Download Print this page
Veris VZ2 Series Installation Manual

Veris VZ2 Series Installation Manual

Zone valve bodies and actuators

Advertisement

Quick Links

Installation Guide
Valves & Actuators
Regulatory Compliance and Safety Information
Electrical equipment should be installed, operated, serviced,
and maintained only by quali ed personnel. No responsibility
is assumed by Veris Industries for any consequences arising
out of the use of this material.
Carefully read these instructions and all information relevant
for this product before trying to install it. Technical literature
and declarations of conformity can be accessed on the Veris
website, www.veris.com.
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION OR
ARC FLASH
• Turn off all power supplying equipment before working on
the equipment.
Failure to follow these instructions will result in
death or serious injury.
NOTICE
RISK OF EQUIPMENT DAMAGE
• Only use manual override when power is off.
Failure to follow these instructions will result in
damage to the gear train or other mechanical damage.
F-28287-1
Page 1 of 4
Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Aerospond, Veris, and the Veris 'V' logo are trademarks or registered trademarks of Veris Industries, L.L.C. in the USA and/or other countries.
Product Overview
VZ2 Series Actuated Control Valves are designed for closed-loop HVAC hydronic heating and cooling systems.
These two-position spring return valves are used with thermostats or BAS to control fluid flow in a fan coil unit,
baseboard heating, or radiant application. The VZ2 Series valves are available in various Cv's and actuator voltages
Veris Industries
Stratford Park 5
of either 24 or 120 VAC.
Telford TF3 3BL
United Kingdom
Product Identification
Size (DN)
VZ2
2 = 1/2"
3 = 3/4"
Accessories for Inverted Flare Connection Valves
3/4" inverted flare bodies accept the following adapters to copper pipe:
Part Number Description
436-220
Union nut and coupling assembly, female for 1/2" (5/8" O.D.) copper, 1-1/16" long
436-252
Union nut and coupling assembly, female for 3/4" (7/8" O.D.) copper, 1-27/32" long
Specifications
System Static Pressure Limits 400 psi (2758 kPa)
Fluid/Ambient Temp. Limits 32 to 200 °F (fluid) @ 104 °F (ambient) (0 to 93 °C @ 40 °C)
Power Requirements 6.5 watts, 7.5 Va
©2023 Veris Industries USA 800.354.8556 or +1.503.598.4564 / support@veris.com
Other companies' trademarks are hereby acknowledged to belong to their respective owners.
VZ2 Series
Zone Valve Bodies and Actuators
Ports
Cv
-
N = NPT
"Zone"
A = 2-position NC = Normally closed
F = Flare
1 = 1
2 = 2.5
3 = 3.5
5 = 5
7 = 7.5
Service Hot and chilled water models, up to 50% glycol
Close-off See table below
Seat Leakage ANSI class IV (0.01%) with pressure at inlet (B-port/A-port, if 3-way)
Body Forged brass
Stem Nickel-plated
Seat Brass
Paddle Buna N
Actuator Voltage 24 Vac @ 50/60 Hz,
120 Vac @ 60 Hz
Actuator Leads 18 in. (0.46 m) wire
Shipping Weight 2.25 lbs (1020 g), actuator/valve assembly
WARRANTY
Limited Warranty 2 years
Control
State
Voltage
A
24 Vac
NO = Normally open
120 Vac
Example:
VZ2
2
N
2
-
A
2-position zone valve, 2-way, 1/2" NPT, 2.5 Cv, 24V,
Normally Closed with Aux Switch
AUX
S
S = SPST
NC
24
S
0823

Advertisement

loading
Need help?

Need help?

Do you have a question about the VZ2 Series and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Veris VZ2 Series

  • Page 1 0823 Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Aerospond, Veris, and the Veris ‘V’ logo are trademarks or registered trademarks of Veris Industries, L.L.C. in the USA and/or other countries. Other companies’ trademarks are hereby acknowledged to belong to their respective owners.
  • Page 2 0823 Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Aerospond, Veris, and the Veris ‘V’ logo are trademarks or registered trademarks of Veris Industries, L.L.C. in the USA and/or other countries. Other companies’ trademarks are hereby acknowledged to belong to their respective owners.
  • Page 3 0823 Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Aerospond, Veris, and the Veris ‘V’ logo are trademarks or registered trademarks of Veris Industries, L.L.C. in the USA and/or other countries. Other companies’ trademarks are hereby acknowledged to belong to their respective owners.
  • Page 4 0823 Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Aerospond, Veris, and the Veris ‘V’ logo are trademarks or registered trademarks of Veris Industries, L.L.C. in the USA and/or other countries. Other companies’ trademarks are hereby acknowledged to belong to their respective owners.

This manual is also suitable for:

Vz22n1Vz22n2Vz22n3Vz23n2Vz23n3Vz23n5 ... Show all