Summary of Contents for Haskris WW Series

  • Page 1 MANUAL WW-SERIES Revision: 01 Effective Date: 4 September 2024...
  • Page 2: Table Of Contents

    Table of Contents Haskris Contact Information ................. 4 Technical Requirements Note about Technical Requirements ..............5 Clearances ...................... 5 Location ......................5 III. Installation Line Sizing ...................... 6 Piping ......................8 Electrical ......................9 Filling the Reservoir..................10 Startup ON/OFF Switch ..................... 11 Pump Priming ....................
  • Page 3 Remote Communication Options ..............20 Modbus and BACnet ..................20 VII. Maintenance Suction Strainer .................... 23 Particle Filter ....................23 Wye Strainer ....................24 Liquid Level and Water Quality ..............25 Phone: 001 847 956 6420 Email: service@haskris.com Page 3 of 25...
  • Page 4: Haskris Contact Information

    I. Haskris Contact Information Contact Haskris with any questions about a unit and/or the information in this manual. Haskris has a team of engineers available to answer questions, troubleshoot issues, or provide supplemental information as needed. Please have the serial number of the Haskris unit available for reference.
  • Page 5: Technical Requirements

    • Units are built to order based on the application cooling requirements and site conditions. The facility water requirements vary. Refer to the quote document or other technical document specific to the unit for facility water requirements, or contact Haskris with any questions. Phone: 001 847 956 6420 Email: service@haskris.com...
  • Page 6: Installation

    III. Installation Line Sizing Contact Haskris for help: Haskris is available to review pipe runs, pressure drop, etc. and make recommendations for individual sites. Approach to line sizing • Size all interconnecting hose and piping equal to or larger than the connections on the unit.
  • Page 7 • If the total straight pipe length is less than 200 ft (61.0 m) use 2” nominal pipe size (ID). • If the total straight pipe length is less than 510 ft (155.4 m) use 2-1/2” nominal pipe size (ID). Phone: 001 847 956 6420 Email: service@haskris.com Page 7 of 25...
  • Page 8: Piping

    • It is recommended to install an 80-mesh wye strainer at the building water inlet. This will provide some protection for the heat exchanger if the facility water has particulate contaminants. Phone: 001 847 956 6420 Email: service@haskris.com Page 8 of 25...
  • Page 9: Electrical

    Phase monitor: Units configured for 3-phase electrical include a phase monitor. Refer to the fault indicators provided on the phase monitor and contact a licensed electrician to correct any faults. Phase monitor Phase fault LED status patterns Phone: 001 847 956 6420 Email: service@haskris.com Page 9 of 25...
  • Page 10: Filling The Reservoir

    • Make sure additional water is on hand when the unit is started up to top off the liquid level as the external piping is filled. • Note: Some units are designed for compatibility with other fluids. Contact Haskris if you are unsure what fluids are compatible with your unit.
  • Page 11: Startup

    Operation: Toggle the switch to the ON position to make the unit run. Toggle the switch to the OFF position to make the unit stop. If a fault occurs, toggling the switch to OFF and then back ON will reset the fault. ON/OFF switch examples Phone: 001 847 956 6420 Email: service@haskris.com Page 11 of 25...
  • Page 12: Pump Priming

    Pump Priming Purpose: All fluid is removed from the pump head prior to shipment from Haskris. When starting the pump, it needs to be filled with fluid. This process is called priming the pump. When the reservoir is full, the pump suction line is “flooded”. In most cases, this flooded suction will automatically prime the pump.
  • Page 13: Bypass Pressure Relief Valve

    8. Use a wrench to tighten the nut at the base of the adjustment post and reinstall the knurled cap. Bypass pressure relief valve, with adjustment post uncovered Phone: 001 847 956 6420 Email: service@haskris.com Page 13 of 25...
  • Page 14: Pump Supply Pressure

    Note: When partially closing a ball valve from a fully open position, it is normal to see no change in operating pressure until the handle is adjusted a significant amount. Contact Haskris for help: Haskris is available to review pressure adjustments. Final Checks •...
  • Page 15: Controller Display

    The Remote ON/OFF feature is enabled, and the remote signal is either not OFF --> Remote present or is telling the unit to be OFF Description of status modes Phone: 001 847 956 6420 Email: service@haskris.com Page 15 of 25...
  • Page 16: Adjusting Set Value (Sv)

    2. Press the buttons to adjust the value 3. Press the button to move the blinking cursor to the top left corner Phone: 001 847 956 6420 Email: service@haskris.com Page 16 of 25...
  • Page 17: Units Of Measure

    7. Press the buttons to select different units of measure 8. Press the button several times to return to the main display Phone: 001 847 956 6420 Email: service@haskris.com Page 17 of 25...
  • Page 18: Faults

    HH:MM DD/MM/YY Fault reset screen Fault reset: Press the button until you go past the last active fault, you will see this screen which explains how to reset faults. Phone: 001 847 956 6420 Email: service@haskris.com Page 18 of 25...
  • Page 19 Reset alarm, check overload and push reset button if necessary, Pump Overload Alarm Pump overload contact opened measure pump amp draw Description of common faults Phone: 001 847 956 6420 Email: service@haskris.com Page 19 of 25...
  • Page 20: Remote Communication Capability

    • Remote ON/OFF interlock • Modbus capability • BACnet capability Contact Haskris for help: Haskris is available to provide detailed information about a specific design’s capabilities. Modbus and BACnet Purpose: Some facilities have centralized building monitoring systems (BMS). This requires a physical wire connection point between the unit and the BMS as well as appropriate software in the unit.
  • Page 21 5. Press the buttons to highlight Communication 6. Press the button 7. If the top of the screen does not say Communication, press the buttons until it does Phone: 001 847 956 6420 Email: service@haskris.com Page 21 of 25...
  • Page 22 Press the button to return the blinking cursor to the top left corner 12. After making all changes, power cycle the controller for the changes to take effect 13. Contact Haskris for support Phone: 001 847 956 6420 Email: service@haskris.com...
  • Page 23: Maintenance

    Maintenance: Record the pump’s running fluid pressure at the completion of startup when the filter is clean. Replace the filter when the pressure increases 5psi to 6 psi (0.3bar to 0.4 bar) above the startup running pressure. Replacement filters are available from Haskris. Phone: 001 847 956 6420 Email: service@haskris.com...
  • Page 24: Wye Strainer

    10 psi (0.7 bar) or more. Phone: 001 847 956 6420 Email: service@haskris.com Page 24 of 25...
  • Page 25: Liquid Level And Water Quality

    Glycol: If biological growth persists even after regularly changing the water and flushing the system, use laboratory/food grade (99% pure) propylene glycol to create a 10% mixture. Haskris recommends that additives be used only as a means of last resort.