GPS 10 Installation Installation must be in accordance with BS 5410 or any local building regulations. Connect the suction line from the main tank to the ‘inlet’, and the “outlet” supply pipe (‘gravity fed’) to the appliance. Connect the overflow facility (*). If your pipe is in PVC or copper you are required to use a 10mm pipe insert at any junction that has a compression fitting.
Troubleshooting and maintenance When under automatic function the vibration noise level is high or not stable, this could indicate that you have air entering the pump: Check suction line vacuum tightness, tube size, and distances related to suction limits of your GPS If the oil does not come up to the GPS 10: - Check suction pipe for blockage and/or vacuum tightness.
6. Accessories – Leak detection system Oil tray with leak detection system An oil tray with an infrared leak detection system is included in your GPS 10. How does the leak detection system function Once installed, the function of your GPS remains unchanged, unless some liquid at the infrared probe activates the leak alarm, or any damage occurs to the probe.
8. Installation examples GPS 10 GPS 10 BURNER Overflow BURNER connection TRAY Suction line TRAY Important: The Oil lifter requires a dedicated suction line from the oil storage tank, this will prevent any fuel starvation from any other appliance on the same suction line. For outdoor use, a weather-proof protective cabinet must be used for the GPS 10.
9. Display quick reference list Normal Operation Status: Pump filling GPS 10 Oil Lifter is powered No Power Supply GPS reservoir Oil level in lifter reservoir has reached stop level. It keeps this state till low level is reached again, or start button Alarm Status: Leak detection alarm Very low level is reached...