IMPORTANT NOTES FOR THE INSTALLER A Quick Check List Is the wall sleeve installed square and caulked to the exterior wall? Is the grille installed? Is the base of the sleeve sloped to the outdoors? Is the disconnect properly sized and installed according to local code? ...
ELECTRICAL WIRING DIAGRAM EVN-AC-H Wiring Diagram This diagram is provided as reference only. Wiring may differ depending on unit. Always refer to correct wiring diagram located on inside cover of electrical panel Optional items that may be ordered separately or field installed: ...
24 hours to flush any continuously at a constant air flow and water through the system at least once a runs the EVN-H main indoor fan at the day. A test button on the control allows continuous FAN speed unless there is a for easy verification that the pump thermostat call.
INSTALLATION WARNING ! Installation should only be performed by qualified personnel. In addition to this manual, all local codes shall be followed. Improper installation may void all warranties. Detailed instructions are shipped with all For installation in a wood frame wall, accessory items and should be followed.
flush to the outdoor finished wall surface. tape or sealing compound. Locate outlets The wall sleeve can be fastened through at least 6 inches from outside walls or the inside face of the sides to the building window coverings. framing with #10 pan head screws. The wall sleeve inside flanges can also be Ductwork installed in unheated space, used to fasten to the wall framing if the...
The wiring diagram is located on the Use copper conductors only. Connect service door. A copy is provided in this power wires to terminal lugs on the document for reference only. Nameplate breaker in the upper electrical section. data is located on the side of the unit. Protect and seal wires where they enter Ampacity is also shown in the the condenser cabinet.
Examine wires for signs of pinching, required. Replacement filters are fraying or charring. Replace as available from Ecologix or can be necessary. sourced from your local hardware store. The unit is designed to fit a standard Condenser Coil 16x25 filter rack.
TROUBLESHOOTING WARNING ! Service should only be performed by qualified personnel. Take proper care to disconnect voltage supply. Use caution when working near charged capacitors. Symptom Cause Check Fan and 1. Power off 1. Check main fuse/circuit breaker compressor will 2.
Page 17
High suction 1. Excessive evap. Air 1. Confirm correct amount of evap. pressure 2. Excessive load Air, adjust air handler air flow. 3. High latent heat 2. Estimate space cooling load and compare to unit capacity. Replace with larger cooling unit if necessary.
Page 18
is reverse flow through the heating loop from a stuck check valve. Fan runs for 1. Room thermostat may 1. Refer to wiring diagram for proper cooling but not be connected installation heating improperly. Heating during 1. Probable cause is 1.
If you require diagnostic assistance, complete the Troubleshooting chart and send to your distributor. START UP INFORMATION AND TROUBLESHOOTING CHART REV: 5/16/2023 EVN Install...
WARRANTY This product is warranted by Ecologix Heating Technologies Inc to be free from defects in materials and workmanship that affect product performance under normal use and maintenance within the applicable periods specified below. Replacements furnished will carry only the un-expired portion of the original warranty.