Advertisement

Quick Links

SCIEX UPS PSW 6 kVA - NA
Operator Guide
RUO-IDV-05-14128-A
October 2023

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the UPS PSW 6 kVA - NA and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for SCIEX UPS PSW 6 kVA - NA

  • Page 1 SCIEX UPS PSW 6 kVA - NA Operator Guide RUO-IDV-05-14128-A October 2023...
  • Page 2 Any such use is intended only to designate those manufacturers' products as supplied by SCIEX for incorporation into its equipment and does not imply any right and/or license to use or permit others to use such manufacturers' and/or their product names as trademarks.
  • Page 3: Table Of Contents

    3.1.4 Operating Mode/ Descriptions................14 3.2 UPS Operation.........................16 3.3 External PDU Installation......................19 4 Trouble Shooting..................29 4.1 Audible Alarm..........................29 4.2 Warning Indicator........................29 4.3 Warning Code Descriptions.....................30 4.4 Trouble Shooting Chart......................31 SCIEX UPS PSW 6 kVA - NA Operator Guide Page 3 / 33 RUO-IDV-05-14128-A...
  • Page 4 5 Specifications..................32 Specifications......................32 PSW 6K SCIEX UPS PSW 6 kVA - NA Operator Guide Page 4 / 33 RUO-IDV-05-14128-A...
  • Page 5: Safety And Emc Instructions

    The UPS must be installed by qualified maintenance personnel. • Do not connect appliances or devices other than the SCIEX equipment to the UPS. • Place cables in such a way that no one can step on or trip over them.
  • Page 6: Maintenance

    CONGÉNITALES. www.P65Warnings.ca.gov 1.5 Maintenance NOTE: Battery replacement service is available through your SCIEX Service Representative. • Even after the UPS is disconnected from the mains supply, the components inside are still connected to the battery packs, which may be potentially dangerous.
  • Page 7: Recycling

    CAN ICES-003 (A) Warning: This is a product for commercial and industrial application in the second environment-installation re- strictions or additional measures may be needed to prevent disturbances. SCIEX UPS PSW 6 kVA - NA Operator Guide Page 7 / 33...
  • Page 8: Installation

    8. Power stage fan 9. Maintenance bypass switch 10. Input circuit breaker 11. Isolation transformer fan 13. External battery connector 20. UPS output 21. UPS input SCIEX UPS PSW 6 kVA - NA Operator Guide Page 8 / 33 RUO-IDV-05-14128-A...
  • Page 9: Ups Electrical Conntections/Installation

    256/128 230/115 266/133 NOTE 1: If settings other than the default are desired, configuration can be done at the factory for an additional voltage configuration fee. SCIEX UPS PSW 6 kVA - NA Operator Guide Page 9 / 33 RUO-IDV-05-14128-A...
  • Page 10: Storage And Maintenance

    Every 2 months 1-2 hours Software Installation For optimal computer system protection, install UPS monitoring software to fully configure UPS shutdown. Refer to the included Viewpower CD. SCIEX UPS PSW 6 kVA - NA Operator Guide Page 10 / 33 RUO-IDV-05-14128-A...
  • Page 11: Operations

    ● No Output mode ○ ○ ○ ○ Bypass mode ● ○ ○ ○ AC mode ○ ● ○ ○ Battery mode ○ ○ ● ○ SCIEX UPS PSW 6 kVA - NA Operator Guide Page 11 / 33 RUO-IDV-05-14128-A...
  • Page 12: Lcd Panel

    Indicates the output voltage, frequency or battery voltage. Vac: output voltage, Vdc: battery voltage, Hz: frequency Load information Indicates the load level as 0-25%, 26-50%, 51-75%, and 76-100%. Indicates an overload. SCIEX UPS PSW 6 kVA - NA Operator Guide Page 12 / 33 RUO-IDV-05-14128-A...
  • Page 13 Indicates a low battery level and low battery voltage. Input & Battery voltage information Indicates the input voltage or frequency or battery voltage. Vac: Input voltage, Vdc: battery voltage, Hz: input frequency SCIEX UPS PSW 6 kVA - NA Operator Guide Page 13 / 33 RUO-IDV-05-14128-A...
  • Page 14: Operating Mode/Descriptions

    UPS will back up power from t h e battery and a n alarm will beep every 4 seconds. LCD display SCIEX UPS PSW 6 kVA - NA Operator Guide Page 14 / 33 RUO-IDV-05-14128-A...
  • Page 15 LCD display Fault status Description When a UPS fault has happened, the UPS shows fault messages on the LCD panel. LCD display SCIEX UPS PSW 6 kVA - NA Operator Guide Page 15 / 33 RUO-IDV-05-14128-A...
  • Page 16: Ups Operation

    If there is no more load to be switched off at that time, you have to shut down all loads as soon as possible to SCIEX UPS PSW 6 kVA - NA Operator Guide...
  • Page 17 2. Please check the loads, wiring, ventilation, utility, battery and so on after the fault occurs. Don’t try to turn on the UPS again before solving the problems. If the problems can’t be fixed, please contact SCIEX customer care immediately.
  • Page 18 NOTE 2: All parameter settings will be saved only when UPS shuts down normally with an internal or external battery connection. (Normal UPS shutdown means turning off input breaker in bypass/no output mode). SCIEX UPS PSW 6 kVA - NA Operator Guide...
  • Page 19: External Pdu Installation

    NEMA PDU (SCIEX UPS PDU - NA) Step 2: Loosen the two screws (M4*8) located on the bottom of case panel as shown below. NEMA PDU (SCIEX UPS PDU - NA) SCIEX UPS PSW 6 kVA - NA Operator Guide Page 19 / 33...
  • Page 20 NEMA PDU (SCIEX UPS PDU - NA) Step 5: Adjust the height of leveling foot to support the unit well. NEMA PDU (SCIEX UPS PDU - NA) SCIEX UPS PSW 6 kVA - NA Operator Guide Page 20 / 33...
  • Page 21 Step 6: Connect the PDU to the UPS output receptacle NEMA PDU (SCIEX UPS PDU - NA) SCIEX UPS PSW 6 kVA - NA Operator Guide Page 21 / 33 RUO-IDV-05-14128-A...
  • Page 22 15 programs to set up. Refer to below table. Parameter 2 and parameter 3 are the setting options or values for each program. Parameter 2 Parameter 3 SCIEX UPS PSW 6 kVA - NA Operator Guide Page 22 / 33 RUO-IDV-05-14128-A...
  • Page 23 You may choose the following output voltage in parameter 3: 208: Presents output voltage is 208Vac 220: Presents output voltage is 220Vac 230: Presents output voltage is 230Vac 240: Presents output voltage is 240Vac SCIEX UPS PSW 6 kVA - NA Operator Guide Page 23 / 33 RUO-IDV-05-14128-A...
  • Page 24 UPS is powered on with mains and before the UPS finished the startup, there will be a few seconds of voltage pulse (same as the input voltage) on the bypass output. If you need to remove the pulse on this mode to protect your load better, you could contact SCIEX customer care. for help.
  • Page 25 50 Hz: The setting range is from 52.0Hz to 54.0 Hz. 60 Hz: The setting range is from 62.0Hz to 64.0Hz. The default value is 52.0Hz/62.0Hz. SCIEX UPS PSW 6 kVA - NA Operator Guide Page 25 / 33 RUO-IDV-05-14128-A...
  • Page 26 DIS: Disable the battery discharge protection and backup time will depend on battery capacity. The default value is DIS. 10: Reserved Interface Setting Reserved 11: Reserved Interface Setting Reserved SCIEX UPS PSW 6 kVA - NA Operator Guide Page 26 / 33 RUO-IDV-05-14128-A...
  • Page 27 Parameter 2: You may choose “Add” or “Sub” to adjust the inverter voltage. Parameter 3: The voltage range is from 0V to 6.4V, the default value is 0V. SCIEX UPS PSW 6 kVA - NA Operator Guide Page 27 / 33...
  • Page 28 For example, if the setting charging current is 4A, but the real current is detected as 3.6A, please set up calibrated current as + 3. Setting charging current 4A = real measured current 3.6A + 0.3A SCIEX UPS PSW 6 kVA - NA Operator Guide Page 28 / 33...
  • Page 29: Troubleshooting

    Fan failure/Over temperature Beeping every second Charger failure Beeping every second I/P fuse broken Beeping every second Overload 3 times in 30 min Beeping every second SCIEX UPS PSW 6 kVA - NA Operator Guide Page 29 / 33 RUO-IDV-05-14128-A...
  • Page 30: Warning Code Descriptions

    PFC current failure in battery mode Inverter over current Bus voltage changes too fast Inverter waveform abnormal SPS 12V abnormal Inverter current detection error 6D Transformer over temperature SCIEX UPS PSW 6 kVA - NA Operator Guide Page 30 / 33 RUO-IDV-05-14128-A...
  • Page 31: Troubleshooting Chart

    Check the fans and notify dealer. The icon flash on the LCD working; or the UPS display and the alarm beeps every temperature is too high. second. SCIEX UPS PSW 6 kVA - NA Operator Guide Page 31 / 33 RUO-IDV-05-14128-A...
  • Page 32 5 Specifications 5.1 PSW 6kVA Specifications SCIEX UPS PSW 6 kVA - NA MODEL NUMBER CAPACITY Power rating 6 kVA (6 kW) INPUT Voltage (nominal) 208 VAC (220 VAC, 230 VAC, 240 VAC optional) Voltage range 110-300 VAC Frequency 46–64 Hz auto-sensing...
  • Page 33 SCIEX and its representatives maintain a staff of sully-trained service and technical specialists located throughout the world. They can answer questions about the system or any technical issues that might arise. For more infor- mation visit the SCIEX website at sciex.com or contact us in one of the following ways: •...

Table of Contents