Copyright Statement Please keep the manual properly and operate in strict accordance with all safety and operating instructions in this manual. Please do not operate the system before reading through the manual. Contact the nearest hazardous waste disposal station when the products or components are discarded.
Grid Meter Grid Introduction 1.1 System Introduction TCL-RSL-5B10 (incl.TCL-RL-B10K and TCL-RSL-5K) can be applied in DC-coupled systems (mostly new installation), AC-coupled systems (mostly retrofit) and Hybrid-coupled systems (mostly retrofit, and PV capacity-increase), as the following schemes show: Normal Loads Configuration...
User Manual User Manual 1.2 Operation Modes: There are three basic modes that end users can choose via inverter screen/APP. Electricity Price TIME 1.3 Safety Introduction 1.3.1 Manual Keeping This manual contains important information about operating the system. Before operating, please read it very carefully.
DC side is switched off. Touching the battery outlets is strictly The TCL-RSL-5B10 must not be touched or put into service until 5 minutes prohibited. The inverter can keep a life-threatening voltage even after disconnecting it after it has been switched off...
Do not move the system when it is already connected with battery modules. Secure the system to prevent tipping with restraining straps in your vehicle. The transportation of TCL-RSL-5B10 must be made by the manufacturer or an instructed personnel .
Page 8
User Manual User Manual Accessory- Cable (TCL-RL-B10K) TCL-RL-B5K Communica on cable 2×M5*12 4×M6 Gasket 4×ST6.3*50 Power cable 4×D10*50 1 Mounting Panel × Accessory- Cable (TCL-RL-B5K) Accessory- Cable (TCL-RL-B15K) Communica on cable Communica on cable Power cable(1 Black, 1 Red) Power cable(Black)
Page 9
User Manual User Manual Accessory- Cable (TCL-RL-B20K) Accessory - Mechanical Top cover Power cable(1*Black) Power cable(2*Black) Power cable(1*Black) Accessory - Floor stand support Power cable(2*Red) Power cable(1*Red) Power cable(1*Red) 20~30mm...
Please be cautious unpacking the battery, otherwise components could be damaged. 2.1 Installation Site and Environment 2.1.1 General This TCL-RSL-5B10 energy storage system is outdoor version and can be installed in an outdoor location. When TCL-RSL-5B10 systems are installed in a room, TCL-RSL-5B10 must not be hampered by the structure of the building, the furnishings and equipment of the room.
TCL-RSL-5B10 and the surface of a wall or structure. If the TCL-RSL-5B10 is mounted at a wall or at a distance of 300mm from the wall or the 2.2.1 Battery Installation structure separating it from the habitable space, the distances to other structures or objects must be increased.
Page 13
User Manual User Manual 2.2.2 Inverter Installation NOTE: Step 6 Inverter Installation. The inverter's built-in residual-current monitoring unit (RCMU) removes DC residual current above 6mA, so an external RCD (type A or type B ) can be used with the system (≥30mA)..In additon, the installation of inverter must fulfill AS/NZS 3000,AS/NZS 4777.1 and AS/NZS 5033.the internal N line of converter is connected to grid neutral via internal relays, when in stand-alone mode.
Page 14
User Manual User Manual Step 8 Please make AC cables on site. d. Insert the crimped conductors L, N and PE into the corresponding terminals and tighten the screw with a hex key wrench screw driver(size:2.5, 1.2~2.0 N.m). Ensure that all conductors Step 8-1 Please follow the AC cable requirements below.
Page 15
User Manual User Manual Step 8-2 (8) Use tool to clamp the AC wiring terminal and wire rod; screw the nut, but do not Connect the Backup and Grid cables in advance according to the connector tighten it. Make sure that the cable is free to pass through the waterproof components. mode, and connect them to the Backup and Grid board connectors in turn.
Page 16
User Manual User Manual Step 9 Step10 Connect the BAT communication cable of the cable box from Step 13 to the Connect the power cables of the bottom battery from Step 4 to the sideterminals of the top battery. Make sure that red connects to red and black connects toblack. topmost battery at the right side.
Page 17
If you connect more than 2 battery modules to the system, please only install the additional batteries 3~4 on the side of the system. You can connect up to 4 batteries, 2 each mounted on top of each other, to the TCL-RSL-5B10. NOTE: To do this, carry out the individual installation steps as for the first two batteries,...
Page 18
User Manual User Manual The default state of DRM/RRCR function is disabled. Only when the "DRM enabled" is enabled, the function will be activated according to the specfic grid code(e.g., Australia, The electricity meter should be mounted and connected at the grid transition point Germany or UK) (feed-in point) so that it can measure the grid reference and feed-in power.
User Manual User Manual System Operation Normal Load 3.1 Switch On Hybrid Inverter Back up When turning on the system, it is very important to follow the steps below to prevent Grid Grid Meter Grid Switch damage to the system. PV Switch PV Panels WARNING: Please check the installation again before turning on the system.
When the TCL-RSL-5B10 energy storage system appears to be running abnormally, you can turn 2. If the battery pack is not on fire yet, extinguish the fire before the battery pack catches off...
User Manual User Manual 4.2. Display and Setting Object Description Name 4.2.1 PV1 input display interface Grid connection Interface Off-grid Indicator LED PV1 INPUT Red: The inverter is in fault. PV1 input real-time voltage VOLT: 33.8V PV1 input real-time current Return Button: Escape from current CURR: 0.00A...
Page 22
User Manual User Manual 4.2.5 att ry Prmet r 4.2.9 Load Interface Interface BACKUP DATA BATTERY PRMETER Emergency load (BACKUP) voltage Battery type:(lead acid, LFP battery) VOLT: 0.00V TYPE: LEAD-ACID Emergency load (BACKUP) current Battery temperature CURR: 0.00A TEMP: 0.0℃ Percentage of battery surplus capacity SOC: 4.2.10 Power...
User Manual User Manual 4.2.13 Status information Description Interface Description Interface -USER- Press ESC on the Main Display Interface to enter →1 :SETUP the user interface. 2:INQUIRE 3:STATISTIC See chapter 8.2 for more setting details. 4:FCTRY RESET STATE SYS: ERROR Enter the password before setting up the user.
Page 24
User Manual User Manual 4.3.1 System setting 1.Self-consumption mode disables grid charging: --CHARGE TIME-- Battery pack can only be charged by PV. Description Interface 00:00-23:59 2.Self-consumption mode enables grid charging: Grid MAX SOC:100% This interface is used to access system information. charges battery pack until MAX SOC during set time.
Page 25
User Manual User Manual ④ DRM enable ⑨ GFCICHK ENB Description Description Interface Interface --DRM ENABLE-- - GFCICHK ENB - GFCICHK ENB(1. Disable Enable Only applicable in Australia and New Zealand. →1:DISABLE 1 DISABLE PV leakage protection enable Default option is disabling. →...
Page 26
User Manual User Manual 4.3.2 Battery parameters CT OR METER Description Description Interface Interface CT or meter (1.CT 2.meter): the energy storage inverter -CT OR METER- --BAT SETTING-- supports the connection of three-phase ammeter. This interface is used to select battery parameters. →...
Page 27
User Manual User Manual Lead-acid battery parameter ④ Charge current Description Description Interface Interface Press UP/DOWN button to increase or decrease the This interface is used to select other lead-acid --CHARGE CURR-- --LEAD-ACID -- input figure; battery parameter. Press Enter to move cursor backward, confirm input Press UP/DOWN button to move corresponding →1:FLOAT VOLT INPUT:...
Page 28
User Manual User Manual BAT WAKE-UP BMS DOD Description Description Interface Interface 1.Disable BMS DOD: It will not close the discharge --BMS DOD-- -- BAT WAKE-UP -- Enter the option 1 to enable or disable the function. circuit when BMS discharging to the set SOC. →1:DISABLE →1:ENABLE Enter the option 2 to adjust the value of the time.
Page 29
User Manual User Manual 4.3.3 Grid standard ① Reactive mode Description Description Interface Interface Press UP/DOWN button to move corresponding Press UP/DOWN button to move corresponding --GRID STD-- options. Here are 24 standards for selection, including → 1:China options; 2:Germany Press Enter to confirm the input and enter power factor China, Germany, Australia, Italy, Spain and U.K.
Page 30
User Manual User Manual GRID VOLT MAX ② Grid Power Description Description Interface Interface -GRID MAX- -GRID PERCENT- Press UP/DOWN button to adjust the input figure; Press ENTER button to confirm or ESC button to INPUT: 100% INPUT: 270V Press Enter to confirm the input. cancel the input and return to operation parameters interface;...
Page 31
User Manual User Manual ⑤Freq Max Low INV frequency Description Description Interface Interface -FREQ MAX- Enter option 1 to adjust the maximum frequency of -INV FREQ LOW- the INV. Enter option 2 to adjust the maximum →1: INV -MAX INPUT: frequency of the grid.
Page 32
User Manual User Manual OVER VOLT START OVER FREQ ENABL Description Interface Description Interface Press UP/DOWN to adjust the input figure; -OVER VOLT- -OVER FREQ- Derate power when Frequency over. INPUT: 264V Press Enter to confirm the input. →1:DISABLE The default option is enable. 2:ENABLE ⑧UNDER VOLT OVER FERQ START...
Page 33
User Manual User Manual 4.3.5 485 Address Description Interface Description Interface The function that the power of inverter derates -UNDER FERQ- Press UP/DOWN button to adjust the input figure; -485 ADDRESS- when frequency is too low. Press UP/DOWN to Press ENTER button to confirm or ESC button to INPUT:1 INPUT: 50.50Hz...
Page 34
User Manual User Manual 4.3.9 Date/time 4.3.13 AutoTest Description Interface Description Interface Press UP/DOWN button to adjust the input figure; Press Enter button to move cursor backward, --DATE/TIME-- The Auto test function works only in the Italy grid -- PASSWORD-- confirm input and return to setup interface;...
User Manual User Manual Description Description Interface Interface Threshold setting value: The value set by upper Threshold setting value: The value set by upper OVER VOLT(S1) VACMAX(S1) computer software. computer software. Threshold setting trip time: The trip time set by Set:49.8Hz 100ms Set:253.0V 603s Threshold setting trip time: The trip time set by...
Page 36
User Manual User Manual ③ Firmware Version ⑥ Running records Description Interface Interface Description SN of the fault: Fault warning codes (500 at This interface displays firmware version for ARM --REC (500) -- --FIRMWARE-- utmost)(the latest fault or alarm marked as No.1) 1:F10-1 ARM VER:1.0.0 and DSP of the inverter;...
Page 37
User Manual User Manual ④ The day Description Interface Interface Description This interface is used to select statistics items; Press UP/DOWN button to move corresponding This interface displays power generation for the --E-TODAY-- options; --STAT.-- day(kWh); 0.0KWH Press Enter to enter the selected menu; →1:TIME STAT.
User Manual User Manual 5.3 Inspection before battery recharging Stick Logger Quick Guide Before recharging a battery, check its appearance: Deformation/Shell damage/Leakage 5.4 Recharge Operation Steps Step 1: Scan the QR Code on the right side and download the APP. Step 1:Connect power cables to the battery charger correctly.
User Manual User Manual 6.3 Logger Status READY 6.3.1 Check Indicator light Fault Description Fault Cause Solution READY Lights Implication Status Description(All lights are single green lights.) 1. Light off: Fail to connect to the router. 1. Connection betw- 1.Check the connection between stick 2.
User Manual User Manual 6.5Usage Methods and Notices for Reset Button SOLARMAN Smart APP 6.5.1 Usage methods and key-press descriptions for reset button 7.1 Registration Key-press Status Description Light Status Go to SOLARMAN Smart and register. Click "Register" and create your account here. Short press 1s SMARTLINK rapid networking status.
User Manual User Manual 7.4 Network Configuration Step 2:Connect to AP network Click "Go to connect" and find the right "AP_XXXXX" network (XXXXX refers to logger After the logger is added, please configure the network to ensure normal operation.Go SN).If the password is required, you can find the password on the logger body.Go back to "Plant Details"-"Device List", find the target SN and click "Networking".
User Manual User Manual Alarm Code And Error Code BMS Program Update Fail CT Reverse 8.1 Alarm code Grid VoltLock Fail English description Codes PV off Grid Volt Low System Reset Grid Volt High Grid Frequency Low 8.2 Error Code Grid Frequency High English description Codes...
User Manual User Manual Fault Diagnosis And Solutions Types Codes Solutions The inverter is easy to maintain. When you encounter the following problems, please (1) Check the input mode setting is correct. refer to the Solutions below, and contact the local distributor if the problem remains (2) Disconnect the PV input, restart the inverter and wait PV Input Short unsolved.
Product Specifications (3) Contact the local power company if voltage and frequency are beyond range or unstable. Battery Specifications TCL-RL-B5K TCL-RL-B10K (1) PV is not connected; Electrical Solar Loss (2) Check grid connection;...
Page 46
User Manual User Manual Maximum Continuous Input Current 32Aa.c. Weight (Kg) Maximum Continuous Input Power 7360VA Dimension (W×H×D)mm 540* 0*240 540*1020*240 Maximum Continuous Output Current 16Aa.c. 22Aa.c. 25Aa.c. 0.8 leading ~0.8 lagging IP Protection IP65 Power Factor (Cos phi), Adjustable (0.95 leading ~0.95 lagging for Germany) Warranty 5 Year Product Warranty, 10 Year Performance Warranty...
Page 47
User Manual User Manual Table 10.1 Grid specification (single-phase) Topology High Frequency Isolation Cooling Natural Convection Output Voltage Output Frequency Grid Boot wait time(S) Specification Range (Vac) Range (Hz) Display LCD/APP China 187-252 49.5-50.2 Communication Interface RS485/CAN2.0/WIFI/4G Germany 184-264 47.5-51.5 Max.
User Manual User Manual Routine Maintenance 11.2 Notes After the equipment is out of operation, please pay attention to following notes while maintaining : 11.1 Maintenance Plan Related safety standards and specifications should be followed in operation and Check if wire connections are loose. maintenance.
User Manual Quality Assurance When product faults occur during the warranty period, Company or his partner will provide free service or replace the product with a new one. Evidence During the warranty period, the customer shall provide the product purchase invoice and date.