Boot Up & Signal Check • Turn on the power supply to the panel, wait for approximately 30 seconds • The power status Green LED 101 will illuminate. • Upon boot up the following sequence is displayed.
Page 15
Emizon TCD Step 5 - Commissioning With ARC • Call the ARC with the TCD serial number. The ARC will then ‘associate’ or link the TCD to the customer details on their system and ‘activate’ the TCD. • Press the ‘Set’ (R H) button for 5 seconds.
Page 16
SEND A TEST SIGNAL TO THE ARC ON BOTH PATHS, PRESS THE SET BUTTON SW401 FOR 5 SECONDS. You can improve signal strength by purchsing a CSL HGA (High Gain Antenna) with a 5M lead & fitted connector. POSITING HGA The HGA must not be fitted right next to the alarm panel, likewise the 5M of cable...
Page 17
THE GS VALUE MUST READ 12 OR ABOVE. THE GS AND GA VALUE MUST READ 05 FOR GSM/GPRS REGISTRATION. IF THE SIGNAL STRENGTH IS STILL LOW THE SIGNAL MAY BE IMPROVED BY RELOCATING TH HGA. CSL CAN SUPPLY A 5M EXTENSION CABLE FOR AREAS WHERE DISTANCE IS A PROBLEM. EAN CODE 5060386680093...
G A and G r readings must display 0 5 Any other value will not allow a GPRS connection. SIGNALS TO THE ARC & CSL Press SW401 for 5 seconds. A test signal will be sent over any paths that are...
Page 19
TCD. Register for Emizon Online Maintenance. Available of the Emzion section of the Installer Zone FAULT CODES & GPRS DIAGNOSTIC Error and fault conditions are shown on the display. The display may show a number code to indicate the nature of the problem. The most common codes together with the potential reasons and solutions are shown on the table CODE POSSIBLE REASON AND SOLUTION...
Page 20
Butt phone recommended signal is 12 and Gateway, use Emizon tester? and the maximum is 31. Online Maintenance / Phone The higher the GS reading app or call CSL the better the signal. GS 99 indicates no signal...
Page 21
Firewall by the should indicate a double Online Maintenance / person who is responsible for flash once every 3 seconds Phone app or call CSL to the network? apply a Dial prefix To identify if both paths are signalling...
Step 8 - Further Information EMIZON RS232 CONVERTER FOR THE TEXECOM RANGE The Texecom RS232 Converter supplied by CSL should be used for connection between the TCD RS232 terminals and a Texecom TTL COM port. This has a 5 way Molex connector on one end for connecting to the panel and 3 trailing wires on the other for connection to the TCD RS232 terminals.
Page 23
[#XXXXXX|Nti00:00:00/YW831|ATCD RESTARTED] Previous Alarm discarded [#XXXXXX|Nti00:00:00/YS832|ATCD EVENT DELIVERY FAIL] [#XXXXXX|Nti00:00:00/YK832|ATCD EVENT DELIVERY RESTORED] Low Battery fault [#XXXXXX|Nti00:00:00/YT833|ATCD PSU VOLTAGE LOW] [#XXXXXX|Nti00:00:00/YR833|ATCD VOLTAGE RESTORED] Self Test Fail (flash CRC fail) [#XXXXXX|Nti00:00:00/YF834|ATCD SELF TEST FAIL] Primary Path Local Fault [#XXXXXX|Nti00:00:00/NT840|ATCD PRI IFACE FAIL] [#XXXXXX|Nti00:00:00/NR840|ATCD PRI IFACE RESTORE] Secondary Path Local Fault [#XXXXXX|Nti00:00:00/NT841|ATCD SEC IFACE FAIL]...
Page 24
6 - Availability as defined in EN50136-1:2012 is calculated on per path, per ATS and by ATSN as required. However, it is now possible for the Emizon TCD (or any SPT) to define what caused each failure. For accurate calculations it is advisable to record all causes of downtime such that calculations of relevant ATS downtime can be made more accurately.
Page 25
the ATS as unavailable. The installer needs to verify the performance of the ATS according table 2 and 3 of the EN50136-1:2012 at commissioning of the ATS and following any changes (ATE and/ or transmission network) 10 - Logical access at level 4 is defined in EN50136-2:2013.
Page 26
Emizon TCD Connecting - Fire Panel For an EN54-21 Type 1 compliant fire installation Fire Type1 EN54-21 (IP/GPRS) product should be chosen. ALARM PRIORTIY The hard-wired pin inputs of the TCD should be used for signalling. To comply with EN54-21 clause 7.4.1 TCD pin 1 should be used for a fire alarm and pin 2 should be used as fire fault.
Page 27
at 12V DC. To comply with EN54-21, a power supply shall conform at the minimum to the same availability level as the power supply for the fire alarm panel in accordance with EN54-4. Please affix the enclosed EN54-21 label supplied with the TCD to the outside of the TCD enclosure.