Graco 20A676 Instructions page 2

Light tower kit

Advertisement

Installation
NOTE: Install the light tower somewhere it will be
visible to the operator during system use.
1. Shutdown the system. See your Reactor operation
manual for shutdown instructions, Installation.
2. Disconnect incoming power at the source.
3. Use the lag screws (6) and gasket (2) to install
bracket (1) in the desired light tower location.
4. Guide the light tower cable through the opening in
the bracket (1) then use screws (3a), washers (3b),
and nuts (3c) to secure light tower to bracket.
5. Connect supplied accessory cable (5) to light tower
cable.
6. Open the electrical enclosure.
7. Route the light tower cable through the opening in
the bottom of the electrical enclosure to the Motor
Control Module (MCM).
8. Connect the light tower cable to the MCM in port
12 (MM) as shown in F
Advance Display Module
(ADM) Configuration
1. On the Reactor ADM, tap
go to Setup > System.
2. Set the MCM Digital Input/Output fields to drive the
appropriate signals to the light tower. See F
a. Set MCM Digital Input/Output 1-2 to Light
Tower Green.
b. Set MCM Digital Input/Output 3-4 to Light
Tower Yellow.
c. Set MCM Digital Input/Output 5-6 to Light
Tower Red.
All written and visual data contained in this document reflects the latest product information available at the time of publication.
GRACO INC. AND SUBSIDIARIES • P.O. BOX 1441 • MINNEAPOLIS MN 55440-1441 • USA
Copyright 2021, Graco Inc. All Graco manufacturing locations are registered to ISO 9001.
. 1, page 1.
IG
. In the drop-down,
. 2.
IG
Graco reserves the right to make changes at any time without notice.
Original instructions. This manual contains English. MM 3A8642
Graco Headquarters: Minneapolis
International Offices: Belgium, China, Japan, Korea
www.graco.com
Revision
F
. 2 ADM Light Tower Configuration Settings
IG
Light Tower Signals
NOTE: See the Reactor proportioner manual for
specific errors associated with the light tower signals.
Signal
Green On Only
Yellow On
Yellow Flashing
Red On
Optional Extension
Cables
Part
123658
,
B
September 2021
Description
System is powered up and there are
no error conditions present.
A low priority error (advisory) exists.
A medium priority error (deviation)
exists.
The system is shut down due to a
high priority error (alarm) condition.
Length
28 ft (8.5 m)