Terminal ES07 Communication CAN 2.0/RS485 SOC display 4LED(25%,50%,75%, 100%) install Floor mount Dimension 680*152*430 680*152*810 680*152*1190 680*152*1570 W*D*H (mm) Weight (kg) 93.5 184.5 Humidity 5%~95%RH Altitude m ≤2000 IP Rating of IP65 Enclosure Certificate IEC 62619/EMC/UN38.3/CE Extensibility Up to 8 systems can be used in parallel...
LES-LV-5K battery packge LES-LV-5K x 1 LES-LV-5K Base package LES-LV-5K Base x 1 ① 2M black external communication cable (RJ45 – M19) ② 2M yellow-green grounding cable (8AWG) ③ ④ 2M DC+ red external power cable (2AWG/100A 1AWG/200A) 2M DC- black external power cable (2AWG/100A 1AWG/200A) ⑤...
battery Recommended charge instructions: Charge the battery at constant current 50A until voltage reaches 58.4V, then charge at constant voltage 58.4V till charge cur rent is 5A. ① When the battery is shut down, press the button (3~6S) to release, and the battery is active and power on, the LED indicator from "RUN"...
SAFETY DESIGN 1.The battery system cannot be turned on if the battery is incomplete or is not instaled properly.2. The system will automatically shut down if the battery does not communicate with the inverter for 24 hours . 3.The system will automatically shut down if the battery or inverter installation error . 4.The battery voltage is too low and the low voltage alarm is triggered, after the operation for 30 seconds, the system will automatically turn off into hibernation and maintain the low power consumption state;...
4. Regulations vary for different countries. Dispose of in accordance with local regulation. Corporate name:LEDVANCE GmbH Company address: Steinerne Furt 6286167 Augsburg Germany Contact Information: Krzysztof Rytel +48 734 134 386 k.rytel@ledvance.com...