www.acornfiresecurity.com The ZetaBeam Reflective optical beam smoke detector user guide Distance and position guidelines These guidelines are recommendations only and it is important that you refer to your appropriate governing standards at all times. When positioning your ZetaBeam there are important factors that you should consider, mainly what distance you are covering and the optimal position in the building.
Page 3
www.acornfiresecurity.com What position? A roof is considered flat unless the height of the apex is greater then 0.6m. If the roof is flat the 0.3m and 0.6m ZetaBeam system can be placed anywhere under the roof between below the roof, up to 7.5m a maximum height of from the floor.
www.acornfiresecurity.com 2 Installing, commissioning and testing step 1 mounting the head Screw the head backing plate to the wall - always try to use as sturdy a location as possible, such as brick or major structural steels (avoid mounting to outer metal cladding etc). Avoid mounting the head where direct sunlight can shine directly into the ‘eyes’...
Page 5
www.acornfiresecurity.com Generic wiring configurations the zetabeam is a conventional device, below are suggested wiring configurations for single and multi heads on a zone. the zetabeam can easily be made addressable with the use of a manufacturers interface and in some cases can also be powered from the loop, ie with the Apollo XP95 switch monitor with isolator.
Page 6
www.acornfiresecurity.com Multiple beams on a zone Other wiring diagrams See our website for further diagrams including interfacing with manufacturers protocols www.zetaalarmsystems.com www.acornfiresecurity.com...
Page 7
www.acornfiresecurity.com step 3 commissioning Commissioning the ZetaBeam is a simple procedure outlined in the following step by step explanation. stage one, language and commissioning speed 1. Important. Do COVER put the reflector up or it if already in place. the ZetaBeam PLUS Air Quality 0% 2.
Page 8
www.acornfiresecurity.com Receiver sensitivity starts off at 5% and output power starts at 10%. The beam will start by raising its sensitivity first and can rise all the way up to 100%, after this the output power will rise. The objective of pre-alignment is to adjust the output power to the correct levels for the distance to be covered.
Page 9
www.acornfiresecurity.com stage three, manual alignment You will now see the manual alignment screen showing anything between 0 and 6%. This is the amount of received signal with no reflector that the beam is picking up from the environment. NOW place or uncover the reflector on the blank wall directly opposite the beam head ensuring there is a clear path through any obstructions such as structural steels etc.
Page 10
www.acornfiresecurity.com stage four, auto-alignment Having received an AQ reading of over 40% enter enter in manual mode press to exit manual and again to go into auto alignment mode. 8.7% 67% 103% A Auto Alignment enter X+0.00° Y+0.00° First you will see the sensitivity and power readings drop if the received signal is over 100%. Once at 100% or if the reading is under 100% the ZetaBeam will automatically move its y and x axis until it centres itself onto the middle of the reflector.
www.acornfiresecurity.com 3 Screen and menu systems Home screen Air Quality 100% This is the screen you would normally see when the beam is commissioned. Status - NORMAL Other screens you may see are: Air Quality 29% FIRE The air quality level has fallen below the fire threshold setting. Status - FIRE If alarm is set to latching and you need to reset from fire press enter...
Page 12
www.acornfiresecurity.com Individual menu items enter 1. The language is factory set to English if this is okay press enter to continue to commissioning or arrow to return to the home screen. To change Language the language use the right left keys to change to your preferred language and press enter...
Page 13
www.acornfiresecurity.com 3. Here we can make changes to how the beam behaves. Press enter to go into enter Mode Change mode change and the sub menus. enter Threshold. Use the right left keys to increase or decrease the beams sensitivity. It is factory set at 35% (meaning the received signal has to drop by 35% to trigger Threshold the fire relay.
Page 14
www.acornfiresecurity.com Green flashing light on / off. By using the right left keys you can turn the green Green Flashing flashing LED, located on the head and controller, or off. This is a useful way of Light On/Off identifying the beam head you are working with (press enter to return to mode...
Page 15
www.acornfiresecurity.com Event counts. Here we can see how many times the beam has gone into fire fault Alarm & Fault since the beam was commissioned or since the event log was last cleared. Event Counts Press enter clear events. enter left/ Press left/back...
www.acornfiresecurity.com technical specifications Electrical Specifications: Test/Reset Features: Supply Voltage. 10.2 to 40 VDC Beam test function by controller Supply Current. 3.5mA (constant current) Alarm latching/auto-reset selectable in all operational states (default auto-reset) Constant Current. 17mA (constant current) Alarm reset in latching mode by controller reset in fast commissioning function, removing power for >5 seconds, apply 12 to 24 VDC to reset connections in Beam Head.