D21-TSSR (PCB color blue) (FW THF-1906 and newer) Safety features: 1- SSR+ output is short protected, short current 60mA max. 2- Low air-flow modulation/shut-off: If the heater's air-flow sensor senses a temperature higher than 44°C (111°F) threshold, the output's pulse width will be reduced from the actual down to zero (at approximately 51°C threshold),...
Page 2
If the normal air-flow condition is reinstated within that 60 seconds, the controller goes back to normal operation and the yellow (or red) light turns OFF. If the normal air-flow condition does NOT come back within the 60 second timeframe, the yellow (or red) Warning LED light begins to flash with a pattern of 1-second ON and 2-seconds OFF, and the controller switches off the SSR output (i.e.
Page 3
After 1 minute with Full ON, the controller turns OFF the elements and the yellow (or red) warning LED light flashes with a pattern of 1-second ON and 2-seconds OFF. 4. To put to normal operation: Remove the short, connect back the air-flow sensor and then turn controller's power off and on (to reset).