IMPORTANT—PLEASE READ
The TPD-CAT6 comes with terminals for hard ground (GRD) and a shield/
floating ground (SHD). For the lowest impedance ground, always connect the
ground wire to the hard ground terminal/GDR.
If the building has a presence of excessive noise or voltage on the ground,
upon installation of the suppressor poor data speed/signal degradation may
occur. To check if the degradation is due to the presence of noise or voltage on
the ground, simply disconnect the ground wire on the TPD-CAT6 and see if the
speed/signal issue improves. If it does, try connecting the ground to the shield/
floating ground (SHD) terminal. That should make the problem disappear. If it
does not, install the TPD-GTGW (Gas Tube Ground Wire) which is a 10-inch
ground wire with a built-in noise isolator in series with your ground connection.
This should eliminate the problem. Consider purchasing a few TPD-GTGW
units to have ready to use in case of any communication issues. If you have
multiple units at one location, only one TPD-GTGW is needed on the final
ground connection.
WARRANTY STATEMENT
During the applicable warranty period, any Transient Protection Design™
device which fails due to defect in materials, workmanship, or any transient
event, including lightning, shall be repaired or replaced at TPD's discretion
without charge. In the event of a return the device must be shipped FOB TPD
place of business within the applicable warranty period. The applicable
warranty period for the TPD surge protective device is outlined below in the
Warranty Period section. The warranty period for any repaired devices or
replacement devices will be only the remaining portions of the original limited
warranty.
A Return Material Authorization (RMA) number must be obtained from the
Company's Customer Service department before returning any Products.
The Company shall have no liability under this warranty for problems or defects
directly or indirectly caused by misuse of the Product, alteration of the Product
(including removal of any warning labels), accidents, improper installation,
application, operation or improper repair of the Product.
THIS WARRANTY REPRESENTS THE ENTIRE WARRANTY OF THE
COMPANY. ALL OTHER WARRANTIES EXPRESS OR IMPLIED, ORAL OR
WRITTEN, INCLUDING, BUT NOT LIMITED TO, THE WARRANTIES OF
MERCHANT ABILITY AND FITNESS FOR A PARTICULAR PURPOSE ARE
HEREBY DISCLAIMED.
The liability of the Company, at its sole option, under this warranty is expressly
limited to the replacement or repair of the defective part thereof. IN NO EVENT
SHALL THE COMPANY BE LIABLE OR RESPONSIBLE FOR SPECIAL,
INCIDENTAL, OR CONSEQUENTIAL DAMAGES OF ANY KIND OR
CHARACTER, NOR SHALL ITS LIABILITY EVER EXCEED THE PURCHASE
PRICE PAID TO COMPANY FOR SUCH DEFECTIVE PRODUCT.
This warranty is not transferable and may only be enforced by the original end
user. Claims under this warranty must be submitted to Transient Protection
Design within thirty (30) days of discovery of any suspected product defect.
Model #
TPD-CAT6 Series
Three Years Unlimited Free Replacement
Need additional assistance?
Call Technical Support at 1-717-436-2856 or visit
www.TransientProtectionDesign.com
Warranty Period
ENCLOSURE DIMENSIONS FOR TPD-CAT6
2.28"
57.9mm
3.94"
100mm
AC breaker panel protection is recommended when using data
NOTE 1:
protection. Data protection diverts or dumps excess energy from data lines into
the power grounding system. By strategically protecting branch breaker panels
with the TPX, surge events will once again be equalized and safely contained at
the breaker panel.
SAVE THESE INSTRUCTIONS
Note: If devices are received damaged, notify the shipping company
immediately. Retain containers and packing materials for inspection.
CAUTION—IMPORTANT SAFETY INFORMATION
Never install surge suppression during a lightning storm.
This product is for INDOOR USE ONLY. INSTALL IN WEATHERPROOF
ENCLOSURE FOR OUTDOOR USE.
The below suppressors are intended for use as protectors for low voltage signal,
data and communication lines.
Read and understand all instructions prior to installation and operation.
Model # TPD-CAT6 Series
Protect 8 wire Ethernet RJ45 Connections with data max data rate at 1 Gbps.
INSTALLATION
1. Unit is Bidirectional. Not In/Out Sensitive. Check unit label for proper
installation.
2. To protect Ethernet switch/hub or equipment end of cable install unit in front
of the equipment you wish to protect and ground to power source feeding
equipment. Install with minimum 12" leads between unit and equipment.
GROUNDING
3. Connect an AWG # 14 ground wire from one of the unit's ground terminals
which are located on either side of the unit, and secure it to the nearest
available electrical system ground. The unit's ground lug must be connected to
the ground AC reference used by the system being protected. In some
environments, this ground point may be the ground bar in the AC power panel
or low voltage equipment electrical ground.
© 2023 Transient Protection Design. All Rights Reserved. This document is the property of Transient Protection Design.
5" Inch
1.25"
pigtail
31.7mm
attached to
TPD-CAT6
model
1.25"
31.7mm

Advertisement

loading
Need help?

Need help?

Do you have a question about the TPD-CAT6 Series and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for TPD TPD-CAT6 Series

  • Page 1 TPD’s discretion immediately. Retain containers and packing materials for inspection. without charge. In the event of a return the device must be shipped FOB TPD place of business within the applicable warranty period. The applicable CAUTION—IMPORTANT SAFETY INFORMATION...
  • Page 2 For new installs or high TPD-PHONE-RJ lightning exposure areas we recommend that an additional ground wire to be run from the originating AC system feeding Ethernet to the TPD-CAT6 series TPD-CAT6 or TPD-CAT6-POE located at the remote end.

This manual is also suitable for:

Tpd-cat6Tpd-cat6-poe