CIT SUPERIOR SLD Series Service Bulletin

Single & dual channel

Advertisement

Quick Links

SUPERIOR™ Gas Detector Series SLD
This manual covers both single and dual channel SUPERIOR Gas Detectors, and applies to all gasses for
which sensors are available. Some instructions apply only to Dual Channel (two sensors) MODEL SLD-2
detectors, and are so noted. IMPORTANT NOTE: Chemical Injection Technologies, Inc. recommends
the use of an UPS (Uninterruptible Power Supply) connected directly to the main AC power supply and
then running the Series SLD Gas Detector directly from the UPS device. These devices are readily
available wherever computers are sold. They offer complete functioning of all features in the event of
power loss, as well as excellent power surge and lightning protection. An optional internal battery backup
is available, but like all other similar types of instrumentation, these internal backup power supplies only
allow limited functions, to conserve power, and do not offer any surge or lightning protection.
Power supply: 115 or 230 VAC, 50/60 Hz,
single phase (user selectable by internal switch)
Power consumption: 12 watts
Sensor Input: 4-20 mA DC, current loop
Loop voltage: 15 VDC, short circuit protected
Sensor output: 4-20 mA DC
Maximum load: 600
Gas Sensors Available: chlorine, sulfur dioxide,
ammonia, ozone
1). Mount the SUPERIOR Series SLD Controller/Monitor at eye level. Mount the sensor(s) 12" (30.5 cm)
off the floor in the area(s) where the gas level is to be monitored. The SUPERIOR Series SLD is
supplied with 25 ft. (7.6 meters) of 2-wire cable, for each sensor. Sensor(s) may be located up to
1000 ft. (305 meters) from the controller/monitor.
2). Standard cable(s) is attached at the factory. If it is necessary to disconnect a cable, in order to run
through walls or conduit, etc., note the connections so they can be re-connected properly. If in doubt,
consult the wiring and connection diagrams at the back of this manual.
3). Turn on AC power to the controller/monitor. On power-up, a two (2)
minute delay is started to allow the sensor device(s) time to stabilize,
which prevents false alarms. First, the countdown timer is
Chemical Injection Technologies
Installation/Service Bulletin
Single & Dual Channel
TECHNICAL SPECIFICATIONS
QUICK START GUIDE
INSTALLATION:
Bulletin 4008 - Rev. 1.30 - 4/18/07
Relays:
Maximum current rating: 5 amps
(resistive)
Maximum voltage: 250VAC/30VDC
Maximum Distance between controller &
sensor(s): 1000 ft. (305 meters)
Operating temperature: 32
N
50
C)
Expected sensor operating life: Two years in
air (decreases with exposure to measured
gasses)
Models: SLD-1 = Single Channel
SLD-2 = Dual Channel
1
N
N
N
F to 122
F (0
C to
SENSOR STABILIZE
2:00

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the SUPERIOR SLD Series and is the answer not in the manual?

Questions and answers

Summary of Contents for CIT SUPERIOR SLD Series

  • Page 1 Bulletin 4008 - Rev. 1.30 - 4/18/07 Chemical Injection Technologies Installation/Service Bulletin SUPERIOR™ Gas Detector Series SLD Single & Dual Channel This manual covers both single and dual channel SUPERIOR Gas Detectors, and applies to all gasses for which sensors are available. Some instructions apply only to Dual Channel (two sensors) MODEL SLD-2 detectors, and are so noted.
  • Page 2: Table Of Contents

    displayed and then the main run screen is displayed. 4). The MAIN RUN SCREEN will display both channels if they are enabled in 1:Cl 0.00 ppm Model SLD-2, or just the single channel if the unit is Model SLD-1. 2:SO 0.00ppm Detector is ready to operate.
  • Page 3 ALARM: SELECT CHANNEL MENU 1). NOTE: On Model SLD-1 Single Channel Gas Detector, the screen will ALM: SELECT CHAN automatically default to the SELECT ALARM menu for Channel 1. For CH1 CH2 Model SLD-1, skip the table below and proceed directly to the CH1 SELECT ALARM MENU table.
  • Page 4: Calibration & Configuration

    TEST Pressing the TEST menu choice from the MAIN MENU will energize all relays, in order to test the functioning of lights, horns, or any other signaling devices connected to the Gas Detector. This will NOT check any of the sensor circuits, and is not intended, in any way, to test either the ability of the sensor to detect a gas, nor to check the sensor output level.
  • Page 5 CALIBRATE ANALOG INPUT CH1 SCREEN: X . X X ppm With the 4-20mA signal generating device wired as shown in the wiring ZRO SPAN diagram at the back of this manual under CALIBRATOR WIRING, the current analog input is displayed in the top right of the screen. Calibrate the zero and full scale value.
  • Page 6: Set Parameters

    SET PARAMETERS (PARM) From the CAL/CFG MENU, press the PARM function key (F2). If you have not previously entered the password from the CAL/CFG MENU, you will be CAL/CFG MENU prompted to enter a password (default is 0000). Use the UP and DWN keys CAL PARM T&D ESC to change the value of the first digit, then press the NXT key to move to the next digit.
  • Page 7 SET CHANNEL 2 GAS SENSOR TYPE: Model SLD-2 Only CH2 SENSOR: SEE CHANNEL 1 INSTRUCTIONS, ABOVE. YOU MAY CHOOSE THE NX8 8 8 8 LST9 9 9 9 ADJ ESC SAME OR A DIFFERENT GAS SENSOR TYPE AS CHANNEL 1. SET CHANNEL 2 RANGE: Model SLD-2 Only CH2 RANGE: SEE CHANNEL 1 INSTRUCTIONS, ABOVE.
  • Page 8 SET DANGER RELAY OPERATION (K2 & K4 terminlas) Scroll through the Parameter settings menus to the DNGR RLY: menu. DNGR RELAY: OFF/ACK This parameter sets the danger relay (high level) operation. You may NX8 8 8 8 LST9 9 9 9 ADJ ESC choose a number of “Energized”...
  • Page 9: Options

    OPTIONS IMPORTANT NOTE: The options section contains settings and choices that rarely need to be changed. There are no visible screens or menu choices that will prompt you to enter the OPTIONS Section. To enter the OPTIONS Section, the MAIN RUN SCREEN must be displayed. Press and HOLD the F4 key for at least four (4) seconds.
  • Page 10 ENABLE EVENT LOGGING: Scroll to the LOG: screen. This setting enables or disables alarm/event LOG: logging. It is recommended that the default ON setting be allowed. From NX8 8 8 8 LST9 9 9 9 ADJ ESC the LOG: screen press the ADJ function key (F3) to toggle between YES or NO.

This manual is also suitable for:

Superior sld-1Superior sld-2

Table of Contents