Page 2
Notices: • Product specifications and design are subject to change without notice for future improvement. • For further details, please check with our authorized dealer. Trademarks “AIRSTAGE Mobile” is a trademark of FUJITSU GENERAL LIMITED. Android and Google Play are trademarks of Google LLC. App Store is a service mark of Apple Inc., registered in the U.S.
1. Specifications Wall mounted Type Inverter, Heat pump RSG07KETF RSG09KETF RSG12KETF RSG14KETF Model name RSG07KETF-B RSG09KETF-B RSG12KETF-B RSG14KETF-B Power supply 230 V~ 50 Hz Power supply intake Outdoor unit Available voltage range 198—264 V Rated Btu/h 6,800 8,500 11,600 14,300 Cooling 0.9—3.0...
Page 7
Wall mounted Type Inverter, Heat pump RSG07KETF RSG09KETF RSG12KETF RSG14KETF Model name RSG07KETF-B RSG09KETF-B RSG12KETF-B RSG14KETF-B Remote controller Wireless (Option: Wired, Mobile app* [AIRSTAGE Mobile]) NOTES: • Specifications are based on the following conditions: – Cooling: Indoor temperature of 27°CDB/19°CWB, and outdoor temperature of 35°CDB/24°CWB.
2. Wireless LAN control By installing mobile app on a smart device, several functions can be controlled from outside the house. 2-1. System requirement Before using this function, prepare the following items: • Wireless router: Wireless LAN standard IEEE802.11b/g/n • U.S.A., Canada: 2.4 GHz (1ch—11ch) Frequency bands* •...
2-2. Wireless LAN function list NOTE: To use the wireless LAN control, user registration in advance and access to the wireless home network are required. Attached Wireless Item Mobile app Remote Controller Operation on/off ○ ○ Operation mode setting ○ ○...
RSG14KETF, RSG07KETF-B, RSG09KETF-B, RSG12KETF- B, and RSG14KETF-B Unit: mm 373.5 417.5 (950) Outline of indoor unit for pipe inlet Ø65 for pipe inlet Ø65 - 6 - 3-1. Models: RSG07KETF, RSG09KETF, RSG12KETF, RSG14KETF, RSG07KETF-B, 3. Dimensions RSG09KETF-B, RSG12KETF-B, and RSG14KETF-B...
Page 11
Wall hook bracket Outline of the indoor unit 166 or more 211 or more 1,500 or more The flare connection part should be installed outdoors. - 7 - 3-1. Models: RSG07KETF, RSG09KETF, RSG12KETF, RSG14KETF, RSG07KETF-B, 3. Dimensions RSG09KETF-B, RSG12KETF-B, and RSG14KETF-B...
Airflow Rate (AFR): For cooling capacity: Total Capacity (TC), Sensible Heat Capacity (SHC), and Input Power (IP) For heating capacity: Total Capacity (TC) and Input Power (IP) 5-1. Cooling capacity ¢ Models: RSG07KETF and RSG07KETF-B Indoor temperature °CDB °CWB °CDB...
5-2. Heating capacity NOTE: Values mentioned in the table are calculated based on the maximum capacity. ¢ Models: RSG07KETF and RSG07KETF-B Indoor temperature °CDB °CWB 1.85 0.95 1.83 0.97 1.81 0.98 1.80 1.02 1.78 1.04 2.22 1.00 2.20 1.02 2.17 1.03...
6. Fan performance 6-1. Air velocity distributions ¢ Models: RSG07KETF, RSG09KETF, RSG12KETF, RSG07KETF- B, RSG09KETF-B, and RSG12KETF-B Fan speed Operation mode Measuring conditions HIGH Unit: m/s Top view Horizontal louver: Up Vertical louver: Center Unit: m/s Top view Horizontal louver: Up Vertical louver: Left &...
Page 17
¢ Models: RSG14KETF and RSG14KETF-B Fan speed Operation mode Measuring conditions HIGH Unit: m/s Top view Horizontal louver: Up Vertical louver: Center Unit: m/s Top view Horizontal louver: Up Vertical louver: Left & Right Unit: m/s Side view Horizontal louver: Up Vertical louver: Center Unit: m/s Side view...
6-2. Airflow ¢ Models: RSG07KETF and RSG07KETF-B Cooling Fan speed Airflow HIGH QUIET Heating Fan speed Airflow HIGH QUIET - 14 - 6-2. Airflow 6. Fan performance...
Page 19
¢ Models: RSG09KETF and RSG09KETF-B Cooling Fan speed Airflow HIGH QUIET Heating Fan speed Airflow HIGH QUIET - 15 - 6-2. Airflow 6. Fan performance...
Page 20
¢ Models: RSG12KETF and RSG12KETF-B Cooling Fan speed Airflow HIGH QUIET Heating Fan speed Airflow HIGH QUIET - 16 - 6-2. Airflow 6. Fan performance...
Page 21
¢ Models: RSG14KETF and RSG14KETF-B Cooling Fan speed Airflow HIGH QUIET Heating Fan speed Airflow HIGH QUIET - 17 - 6-2. Airflow 6. Fan performance...
7-2. Sound level check point Microphone Microphone NOTE: Detailed shape of the actual indoor unit might be slightly different from the one illustrated above. - 20 - 7-2. Sound level check point 7. Operation noise (sound pressure)
8. Safety devices Model Type of Protection form RSG07KETF RSG09KETF RSG12KETF protection RSG07KETF-B RSG09KETF-B RSG12KETF-B Circuit Current fuse (PCB*) 250 V, 3.15 A protection More than 85°C Activate Fan motor speed down Fan motor Thermistor protection protection 85°C or less...
9-1. External input With using external input function, some functions on this product can be controlled from an external device. • “Operation/Stop” mode or "Forced stop" mode can be selected with function setting of indoor unit. • A twisted pair cable should be used. Maximum length of cable is 150 m. •...
Page 28
¢ External Input and Output PCB The indoor unit Operation/Stop can be set by using the input connector on the PCB. • Input select Use either one of these types of connectors according to the application. (Both types of connec- tors cannot be used simultaneously.) –...
Page 29
¢ Input signal type • Indoor unit Input signal type is only "Edge". Edge • External Input and Output PCB The input signal type can be selected. Signal type (edge or pulse) can be switched by the DIP switch 2 (SW302) on the External Input and Output PCB.
9-2. External output Use an external output cable with appropriate external dimension, depending on the number of ca- bles to be installed. ¢ Indoor unit • A twisted pair cable should be used. Maximum length of cable is 25 m. •...
Page 31
¢ External Input and Output PCB • A twisted pair cable should be used. Maximum length of cable is 25 m. • Output voltage: High DC 12 V ±2 V, Low 0 V. • Permissible current: 50 mA • For details, refer to "Setting of external input and output"...
9-3. Setting of external input and output • Indoor unit Input Connection point Function setting number 46 Function Operation/Stop mode 1 (R.C. enabled) (Setting prohibited) CN46 Forced stop mode Operation/Stop mode 2 (R.C. disabled) Output Connection point Function setting number 60 Function Operation/Stop 01 to 08...
9-4. Details of control input function ¢ Operation/Stop mode 1 • In the case of "Edge" input External Input and Output PCB Function External input Input signal Command setting Rotary SW302 switch Off → On Operation — Input of indoor unit CN46 On →...
Page 34
¢ Forced stop • In the case of "Edge" input External Input and Output PCB Function External input Input signal Command setting Rotary SW302 switch Forced stop Off → On (R.C. disabled) — Input of indoor unit CN46 Normal On → Off (R.C.
Page 35
¢ Operation/Stop mode 2 • In the case of “Edge” input External Input and Output PCB Function External input Input signal Command setting Rotary SW302 switch Operation Off → On (R.C. enabled) — Input of indoor unit CN46 Stop On → Off (R.C.
Page 36
¢ Forced thermostat off External Input and Output External input Input signal Command Rotary switch Off → On Thermostat off External Input and 2, B, C, D CN313 Output PCB On → Off Normal operation CN313 Compressor Room temp. Set temp. - 32 - 9-4.
9-5. Details of control output function ¢ Operation status External Input and Function Output PCB External output Output signal Status setting Rotary switch Off → On Operation 60-00 1, 2 Output of indoor unit CN47 On → Off Stop Off → On Operation External Input and —...
Page 38
¢ Indoor unit fan operation status External Input and Function Output PCB External output Output signal Status setting Rotary switch Off → On Fan run 60-10 Output of indoor unit CN47 On → Off Fan stop Off → On Fan run External Input and —...
10. Group connection NOTE: Group control cannot be used together with WLAN Adapter. Installation procedure for group control system: A number of indoor units can be operated at the same time using a single remote controller. NOTE: When different type of indoor units (such as wall-mounted type and cassette type, cassette type and duct type, or other combinations) are connected using group control system, some functions may no longer be available.
12. Function settings To adjust the functions of this product according to the installation environment, various types of function settings are available. NOTE: Incorrect settings can cause a product malfunction. 12-1. Function settings by using remote controller Some function settings can be changed on the remote controller. After confirming the setting proce- dure and the content of each function setting, select appropriate functions for your installation envi- ronment.
Page 43
NOTES: • The air conditioner custom code is set to prior to shipment. • If you do not know the air conditioner custom code setting, try each of the custom codes ( → → → ) until you find the code that operates the air conditioner. - 39 - 12-1.
Page 44
¢ Contents of function setting Each function setting listed in this section is adjustable in accordance with the installation environ- ment. NOTE: Setting will not be changed if invalid numbers or setting values are selected. Function setting list Function no. Functions Filter sign 30/31...
Page 45
2) Room temperature control for indoor unit sensor Depending on the installed environment, correction of the room temperature sensor may be re- quired. Select the appropriate control setting according to the installed environment. The temperature of the room temperature sensor is corrected as follows: Corrected temp.
Page 46
3) Room temperature control for wired remote controller sensor Depending on the installed environment, correction of the wire remote temperature sensor may be required. Select the appropriate control setting according to the installed environment. To change this setting, set Function 42 to Both “01”. Ensure that the Thermo Sensor icon is displayed on the remote controller screen.
Page 47
6) Remote controller custom code (Only for wireless remote controller) The indoor unit custom code can be changed. Select the appropriate custom code. Function number Setting value Setting description Factory setting ♦ 7) External input control "Operation/Stop" mode or "Forced stop" mode can be selected. Function number Setting value Setting description...
Page 48
10) Switching functions for external output terminal Functions of the external output terminal can be switched. For details, refer to “External input and output”. Function number Setting value Setting description Factory setting Operation status ♦ 01—08 (Setting prohibited) Error status Indoor unit fan operation status (Setting prohibited) - 44 -...
12-2. Custom code setting for wireless remote controller To interconnect the air conditioner and the wireless remote controller, assignment of the custom code for the wireless remote controller is required. NOTE: Air conditioner cannot receive a signal if the air conditioner has not been set for the custom code.
14. Optional parts 14-1. Controllers Exterior Part name Model name Summary Easy finger touch operation with LCD panel. Backlit LCD enables easy operation in a dark room. Wired Remote UTY-RNRXZ* Wire type: Non-polar 2-wire Controller Optional Communication Kit is necessary for installation. High visibility and easy operation.
14-2. Others Exterior Part name Model name Summary Use to connect with various peripheral devices and air conditioner PCB. External UTY-XWZX Connect Kit Connecting point: CN47 on Main PCB Required when external device is connected. External UTY-XWZXZ5 Connect Kit Connecting point: CN47 on Main PCB Use to connect with external devices and air conditioner PCB.
1. Specifications Type Inverter, Heat pump Model name ROG07KETA ROG09KETA ROG12KETA ROG14KETA Power supply 230 V~ 50 Hz Power supply intake Outdoor unit Available voltage range 198—264 V Starting current Cooling 1,650 1,700 1,680 Airflow rate Heating 1,450 1,470 1,580 Type ×...
2. Dimensions 2-1. Models: ROG07KETA, ROG09KETA, and ROG12KETA Unit: mm 4-M10 hole Pitch of bolts for installation Top view Side view Front view Side view Airflow Drain port Ø42 Bottom view Side view (Valve part) - 51 - 2-1. Models: ROG07KETA, ROG09KETA, and ROG12KETA 2.
2-2. Model: ROG14KETA Unit: mm 4-M10 hole Pitch of bolts for installation Top view Side view Front view Side view Airflow Drain port Ø42 Bottom view Side view (Valve part) - 52 - 2-2. Model: ROG14KETA 2. Dimensions...
3. Installation space 3-1. Models: ROG07KETA, ROG09KETA, ROG12KETA, and ROG14KETA ¢ Space requirement Provide sufficient installation space for product safety. CAUTION Keep the space shown in the installation examples. If the installation is not performed accordingly, it could cause a short circuit and result in a lack of operating performance.
Page 58
Multiple outdoor unit installation • Provide at least 250 mm of space between the outdoor units if multiple units are installed. • When routing the piping from the side of an outdoor unit, provide space for piping. • No more than 3 units must be installed side by side. When 4 units or more are arranged in a line, provide the space as shown in the following ex- ample “When an obstruction in the upper space:”.
Page 59
Outdoor units installation in multi-row Unit: mm Single parallel unit arrangement Multiple parallel unit arrangement 100 or more 200 or more 1,000 or more 2,000 or more 200 or more 400 or more 500 or more 1,000 or more 200 or more 250 or more 1,000 or more...
6. Capacity compensation rate for pipe length and height difference Height difference H Indoor unit is higher than outdoor unit Indoor unit is lower than outdoor unit Outdoor unit Indoor unit Outdoor unit Indoor unit Connection pipe Connection pipe 6-1. Models: ROG07KETA and ROG09KETA NOTE: Values mentioned in the table are calculated based on the maximum capacity.
6-2. Model: ROG12KETA NOTE: Values mentioned in the table are calculated based on the maximum capacity. Pipe length (m) COOLING — — — 0.858 0.868 — — 0.929 0.872 0.882 Indoor unit is higher than outdoor unit *1 — 0.960 0.933 0.876 0.885...
9-2. Sound level check point Rear Microphone Microphone Airflow Side view Rear view NOTE: Detailed shape of the actual outdoor unit might be slightly different from the one illustrated above. - 66 - 9-2. Sound level check point 9. Operation noise (sound pressure)
10. Electrical characteristics Model name ROG07KETA ROG09KETA ROG12KETA ROG14KETA Voltage 230~ Power supply Frequency Max operating current * Starting current Circuit breaker current Power cable Cross- Wiring sectional spec. * Connection area cable * Limited wiring length NOTES: • *1: Maximum operating current is the total current of the indoor unit and the outdoor unit. •...
11. Safety devices Model Type of protection Protection form ROG07KETA ROG09KETA 250 V, 20 A Circuit protection Current fuse (Main PCB) 250 V, 5 A 85—122 °C Activate Fan motor stop Fan motor Terminal protection protection program 77—114 °C Reset Fan motor restart 110 °C Activate...
Need help?
Do you have a question about the RSG07KETF and is the answer not in the manual?
Questions and answers