Operation & Maintenance Manual – Sertus Pod ™ OM / RMP-R MAX / 24.03.22 VERSION Contents – Sertus Pod Max Control Panel ....................... Overview ......................Description ..................System Specification ....................System Operation ....................System Idle ..........FIRE Mode (No Faults on Initialisation) ..........
Page 3
Operation & Maintenance Manual – Sertus Pod ™ OM / RMP-R MAX / 24.03.22 VERSION Contents – Sertus Pod Max Control Panel (cont.) ................. BMS Outputs (if selected) ....................System Active ....................System Faults ................. Main PLC Inputs/Outputs ......................Inputs ......................
Page 4
Contact Transfer Time ................Operating Transfer Time ................. Total Operating Time ................. Return Transfer Time ....................... Off Time ....................Normal Operation ....................System Idle ..............State 1 – Non-Generator Mode Sertus Ltd, Europa House, Cranleigh, Surrey, GU6 8NQ hello@sertus.uk 01483 269 999...
The Sertus Pod Max is a single-shaft smoke extraction system designed to integrate with either the Sertus Multi-Zone System or a third-party fire system. When a fan start signal is received from the fire panel the system will run the smoke extraction fans accordingly by means of a duty and standby Inverter motor drive.
The measured Battery voltage is displayed at the bottom of the System Idle Screen. The displayed example represents 23.25V DC. The set running speed for the system can be checked by pressing the ‘down’ cursor key of the Sertus PLC. The PLC DISPLAY will show the following; Setback 00000Hz Speed 1 00000Hz...
On receiving a Fan Start input from either the Sertus Multi-Zone System or a third-party fire system the Sertus Pod will initiate in MOE mode and run the Duty Fan at the speed set in DR51. When the system is in this state the System Running BMS Output will activate and the panel mounted LEDs will be as follows: –...
Page 10
This operation can be initiated when the Sertus Pod is idle or running in MOE mode. On receiving an Off input from either the Sertus Multi-Zone System or a third-party fire system the Sertus Pod will stop the Duty Fan. This mode CANNOT be overridden.
Page 11
This operation is only active when the Sertus Pod is running in MOE mode. On receiving a Pressure Switch input from either the Sertus Multi-Zone System or a third-party fire system the Sertus Pod will run in Pressure Switch mode and run the Duty Fan at the speed set in DR50.
System On – ON – System Running – ON – System Fault – ON The PLC DISPLAY will show the following: Standby Inverter No 1 Extraction Fan Then: Offline Active Sertus Ltd, Europa House, Cranleigh, Surrey, GU6 8NQ hello@sertus.uk 01483 269 999...
Page 13
This allows the system to continue to operate as per the System Input commands. Note: The PLC Display messages work on a priority system and, therefore, the most important message will be shown even if others are activated within the program. Sertus Ltd, Europa House, Cranleigh, Surrey, GU6 8NQ hello@sertus.uk 01483 269 999...
The system monitors for both under and overcurrent on the Duty and Stand-By fans whilst running. These levels are to be set relative to the fan type/size installed within the Sertus Pod. Four settings are available that cover the following fan specifications: –...
Press ↓ To Stop Automatic Transfer Switch Monitoring The internal ATS is monitored by the Sertus Pod PLC. If the ATS goes into fault then the system will initiate the General Fault BMS output (if selected). The PLC DISPLAY will show the following:...
If the PSU fails the system will initiate the General Fault and Control Voltage Fault BMS outputs (if selected). The PLC DISPLAY will show the following: Control Voltage Failed Batteries Active BATT 00000V Sertus Ltd, Europa House, Cranleigh, Surrey, GU6 8NQ hello@sertus.uk 01483 269 999...
On reaching the desired high set point the cabinet fans run until the temperature has risen sufficiently to switch said fans off. The PLC DISPLAY will show the following: Cabinet Thermal Warning Excess Temp Sertus Ltd, Europa House, Cranleigh, Surrey, GU6 8NQ hello@sertus.uk 01483 269 999...
Duty Fault: This is enabled in the following circumstances: – Any Duty Inverter communications, power or motor over/under current fault when idle or running Sertus Ltd, Europa House, Cranleigh, Surrey, GU6 8NQ hello@sertus.uk 01483 269 999...
24VDC Input 8 x DC Input 4 x DC RS 485 DC 24V Input 4 x 0... 10vdc Lovato Lovato -PLC1 EXT-1 Output 4 x relay/8A Output relay/8A Sertus Ltd, Europa House, Cranleigh, Surrey, GU6 8NQ hello@sertus.uk 01483 269 999...
DR3E Pressure Switch Delay (Default set to 00005 = 5 seconds) Sets the time, in seconds, between the pressure switch input becoming inactive and the fan speed returning to MOE mode Sertus Ltd, Europa House, Cranleigh, Surrey, GU6 8NQ hello@sertus.uk 01483 269 999...
Page 22
Sets the speed, in HZ, at which the fan will run when in MOE DR52 Boost Fan Running Speed (Default set to 05000 = 50Hz or 100%) Sets the speed, in HZ, at which the fan will run when in Boost Sertus Ltd, Europa House, Cranleigh, Surrey, GU6 8NQ hello@sertus.uk 01483 269 999...
Operation & Maintenance Manual – Sertus Pod ™ OM / RMP-R MAX / 24.03.22 VERSION Control Panel Inverter Information Reference Pages Sertus Ltd, Europa House, Cranleigh, Surrey, GU6 8NQ hello@sertus.uk 01483 269 999...
Page 24
Operation & Maintenance Manual – Sertus Pod ™ OM / RMP-R MAX / 24.03.22 VERSION Control Panel Sertus Ltd, Europa House, Cranleigh, Surrey, GU6 8NQ hello@sertus.uk 01483 269 999...
Page 25
Operation & Maintenance Manual – Sertus Pod ™ OM / RMP-R MAX / 24.03.22 VERSION Control Panel Sertus Ltd, Europa House, Cranleigh, Surrey, GU6 8NQ hello@sertus.uk 01483 269 999...
Note: If you enter one of the parameters but do not change the value, when the ‘ENT’ (11) button is pressed display will show the next parameter available. Sertus Ltd, Europa House, Cranleigh, Surrey, GU6 8NQ hello@sertus.uk 01483 269 999...
Press the ‘OK’ button, the screen will display “STOP PROGRAM”, make sure the cursor is on “YES” and press ‘OK’. Now scroll to the DATA REGISTERS menu item and press ‘OK’. Sertus Ltd, Europa House, Cranleigh, Surrey, GU6 8NQ hello@sertus.uk 01483 269 999...
Page 28
Once you have changed the value, press ‘OK’. This will save the new value to the register. Now press escape to return to the main menu. Make sure to “RUN” the program, using the same method that was used to “STOP” the program. Sertus Ltd, Europa House, Cranleigh, Surrey, GU6 8NQ hello@sertus.uk 01483 269 999...
Once you have changed the time and date, press ‘OK’ to save changes. Now press ‘ESC’ to return to the main menu/ home screen. Sertus Ltd, Europa House, Cranleigh, Surrey, GU6 8NQ hello@sertus.uk 01483 269 999...
SYSTEM SYSTEM FAULT RUNNING Sertus – Europa House – Alfold Road – Cranleigh – GU6 8NQ – Tel: 01483 269999 – www.trustSertus.com System On This is enabled in the following circumstances: – The System is able to operate as required (PLC set to run)
As part of our continuous improvement processes, Elta reserves the right to make Printed 13/12/2021 16:29:20 changes in design or specification to products without notice. Sertus Ltd, Europa House, Cranleigh, Surrey, GU6 8NQ hello@sertus.uk 01483 269 999 Page 5 of 18...
Page 32
Printed 13/12/2021 16:29:20 changes in design or specification to products without notice. changes in design or specification to products without notice. Page 6 of 18 Page 6 of 18 Sertus Ltd, Europa House, Cranleigh, Surrey, GU6 8NQ hello@sertus.uk 01483 269 999...
Page 33
As part of our continuous improvement processes, Elta reserves the right to make Printed 13/12/2021 16:29:21 changes in design or specification to products without notice. Page 7 of 18 Sertus Ltd, Europa House, Cranleigh, Surrey, GU6 8NQ hello@sertus.uk 01483 269 999...
Page 34
Printed 13/12/2021 16:29:21 changes in design or specification to products without notice. changes in design or specification to products without notice. Page 8 of 18 Page 8 of 18 Sertus Ltd, Europa House, Cranleigh, Surrey, GU6 8NQ hello@sertus.uk 01483 269 999...
Page 35
As part of our continuous improvement processes, Elta reserves the right to make Printed 13/12/2021 16:29:22 changes in design or specification to products without notice. Page 9 of 18 Sertus Ltd, Europa House, Cranleigh, Surrey, GU6 8NQ hello@sertus.uk 01483 269 999...
Page 36
Printed 13/12/2021 16:29:22 changes in design or specification to products without notice. changes in design or specification to products without notice. Page 10 of 18 Page 10 of 18 Sertus Ltd, Europa House, Cranleigh, Surrey, GU6 8NQ hello@sertus.uk 01483 269 999...
Page 37
As part of our continuous improvement processes, Elta reserves the right to make Printed 13/12/2021 16:29:23 changes in design or specification to products without notice. Page 11 of 18 Sertus Ltd, Europa House, Cranleigh, Surrey, GU6 8NQ hello@sertus.uk 01483 269 999...
Page 38
Printed 13/12/2021 16:29:23 changes in design or specification to products without notice. changes in design or specification to products without notice. Page 12 of 18 Page 12 of 18 Sertus Ltd, Europa House, Cranleigh, Surrey, GU6 8NQ hello@sertus.uk 01483 269 999...
Page 39
As part of our continuous improvement processes, Elta reserves the right to make Printed 13/12/2021 16:29:24 changes in design or specification to products without notice. Page 13 of 18 Sertus Ltd, Europa House, Cranleigh, Surrey, GU6 8NQ hello@sertus.uk 01483 269 999...
Page 40
Printed 13/12/2021 16:29:24 changes in design or specification to products without notice. changes in design or specification to products without notice. Page 14 of 18 Page 14 of 18 Sertus Ltd, Europa House, Cranleigh, Surrey, GU6 8NQ hello@sertus.uk 01483 269 999...
Page 41
As part of our continuous improvement processes, Elta reserves the right to make Printed 13/12/2021 16:29:25 changes in design or specification to products without notice. Page 15 of 18 Sertus Ltd, Europa House, Cranleigh, Surrey, GU6 8NQ hello@sertus.uk 01483 269 999...
Page 42
Printed 13/12/2021 16:29:25 changes in design or specification to products without notice. changes in design or specification to products without notice. Page 16 of 18 Page 16 of 18 Sertus Ltd, Europa House, Cranleigh, Surrey, GU6 8NQ hello@sertus.uk 01483 269 999...
Page 43
As part of our continuous improvement processes, Elta reserves the right to make Printed 13/12/2021 16:29:26 changes in design or specification to products without notice. Page 17 of 18 Sertus Ltd, Europa House, Cranleigh, Surrey, GU6 8NQ hello@sertus.uk 01483 269 999...
Page 44
Printed 13/12/2021 16:29:26 changes in design or specification to products without notice. changes in design or specification to products without notice. Page 18 of 18 Page 18 of 18 Sertus Ltd, Europa House, Cranleigh, Surrey, GU6 8NQ hello@sertus.uk 01483 269 999...
A variation in the power supply characteristics which signals the ATS to operate when a deviation from the specified limits occurs. Voltage Supply Deviation Change or loss of voltage of the normal power supply. – Phase loss – Phase sequence – Asymmetry Sertus Ltd, Europa House, Cranleigh, Surrey, GU6 8NQ hello@sertus.uk 01483 269 999...
– The contact transfer time excluding any purposely introduced time is < 1.0 seconds Total Operating Time Sum of the operating transfer and any purposely introduced time delay. Sertus Ltd, Europa House, Cranleigh, Surrey, GU6 8NQ hello@sertus.uk 01483 269 999...
When the Primary Supply becomes healthy again the ‘Return to Primary’ delay timer, set in DR04, becomes active and, once this time settable period is complete, the ATS will release the Secondary contactor and activate the Primary contactor. Sertus Ltd, Europa House, Cranleigh, Surrey, GU6 8NQ hello@sertus.uk 01483 269 999...
Primary supply become healthy for the time period set in DR01 the Secondary contactor will release and the Primary contactor will activate. When the system is in this state the panel mount LEDs are as follows: – Fault Lamp – OFF Sertus Ltd, Europa House, Cranleigh, Surrey, GU6 8NQ hello@sertus.uk 01483 269 999...
If the ATS PSU fails while either the Primary or Secondary supplies are active the fault lamp will activate. This can be inhibited by setting DR12 to 1 if required. Sertus Ltd, Europa House, Cranleigh, Surrey, GU6 8NQ hello@sertus.uk 01483 269 999...
ATS is in any state other than the ‘Primary Active Position’, will reset the system as if the panel has been powered down and then on again. Sertus Ltd, Europa House, Cranleigh, Surrey, GU6 8NQ hello@sertus.uk...
If the generator times out the system will return to primary and the fault lamp will activate. If the Secondary contactor fails the system will return to primary and the fault lamp will activate. Sertus Ltd, Europa House, Cranleigh, Surrey, GU6 8NQ hello@sertus.uk...
If the Primary Supply is Healthy & Active (DR08 set to 1) System Outputs (Volt Free Contacts): General Fault General Fault Pri’ Supply Hea/Act Pri’ Supply Hea/Act Sec’ Supply Hea/Act Sec’ Supply Hea/Act Sertus Ltd, Europa House, Cranleigh, Surrey, GU6 8NQ hello@sertus.uk 01483 269 999...
The delay time set before the ‘BMS System Fault’ and ‘Changeover Healthy’ outputs activate DR12 PSU/Battery Monitoring Inhibit (Default set to 00001) Sets the system to ignore ANY PSU/Battery monitoring inputs Sertus Ltd, Europa House, Cranleigh, Surrey, GU6 8NQ hello@sertus.uk 01483 269 999...
“STOP”. Press the ‘OK’ button, the screen will display “STOP PROGRAM”, make sure the cursor is on “YES” and press ‘OK’. Sertus Ltd, Europa House, Cranleigh, Surrey, GU6 8NQ hello@sertus.uk 01483 269 999...
Page 56
Press the ‘SELECT’ button. Each digit can now be changed by scrolling left and right and cycling through values 1–9 using the up and down arrows. Sertus Ltd, Europa House, Cranleigh, Surrey, GU6 8NQ hello@sertus.uk 01483 269 999...
Page 57
Once you have changed the value, press ‘OK’. This will save the new value to the register. Now press escape to return to the main menu. Make sure to “RUN” the program, using the same method that was used to “STOP” the program. Sertus Ltd, Europa House, Cranleigh, Surrey, GU6 8NQ hello@sertus.uk 01483 269 999...
Once you have changed the time and date, press ‘OK’ to save changes. Now press ‘ESC’ to return to the main menu/ home screen. Sertus Ltd, Europa House, Cranleigh, Surrey, GU6 8NQ hello@sertus.uk 01483 269 999...
Operation & Maintenance Manual – Automatic Transfer Switch OM / RMP-R MAX / 24.03.22 VERSION Voltage Monitor Voltage Monitoring Series SM 501: Sertus Ltd, Europa House, Cranleigh, Surrey, GU6 8NQ hello@sertus.uk 01483 269 999...
Operation & Maintenance Manual – Automatic Transfer Switch OM / RMP-R MAX / 24.03.22 VERSION Frequency Monitor Frequency Monitoring Series PD 225: Sertus Ltd, Europa House, Cranleigh, Surrey, GU6 8NQ hello@sertus.uk 01483 269 999...
The Secondary Supply is available and both the Secondary Frequency and Voltage monitors are healthy Secondary Active This is enabled in the following circumstance: – The Secondary contactor has activated Sertus Ltd, Europa House, Cranleigh, Surrey, GU6 8NQ hello@sertus.uk 01483 269 999...
This is enabled in the following circumstances: – PSU fault – Battery Connection Fault – Secondary Not Healthy (in Non-Generator Mode) – Primary contactor failed – Secondary Contactor failed – Generator timed out Sertus Ltd, Europa House, Cranleigh, Surrey, GU6 8NQ hello@sertus.uk 01483 269 999...