- Accessing control panel by using RS-485 communication module at 1200 meters. Each fire alarm control panel must have ML-1201 Network module in order to establish the connection between GCU and Maxlogic series fire alarm control panels and ML-12XX.N models must be selected.
4.4 Control Panel - GCU Connection GCU can be connected directly to a maxlogic series fire alarm control panel with network card or to a network line consisting of Maxlogic series control panels. The connection of GCU to fire alarm control panel is made via network card. The connections must be made by using 2x0.75 LIHCH FE 180 / PH 120 network cable.
4.5 PC - GCU Connection Specially designed software is used to configure GCU. (More explained in Section-8 GCU Configuration and Putting in Service) Cable connection, between GCU and PC on which the software is installed, is made through the PC socket on control panel front facade.
5 - OUTPUTS After installing supervisor software, connection type and communication module which will be used between control panels and computer (Supervisor) chall be selected. Upon selecting the desired communication module, the appropriate GCU model needs to be supplied. 5.1 RS-232 Output Used for communication between control panel and computer at max.
Cable connection for RS-485 must be made as below: 5.3 TCP/IP Output Used for communication, between control panel and computer on which Supervisor is installed, through internet (LAN or WAN). GCU model must be ML-1207.C which includes MLY-1207.C TCP/IP Module. If computer is in the network, cable connection must be made to Ethernet dipswitch.
Page 8
The connection of TCP/IP and GPRS Modules to computer on which Supervisor Software is installed must be made as shown below. KK-641.015 Rev.No:10 20.04.18 GCU User Manual 8/27...
6 - Buttons and Indicators 6.1 Indicators 6.1.1 GCU Indicators Power On: It shows that GCU operates and the power supply has been properly made. It illuminates “Green” continuously. General Fault: It shows that there has been a fault during normal operating condition of GCU. It illuminates “Yellow” continuously.
7 - Fuses Fuses on MLY-0502 Power supply; 28 V input fuse (F1) The Self-resetting fuse gets activated on 3A current overload and in case of PSU failure. Battery fuse (F2) The Self-resetting fuse gets activated on 1.1A current overload and in case of any failure related to battery input. Batteries becomes disabled.
Page 11
SOCKET ID = 5 RS-232/ RS-232/ TCP/IP GPRS TCP/IP RS-485 RS-485 Module Module Module Module Module GCU Address Module Module Module Module Module Between 1 to 64 Address 1 Address 2 Address 3 Address 15 Address 16 Main Back up Back As indicated above, the communication module with the lowest address in the same SOCKET number is the main and the others are back ups respectibely.
Page 12
Normal Mode Used for control panels and repeater panels. Operating type setting Transparent Used for signal amplifiers which are used to Mode extend the distance. 120R End of line resistor deactivated Used in order to activate 120R End of line setting 120R activated resistor.
8.2 RS-232 / RS-485 Communication Module Settings 8.2.1 RS-232 / RS-485 Communication Module Dipswitch Settings Below settings are made by using the 1 unit of dipswitch which founds on RS-232 / RS-485 Communication Module. (ANNEX-B Figure-12) RS-232/RS-485 Module Address EOL Resistor Module is Module Address activated...
Page 14
Below screen appears. Boud Rate Communication Speed is selected as 19200. Used to create communication back up. (Same socket ID should be selected for every communication Socket ID modules for back up feature.) Save Turn back to main screen while saving all changes. Abort Turn back to main screen without saving the changes if any.
8.3 TCP/IP Communication Module Settings 8.3.1 TCP/IP Communication Module Dipswitch Settings The following settings can be made via dipswitch on TCP/IP Communication module. (ANNEX-B Figure-13) EOL Resistor Module Address Always ‘OFF’ used Position Module Address Module is activated Used to desactivate the module Module is activated Used to activate the module 120R disabled...
Page 16
IP Address This is the IP Address of TCP/IP Communication Module. IP Port No This is the Port number for TCP/IP Communication Module. Subnet Mask “255.255.255.0” shall be entered as standard. Default Gateway This is the IP Address number of the unit which provides internet access. Destination IP Static IP number of computer on which Supervisor Software is installed.
Page 17
Select “custom server” in NAT-Virtual Servers part and assign it a name “supervisor”. After, Enter the IP Address of TCP/IP Module into “server IP Address” part. (In this example, it has been assumed that the TCP / IP Module has the IP Address “192.168.1.2”.
Page 18
After making all settings, the configuration which has been made is to be displayed. In case more than one TCP/IP Communication Module is mounted inside GCU; since each TCP/IP. Module will have different client IPs, it must be defined a unique port for each one (4172, 4173 etc.) and follow the same procedure for modem interfaces and create separate configurations.
8.3.3 TCP/IP Communication Module Connection Settings with Supervisor Software The following screen appears on the screen upon clicking on “Settings” button and selecting “Connection” section from the new coming window. The following settings shall be made for the new appearing window. Allowed IP Addresses Enter Static IP data of GCU Port...
Page 20
Used to desactivate the module Module is Active Used to activate the module 120R disabled EOL Resistor Settings 120R enabled Used to activate 120R EOL Resistor It must always be at this position 8.4.2 GPRS Communication Module Connection Settings with Supervisor Software Run GCU Configuration Software after establishing the connection between computer and GCU.
Page 21
Upload the configuration to GCU by clicking “Configure” button on the main window. Settings for communication through internet: Static IP must have already been defined for both GCU location and PC (Supervisor Software) location. System communication gets realized over Static IPs. All necessary settings must be made on the unit (modem, server/firewall etc.) which is used to connect GCU to internet.
Page 22
In case of using more than 1 TCP/IP Module, a different port (4172, 4173 etc.) must be assigned to each TCP/IP Module in GCU. The same steps must be repeated for each TCP/IP Module. S8.4.3 GPRS Communication Module Connection Settings with Supervisor Software Supervisor program, the "Settings"...
10 - Module Models Product Code Product Description ML-1207.C Maxlogic Intelligent Addressable System GCU, 3A Power supply included, inside B type cabinet, TCP / IP Module included ML-1207.G Maxlogic Intelligent Addressable System GCU Modülü, 3A Power Supply included, inside B type cabinet, GPRS Module included ML-1207.K...