VISUAL4
Installation and Startup Guide
1
This document covers the installation of VISUAL4 HMI, for the detailed specifications and
operation, please refer to Brochure and EasyBuilder Pro User Manual.
Install Environment:
NEMA Rating
The
HMI product is NEMA 4 rated (Indoor Only).
The
HMI product has been tested to conform to European CE requirements. This
Electrical
means that the circuitry is designed to resist the effects of electrical noise. This
Environment
does not guarantee noise immunity in severe cases. Proper wire routing and
grounding will insure proper operation.
(1) Make sure that the displays are installed correctly and that the operating
limits are followed. Avoid installing units in environments where severe
mechanical vibration or shocks are present.
(2)
Do not operate the unit in areas subject to explosion hazards due to
flammable gases, vapors or dusts. MT8071iE is certified in accordance with
ATEX zone 2/22 categories 3 G/D. The unit has to be installed in an
additional enclosure ensuring a minimal protection level for 3G/D
Environmental
equipment. The enclosure equipped with the unit has to be certified and
Considerations
shouldn't be opened when an explosive atmosphere is present.
(3) Do not install the unit where acid gas, such as SO2 exists.
(4)
This device should be mounted in the vertical position and for use on the flat
surface enclosure.
(5)
Conform to UL508 (ISBN 0-7629-0404-6) machine safety for use in
Pollution Degree 2 Environment.
(6)
Relative Humidity: 10% ~ 90% (non-condensing)
2
Unpacking the Unit
Unpack and check the delivery. If damage is found, notify the supplier.
NOTE:
Place the operator panel on a stable surface during installation. Dropping it or letting it fall may
cause damage.
(1) Installation Instruction, 2-sided A4 *1
(2) Human Machine Interface *1
(3) Power Connector *1
(4) Brackets & Screws *1 pack
(5) USB Stick Clamp & Tying Strap *1
(6) Fuse 1.25A/250V 5*20mm *1
3
Installation Instructions
Secure the operator panel in position, using all the fastening holes and the provided brackets
and screws. Screw Torque: 2.6 ~ 3.9 lbf.in. (For reaching waterproof effect and preventing the panel
from being deformed.)
Installation Instruction
(A)
Cutout
(B)
Type
A(mm)
B(mm)
192
138
MT6071/8071iE
260
202
MT8101iE
USB Stick Clamp Usage
Combining the USB Stick with the clamp and the tying strap can prevent USB stick from disconnecting
with HMI when strong vibration is present.
1. Insert the USB connector to the clamp and tie them together with the tying strap.
2. Press the spring and insert the USB stick into HMI.
4
Power Connections
NOTE:
1. Connect positive DC line to the '+' terminal and
the DC ground to the '-' terminal.
2. When downloading project using a USB cable,
do not connect HMI with PLC and PC
simultaneously, for electric potential difference
may result in damage to HMI or PC.
5
System Settings
When HMI is powered up and displays image,
click the system setting button.
(Default System Password: 111111)
It is necessary to connect the HMI to
your network through a RJ-45 cable.
(N/A for MT6071iE)
Go to the Network tab, you may choose
to auto get DHCP IP, or designate your
own IP.

Advertisement

loading
Need help?

Need help?

Do you have a question about the VISUAL4 and is the answer not in the manual?

Questions and answers

Summary of Contents for Seneca VISUAL4

  • Page 1 Type A(mm) B(mm) Installation and Startup Guide MT6071/8071iE This document covers the installation of VISUAL4 HMI, for the detailed specifications and MT8101iE operation, please refer to Brochure and EasyBuilder Pro User Manual. Install Environment: USB Stick Clamp Usage Combining the USB Stick with the clamp and the tying strap can prevent USB stick from disconnecting NEMA Rating HMI product is NEMA 4 rated (Indoor Only).
  • Page 2 NOTE: Make sure that all local and national electrical standards are met when CAUTION EasyBuilder Pro Software Settings installing the unit. Contact your local authorities to determine which codes apply. Launch EasyBuilder Pro software, select your project file, press F7 shortcut key to open the download The unit can be powered by DC power only, voltage range: 24±20% Volts DC, compatible with dialog box: Select Ethernet >...