GmbH. Violations will result in a claim for damages. The solvimus GmbH reserves the right to provide for any alterations or modifications that serve to increase the efficiency of technical progress. All rights in the event of the granting of a patent or the protection of a utility model are reserved by solvimus GmbH.
MBUS-PU3 - User manual Firefox is a trademark of the Mozilla Foundation in the U.S. and other countries. Chrome™ browser is a trademark of Google Inc. Microsoft Excel is a trademark of the Microsoft group of companies. 7-Zip Copyright (C) 1999-2022 Igor Pavlov.
When handling the components, ensure that everything in the vicinity is well earthed (personnel, work- place and packaging). Do not touch electrically conductive components, e.g. data contacts. 1.7 Scope This documentation describes the device manufactured by solvimus GmbH, Ilmenau, and stated on the title page. 1.8 Abbreviations...
Page 7
MBUS-PU3 - User manual Table 2 – Continued from previous page Abbreviation Meaning Clear to send D0 interface (optical interface, IEC 62056-21) Direct Digital Control DHCP Dynamic Host Configuration Protocol Digital Input, digital input terminal Data information field DIFE Data information field extensions Deutsches Institut für Normung, German Institute for Standardization...
Page 8
MBUS-PU3 - User manual Table 2 – Continued from previous page Abbreviation Meaning Programmable Logic Controller PLMN Public Land Mobile Network Point-to-Point Protocol PPPoE Point-to-Point Protocol over Ethernet Polymer with positive temperature coefficient Personal Unblocking Key Random Access Memory REQ_UD...
The device supports operating 3 unit loads at the wired M-Bus (mostly equivalent to the number of meters). The MBUS-PU3 is installed in the housing of a USB stick and can be connected directly on the USB connector of the end device. The supply is assured by the USB connector.
* without legend Table 5: Status LEDs 2.5 First steps The MBUS-PU3 is operational after connection to the host system via USB. The red Power LED indicates the operation of the device. The following figure shows a typical usage of a MBUS-PU3: Figure 2: Typical usage of the MBUS-PU3 Further steps are not required for commissioning the device.
The following dialogue will be displayed: Figure 3: Dialogue for the installation of the driver Once the installation of the driver is achieved, the MBUS-PU3 can be used for the communication with the M-Bus. 2.5.2 Configuration of the logical bus master Whereas the MBUS-PU3 provides the physics of the M-bus master, the protocol, which is the logic of the M-bus, needs to be implemented via software on a PC.
MBUS-PU3 - User manual Figure 4: Device manager with CP210x USB to UART Bridge at COM port An external software (not included) is required to access the data of the M-Bus participants. Further interface parameters are parametrised in the respective system using the communication software. These settings are then automatically adopted for the M-Bus.
Table 7: M-Bus specific terms 2.6 Specific troubleshooting In case the MBUS-PU3 does not work as described in this document, it is useful to locate the malfunction in order to resolve the issue and to recover the full functionality again.
Only trained and appropriately qualified personnel are allowed to check the electric power supply (see Section 1.2.3). Check the cable between MBUS-PU3 and the meter, and replace faulty cables if necessary. Measure the M-Bus voltage at the device and at the meter, it should be approximately 32 VDC.
MBUS-PU3 - User manual 2.7 Technical data 2.7.1 General specifications Dimensions/Mass The device has the following dimensions (including connector) and the following mass: • Width: 19 mm • Height: 12 mm • Depth: 80 mm • Mass: approx. 15 g...