INT-TCP/IP-V2-P2P GATEWAY INTERFACE MADE IN PORTUGAL - EU GLOBAL FIRE EQUIPMENT S.A. Parque Industrial Municipal da Barracha, 8150-017 São Brás de Alportel - PORTUGAL | Tel: +351 289 896 560 Email: info@globalfire-equipment.com | Technical Support: techs@globalfire-equipment.com | www.globalfire-equipment.com CONFIGURATION MANUAL...
To configure the interface, you only need to access the user-friendly configuration web page directly via Wi-Fi AP mode. Ensure that the interface is in Access Point mode, and you're ready to proceed. TECHNICAL SPECIFICATIONS INT-TCP/IP-V2-P2P-GATEWAY SUPPLY VOLTAGE 20 to 30V DC...
Examples of LAN or WI-FI supported networks NETWORK SWITCH WI-FI SWITCH Disclaimer: Wi-Fi Connection Limitations Please be aware that the Wi-Fi connectivity feature of the device operates exclusively on the 2.4GHz frequency band. It is important to note that the device does not support 5GHz Wi-Fi networks. To ensure a stable and reliable connection, it is recommended to have a strong and consistent Wi-Fi signal strength in the area where the device is being used.
CONNECTION DIAGRAM The method used to provide power and communication to the interface is through a 5-way flat cable, which is connected to a 5-pin Molex connector located on the communication channels of the panels. Please note that this connection method may differ depending on the hardware variant of the panel.
INTERFACE CONFIGURATION LEDs Status and behaviour modes START-UP MODE Before any configuration is executed, the default startup behaviour of the interface ensures basic functionality. INT-TCPIP-V2-P2P-GATEWAY DESCRIPTION Yellow No power Yellow During start-up BLINKING Waiting for ethernet network Alternating ON/OFF AP Mode OPERATION MODE The operation mode of the interface is characterized by the behaviour of its LED indicators.
Configuration using Wi-Fi with the module in AP MODE Ensure to follow the instructions in the manual to configure your interface properly and avoid connecting the Ethernet cable until the configuration process is completed. This will help ensure a successful and smooth setup of your device. ATTENTION: It is important to note that the Ethernet cable should not be connected during or before the configuration procedure.
CONFIGURATION PAGE DETAILS Connect using: CONNECT USING: From the drop-down menu, you can choose the type of connection you want to use, either WIFI or Ethernet cable RJ45. DHCP: Normally activated by default. ● DHCP Configuration for Interface Pairing To ensure correct functionality, please note the following when pairing your TCPIP interface with other interfaces: A.
Page 8
MODE: Choose the binding mode options: Disabled (OFF), Initiator (TX), or Listener (RX). This allows you to set up and connect interfaces together. To establish the connection, the Initiator connects to the Listener. The channels are connected in a daisy chain manner, where CH1 connects to CH2.
7. Press the “APPLY” button to save your configured settings. Press RESET to restart the configuration. The interface will restart with the configured settings. The LEDs will flash when the interface connects, see LED behavior table. IMPORTANT NOTE: Double-check that all information is accurate before proceeding.
RESET to switch pressed, the interface will also RESET interface to restart GLOBAL FIRE EQUIPMENT S.A. Parque Industrial Municipal da Barracha, 8150-017 São Brás de Alportel - PORTUGAL | Tel: +351 289 896 560 Email: info@globalfire-equipment.com | Technical Support: techs@globalfire-equipment.com | www.globalfire-equipment.com...
Need help?
Do you have a question about the INT-TCP/IP-V2-P2P-GATEWAY and is the answer not in the manual?