Contents Contents About this document ................3 Safety and disposal ................4 Product-specific information ..............4 Disposal ....................7 Intended use ..................7 Product description ................8 Overview ....................8 First steps ................... 10 Switching the instrument on and off ............. 10 Evacuation with a manifold ..............
1 About this document 1 About this document • The instruction manual is an integral part of the instrument. • Pay particular attention to the safety instructions and warning advice in order to prevent injury and damage to the product. •...
Product-specific information To prevent personal injury, please read the operating manual carefully. • The testo 565i vacuum pump may only be used by qualified personnel with the appropriate qualifications and in accordance with local regulations. • Wear goggles when working with refrigerants.
Page 7
2 Safety and disposal During maintenance work, the employer must ensure that a hazardous explosive atmosphere is prevented (see also TRBS1112, TRBS2152 VDMA 24020-3). A hazardous and potentially explosive atmosphere must be anticipated during maintenance and repair work on refrigeration systems with flammable refrigerants (e.g.
Page 8
2 Safety and disposal WARNING For model 0564 6562 01 and 0564 6563 01: This product is for use on a nominal 120 V circuit and has a grounding plug similar to the plug illustrated in sketch A in the figure below. Only connect the product to an outlet having the same configuration as the plug.
• WEEE Reg. No. DE 75334352 3 Intended use The testo 565i vacuum pumps is intended to be used in the refrigeration service including CFC, HCFC, and HFC refrigerants (such as R12/R22/R23/R32/R134A/1234yf and so on), Printing lndustry vacuum packaging, Gas Analysis, Thermo Forming industry and so on. lt can also be applied as the pre-pump of various types of high vacuum equipment.
4 Product description 4 Product description Overview 1 Power switch 2 Nameplate 3 Handle 4 Inlet fitting 5 Oil fill cap 6 Exhaust fitting 7 Oil housing 8 Sight glass 9 Oil drain plug 10 Base 11 Motor 12 Fan cover...
Page 11
4 Product description Symbol explanation Observe operating instructions ATTENTION Magnetic field Damage to other devices! - Keep a safe distance from products that can be damaged by magnetism (e.g. monitors, computers, credit cards). WARNING Magnetic field May be hazardous to the health of pacemaker wearers. - Keep a minimum distance of 15 cm between the pacemaker and the device.
CAUTION Danger of oil spillage in case of fast filling. - Fill in the oil slowly. Switching on testo 565i Turn the motor switch to ON position. This may takes 2 to 30 seconds depend on the ambient temperature.
Page 13
5 First steps The oil level should always be visible in the middle between Max and Min mark when the pump is running. lnsufficient oil filled will result in poor vacuum performance. Excessive of oil can result in overflowing of oil from the exhaust fitting.
Establish a Bluetooth connection between manifold and testo Smart App. All configurations are done via the manifold. The testo Smart App is operating in second screen mode. All measurement values from the installation aid are mirrored in the testo Smart App.
Page 15
5 First steps Enter the desired vacuum target values in the manifold and activate Auto Re-Start function if required (value higher than 0). Auto Re-Start function: Once the target value has been reached, the pump is reactivated and the vacuum hold test is performed.
Page 16
5 First steps When the target values are reached, the evacuation and therefore also the pump are stopped automatically. The vacuum hold test begins. If the Auto Re-Start function has been activated, evacuation is restarted in order to restart the vacuum hold test once the target value has been reached.
Page 17
5 First steps The measurement data is transferred to the testo Smart App and evaluated there.
5 First steps Direct Evacuation Connect testo 565i and testo 552i to the refrigeration circuit. Establish a Bluetooth connection between testo 552i and testo 565i. Establish a Bluetooth connection between testo 565i and testo Smart App.
Page 19
5 First steps Enter the desired vacuum target values in the testo Smart App. Activate/deactivate the Auto Re- Start function to repeat the evacuation and vacuum hold test after the target value has been reached. By entering the maximum number of repetitions, you determine the number of automatic evacuations/vacuum hold tests.
Page 20
5 First steps Start evacuation with Start. The pump starts automatically and the measurement begins. The measurement is running, the vacuum holding test has not yet started.
Page 21
5 First steps When the target values are reached, the evacuation and therefore also the pump are stopped automatically. The vacuum hold test begins. The vacuum hold test can be ended via Stop. If the Auto Re-Start function has been activated, evacuation is restarted in order to restart the vacuum hold test once the target value has been reached.
Page 22
5 First steps The measurement data is transferred to the testo Smart App and evaluated there.
6 Maintenance 6 Maintenance Cleaning instruments Do not use any aggressive cleaning agents or solvents! Mild household cleaning agents and soap suds may be used. > If the instrument housing is dirty, clean it with a damp cloth. Keeping connections clean >...
6 Maintenance Changing pump oil Ensure the pump is warmed up. Remove the oil drain plug. Drain off contaminated oil into a container and dispose it properly. Oil can be removed from the pump by opening the inlet and partially blocking the exhaust with a cloth while the pump is running.
7 Technical data 7 Technical data Version 7 CFM Feature Value Model no. 0564 5652 01 0564 5652 Voltage 120 V~ / 60 Hz 230 V~ / 50 Hz Rated current 3.3 A 1.9 A Max. current 8.5 A 4.8 A Power 805 W 800 W...
Order no. testo 552i – App-controlled wireless vacuum probe 0564 2552 Vacuum pump oil 330 ml 0564 1002 For a complete list of all accessories and spare parts, please refer to the product catalogues and brochures or visit our website www.testo.com.
9 Support 9 Support You can find up-to-date information on products, downloads and links to contact addresses for support queries on the testo website at: www.testo.com. Trouble shooting Problem Possible reason Actions - Fasten the intake port cap Fail to attain...
Please restart the vacuum pump. If the error continues to occur, please contact Testo Service. Vacuum pump overheats The vacuum pump testo 565i has stopped evacuation because the motor overheated. As soon as the motor has cooled down, you can restart the evacuation via the vacuum pump.
Page 29
2. please check whether the testo 552i has sufficient battery capacity. If not, please replace the batteries. If you have any questions please contact your local dealer or the Testo Customer Service. You can find contact details on the back of this document or online at www.testo.com/service-contact.
Need help?