The catching up of the switching times on restart, time change and unlocking can be set separately for each channel. MDT technologies GmbH · Papiermühle 1 · 51766 Engelskirchen · Germany Telephone: +49 (0) 2263 880 · knx@mdt.de · www.mdt.de...
Page 6
The MDT Time Switch supports “long frames” (longer telegrams). These contain more user data per telegram, which significantly reduces the programming time of the actuators with the ETS. MDT technologies GmbH · Papiermühle 1 · 51766 Engelskirchen · Germany Telephone: +49 (0) 2263 880 · knx@mdt.de · www.mdt.de...
5. Set and programme the individual address in the ETS. (Programming LED turns off) 6. Configure and programme the settings in the application programme. MDT technologies GmbH · Papiermühle 1 · 51766 Engelskirchen · Germany Telephone: +49 (0) 2263 880 · knx@mdt.de · www.mdt.de...
Page 11
Day / Night Status: Lock 1 Bit ■ ■ ■ Table 2: Communication objects – Standard setting: Functions MDT technologies GmbH · Papiermühle 1 · 51766 Engelskirchen · Germany Telephone: +49 (0) 2263 880 · knx@mdt.de · www.mdt.de 11 / 54...
Page 12
The flags assign the communication objects their respective tasks in programming, where C stands for communication, R for read, W for write, T for transmit and U for update. MDT technologies GmbH · Papiermühle 1 · 51766 Engelskirchen · Germany Telephone: +49 (0) 2263 880 · knx@mdt.de · www.mdt.de...
A time must be defined for the function. The time for cyclical sending of the “Slave” should be set the same as the time for cyclical sending of the “Master”. MDT technologies GmbH · Papiermühle 1 · 51766 Engelskirchen · Germany Telephone: +49 (0) 2263 880 · knx@mdt.de · www.mdt.de...
The time switch can output a time cycle and up to 2 cycle programs. The time clock sends a 1 command cyclically (every minute/hour/day) and can be used for synchronization or for executing periodic processes. MDT technologies GmbH · Papiermühle 1 · 51766 Engelskirchen · Germany Telephone: +49 (0) 2263 880 · knx@mdt.de · www.mdt.de...
The display lock can also be activated via the display in the “Settings” - “Display lock” level menu at the device. MDT technologies GmbH · Papiermühle 1 · 51766 Engelskirchen · Germany Telephone: +49 (0) 2263 880 · knx@mdt.de · www.mdt.de 20 / 54...
Page 23
Sending: 1 Public holiday active up to configured return. Automatic mode becomes active again from the next day MDT technologies GmbH · Papiermühle 1 · 51766 Engelskirchen · Germany Telephone: +49 (0) 2263 880 · knx@mdt.de · www.mdt.de 23 / 54...
A list of functions appears, which can be activated individually. When a function is active, a separate sub menu appears for it. MDT technologies GmbH · Papiermühle 1 · 51766 Engelskirchen · Germany Telephone: +49 (0) 2263 880 · knx@mdt.de · www.mdt.de...
■ A function level is displayed on the device when at least one function for this level is active. MDT technologies GmbH · Papiermühle 1 · 51766 Engelskirchen · Germany Telephone: +49 (0) 2263 880 · knx@mdt.de · www.mdt.de 26 / 54...
Must be linked to the status of the actuator to be switched. Table 19: Communication objects – Function: Switch MDT technologies GmbH · Papiermühle 1 · 51766 Engelskirchen · Germany Telephone: +49 (0) 2263 880 · knx@mdt.de · www.mdt.de 27 / 54...
(in the “Time Switch” menu), which is also set to the shift via 2 Bytes. The current setpoint value sent by the controller can be shown on the display via status object. MDT technologies GmbH · Papiermühle 1 · 51766 Engelskirchen · Germany Telephone: +49 (0) 2263 880 · knx@mdt.de · www.mdt.de...
For each of the 8 switching times, you can set the days of the week on which they should be active. MDT technologies GmbH · Papiermühle 1 · 51766 Engelskirchen · Germany Telephone: +49 (0) 2263 880 · knx@mdt.de · www.mdt.de...
Behaviour like Sunday ■ The Time Switch only executes the switching times that are activated exclusively for “Sunday”. MDT technologies GmbH · Papiermühle 1 · 51766 Engelskirchen · Germany Telephone: +49 (0) 2263 880 · knx@mdt.de · www.mdt.de 40 / 54...
Page 41
“Behaviour on holiday active” must be set to “Behaviour like Sunday”. This means that while “Holiday” is active, only the timers that are defined exclusively for Sunday are executed. MDT technologies GmbH · Papiermühle 1 · 51766 Engelskirchen · Germany Telephone: +49 (0) 2263 880 · knx@mdt.de · www.mdt.de...
...” appears. If lock and holiday are active and both are set to “Send lock and fixed value cyclically”, the text “Send value during lock + holiday cyclically every ...” appears. MDT technologies GmbH · Papiermühle 1 · 51766 Engelskirchen · Germany Telephone: +49 (0) 2263 880 · knx@mdt.de · www.mdt.de 42 / 54...
Page 43
■ After unlocking/end of holiday, no action is performed and the time switch remains in its current state. MDT technologies GmbH · Papiermühle 1 · 51766 Engelskirchen · Germany Telephone: +49 (0) 2263 880 · knx@mdt.de · www.mdt.de 43 / 54...
Use buttons 2 and 3 to select the corresponding category and press button 4 to call it up. All functions assigned to this category appear there: MDT technologies GmbH · Papiermühle 1 · 51766 Engelskirchen · Germany Telephone: +49 (0) 2263 880 · knx@mdt.de · www.mdt.de...
Page 48
Important: In this level, the display remains active (does not switch to standby) until you leave the level. MDT technologies GmbH · Papiermühle 1 · 51766 Engelskirchen · Germany Telephone: +49 (0) 2263 880 · knx@mdt.de · www.mdt.de 48 / 54...
Page 49
Use buttons 2 and 3 to select the desired setting for time, holiday and reset. Press button 4 to switch to the corresponding level. Press button 1 to switch to the higher level. MDT technologies GmbH · Papiermühle 1 · 51766 Engelskirchen · Germany Telephone: +49 (0) 2263 880 · knx@mdt.de · www.mdt.de...
Page 50
Press button 1 to reset all changes at the Time Switch and the settings made in the ETS are referred to. MDT technologies GmbH · Papiermühle 1 · 51766 Engelskirchen · Germany Telephone: +49 (0) 2263 880 · knx@mdt.de · www.mdt.de...
Page 51
If holiday and “behaviour like Sunday” If public holiday and “behaviour like Sunday” Table 38: Legend – Symbols in the display MDT technologies GmbH · Papiermühle 1 · 51766 Engelskirchen · Germany Telephone: +49 (0) 2263 880 · knx@mdt.de · www.mdt.de 51 / 54...
V1.0 First version of the manual DB V2.0 04/2021 V1.1 Adaptations to new database, extension of languages DB V2.1 05/2024 MDT technologies GmbH · Papiermühle 1 · 51766 Engelskirchen · Germany Telephone: +49 (0) 2263 880 · knx@mdt.de · www.mdt.de 54 / 54...