Modbus Protocol (V2.2) for the AOWD-MB LOGIK Heat Pump Water Heater Preface This protocol specifies the communication format and also the data format for the Modbus communication of the Verstali heat pump water heater. This protocol is applicable to the Verstali heat pump water heater. Terms and Definitions 1) Modbus Communication Modbus protocol is such a protocol used for industrial communication and distributed control system.
The interface RS485 of Modbus communication protocol, provided by the long-distance monitoring system, can be directly connected with the BMS system or Daitsu long-distance monitoring system, that is, control up to 255 units and display their running status at the same time. The control function of the BMS system is equal to that of the long-distance monitoring system.
Modbus Protocol (V2.2) for the AOWD-MB LOGIK Heat Pump Water Heater 3.2 Topological Structure 3.2.1 Topological Strcutre (<255) Figure 1: Topological Strucure (<255) 3.2.2 Topological Strucuture (>255) Figure 2: Topological Structure (255) MODBUS Protocol Format General Modbus actually has become the industrial communication standard because it is not only fully opened and used widely but also simple and can be debugged flexibly.
Page 6
Modbus Protocol (V2.2) for the AOWD-MB LOGIK Heat Pump Water Heater Check Bit:None Stop Bit:1 3) Hardware interface of Wired Controller: Interface Specifications Instructions Interfaces Two-wire communication To be integrated into 1——A communication line, Class twisted the BMS system 2——B interface pairs,...
Page 7
Modbus Protocol (V2.2) for the AOWD-MB LOGIK Heat Pump Water Heater Step 2: press “Next” (the 1st from the right side) to go to the page where “Address” is. Step 3: Select the option “Address”, and then go to the setting page.
Modbus Protocol (V2.2) for the AOWD-MB LOGIK Heat Pump Water Heater Step 3:After that, press “ ” or “ ” to increase or decrease the “Address” value. Step 4:Press “OK”to save the value. Note: the “Address” can’t be 0 or 126. When the setting is finished, the address in the control command sent by the BMS software should be same as this setting value by the controller.
Modbus Protocol (V2.2) for the AOWD-MB LOGIK Heat Pump Water Heater 5) The bit count which the master unit can read or transmit is less than Byte×8. The ineffective data bit of the last byte should be cleared when transmit or read the effective data of the communication frame. For instance, when nine “1” bits are read or transmitted, then two bytes are need, “1111 1111”...
Modbus Protocol (V2.2) for the AOWD-MB LOGIK Heat Pump Water Heater Table 7: Response Frame Device Add. Function Code Starting Add. Data Size 1 Byte 1 Byte 2 Bytes 2 Bytes 2 Bytes Note: The response frame has the same device address, function code, starting address and data size as the request frame.
Modbus Protocol (V2.2) for the AOWD-MB LOGIK Heat Pump Water Heater an alarm response is replied. Function Code: Set the highest-order bit to “1”, which is value figured out through the OR operation of the request frame’s function code and 0x80. Communication Format of the Response Frame Table12: Alarm Response Frame Device Add.
Modbus Protocol (V2.2) for the AOWD-MB LOGIK Heat Pump Water Heater deactivated, “Floor Debug Sections”, “First Floor Debug Section Temp”, ‘Each Floor Debug Section Temp” or “Each Floor Debug Section Interval” settings are effective, or the monitoring software is suggested to tell this operation is invalid. ★(5): Disinfection: please read the Installation and Operation Instructions of the Wired Controller of the Versati heat pump water heater for details about the “Disinfection”...
Page 13
Modbus Protocol (V2.2) for the AOWD-MB LOGIK Heat Pump Water Heater Actual value: 7~25℃/ 5~25℃[Second generation monobloc] Unsigned WOT-Cool Default: 1℃ Integer 18℃/18℃[Second generation monobloc] Word Transmission value=Actual value Actual value: 20~60℃ [High-temp] / 20~55℃[low-temp]/ 20~65℃ [Second generation monobloc] Word Default:...
Page 14
Modbus Protocol (V2.2) for the AOWD-MB LOGIK Heat Pump Water Heater Unsigned Integer Actual value: 18~21℃, Lower RT-Heat 1℃ Default: 18℃ Transmission value = Actual Word value Actual value: Unsigned Integer 20~60℃[High-temp]/ 20~55℃[Low-temp] Default: Upper WT-Heat 1℃ 55℃[High-temp]/55℃ [Low-temp] Word Transmission value =...
Page 15
Modbus Protocol (V2.2) for the AOWD-MB LOGIK Heat Pump Water Heater ONE/Second generation monobloc] Default :5℃ Transmission value = Actual value Actual value:1~5℃, Default :2℃ Unsigned △T-Room temp Integer Word Transmission value=Actual 1℃ value Word Word Actual value:1~3 Default :1 Unsigned Other thermal logic Integer...
Page 16
Modbus Protocol (V2.2) for the AOWD-MB LOGIK Heat Pump Water Heater Integer 1.2~16.1Kw[Single]/ 3.5~17.3Kw[Three phase] Default : 3.0Kw[Single 4/6Kw]/ 6.2Kw[Single 8/10Kw]/ 7.6Kw[Single 12/14/16Kw]/ 9.0Kw[Three phase] Transmission value=Actual value * 10 Word 0: Does not clear fault Unsigned Error reset 1: Clear fault Integer 0:Off Unsigned...
Page 17
Modbus Protocol (V2.2) for the AOWD-MB LOGIK Heat Pump Water Heater frequency at the Quiet Default :/ Integer mode for heat and hot Transmission value = Actual water value Unsigned Actual value:35~120Hz Compressor operating Integer Default :/ frequency at the Quiet Transmission value =...
Page 18
Modbus Protocol (V2.2) for the AOWD-MB LOGIK Heat Pump Water Heater value Actual value:65~85 Hz Running Frequency Setting Default :75Hz Unsigned for cool Integer Word Transmission value = Actual value Actual value:65~85 Hz Running Frequency Setting Default :75Hz Unsigned for heat Integer Transmission value =...
Page 19
Modbus Protocol (V2.2) for the AOWD-MB LOGIK Heat Pump Water Heater Word Reserved Word Reserved Word Reserved Word Reserved Word Reserved Word Reserved Word Reserved Word Reserved Word Reserved Word Reserved Word Reserved Word Reserved Word Reserved Word Reserved Word Reserved Word Reserved...
Page 20
Modbus Protocol (V2.2) for the AOWD-MB LOGIK Heat Pump Water Heater 08: Off/ Default: / Transmission value = Actual value Integer Actual value: -30~150℃ 0.1℃ Default: / T-outdoor Word Transmission value = Actual value*10 Integer Actual value: -30~150℃ 0.1℃ Default: / T-discharge Word Transmission value =...
Page 21
Modbus Protocol (V2.2) for the AOWD-MB LOGIK Heat Pump Water Heater value*10 Actual value: Unsigned 1: Cool/ Integer 2: Heat/ Thermostat 3: Off Default: / Transmission value = Actual Word value Actual value: actual calculated Unsigned 1℃ value Integer Default: / T-floor debug Word Transmission value =...
Page 22
Modbus Protocol (V2.2) for the AOWD-MB LOGIK Heat Pump Water Heater Default: Off Transmission value=Actual value Actual value: Unsigned ZF63011MJ 0: Off/ Integer EVU signal 1: On ZF2011EJV1 Word Default: Off Transmission value=Actual value Actual value: Unsigned ZF63011MJ 0: No/ Integer 1: Yes ZF2011EJV1...
Page 23
Modbus Protocol (V2.2) for the AOWD-MB LOGIK Heat Pump Water Heater value*100 Actual value: 0~655.35 kWh 0.01kW Unsigned Integer Power consumption Jul. Default: / ZF63011MJ (high) Word Transmission value = Actual value*100 Actual value: 0~655.35 kWh 0.01kW Unsigned Integer Power consumption Jul. Default: / ZF63011MJ (low)
Page 24
Modbus Protocol (V2.2) for the AOWD-MB LOGIK Heat Pump Water Heater Actual value: actual calculated Unsigned value Integer ZF2011EJV1 Default: / Fan frequency Transmission value = Actual Word value Actual value: actual calculated Unsigned M³/h value Integer ZF2011EJV1 Default: / Water flow Word Transmission value =...
Page 25
Modbus Protocol (V2.2) for the AOWD-MB LOGIK Heat Pump Water Heater 0: Off/1: On State Variable Outdoor Holiday Mode Bit 34 Unit 0: Off/1: On State Variable Refri. recovery Bit 35 0: Off/1: On Manual defrost State Variable Bit 36 0: Off/1: On Cool 2-Way valve State Variable...
Page 26
Modbus Protocol (V2.2) for the AOWD-MB LOGIK Heat Pump Water Heater Reserved Bit 75 Reserved Bit 76 Reserved Bit 77 Reserved Bit 78 Reserved Bit 79 State Variable Compressor State 1: On; 0: Off Bit 80 1: On; 0: Off State Variable ODU Fan State Bit 81...
Page 27
Modbus Protocol (V2.2) for the AOWD-MB LOGIK Heat Pump Water Heater Reserved Bit 119 Reserved Bit 120 Reserved Bit 121 Reserved Bit 122 Reserved Byte Bit 123 Reserved Bit 124 Reserved Bit 125 Reserved Bit 126 Reserved Bit 127 DC Bus Low-voltage or Voltage Error 1: Error;...
Page 28
Modbus Protocol (V2.2) for the AOWD-MB LOGIK Heat Pump Water Heater Refrigerant Vapor Line Temp 1: Error; 0:Normal Error Bit 158 Sensor Error Error Reserved Bit 159 Remote Room Temp Sensor 1: Error; 0:Normal Error Bit 160 Error Error Reserved Bit 161 Reserved Bit 162...
Modbus Protocol (V2.2) for the AOWD-MB LOGIK Heat Pump Water Heater Precautions befor the Use 1) Make sure the proper adapter is used; or normal communication would fail. 2) Reinforce the stability of the communication cord through soldering and insulate it with the insulating tape to prevent oxidation and short circuit.
Page 30
Eurofred S.A. Marqués de Sentmenat 97 08029 Barcelona www.eurofred.es...