Troubleshooting
1. Q: I hooked up shore power, but on the screen it shows AC abnormal.
A: If the screen displays "AC abnormal", it may caused by three reasons:
1. The inverter connect to shore power / generator, but the AC input doesn't
in the range which the inverter can be acceptable.
Please use the multimeter to measure the AC input voltage at the AC input
terminal of inverter and check if in the range.
2. If not connect to the shore power, it will displays "AC abnormal" when the
inverter operate under the inverter mode.
3. In battery priority mode, if there is a AC input when the battery power is
sufficient, the AC mains voltage can also be detected, but the display will still
show "AC abnormal".
If it falls into these three situations,
it is normal, because this is what our
software's set up. Thanks.
2. Q: The inverter charger doesn't charge the batteries.
A: If you switched SW5 to 0 (utility priority mode), please make sure that the
following settings are correct:
1. Please switch SW2 to 1 (if you connect to generator) and SW4 to 1 (if
60HZ);
2. Please choose the switch setting of battery type selector according to your
battery type and do not choose 0. The charge current can be adjusted from
0%-100% via a liner switch at the right of the battery type selector, please
make sure it is not 0%.
If you switched SW5 to 1 (battery priority mode), and if the battery voltage is
high/sufficient, the inverter cannot be transferred to the mains for charging, so
the battery is not charged. It won't transferred to the shore power to charge the
battery until the battery voltage is low.
3. Q:I hook up shore power and all setting are correct, but LCD display
shows AC input 0V, cannot charge the battery.
A: It seems the inverter cannot detect the AC input, please use multimeter to
measure the voltage at AC input terminal of inverter and make sure the AC
input voltage is qualified because some models (single phase model) only can
1