Summary of Contents for Fantini Cosmi OPENTHERM C800WIFIOTRQ
Page 1
OPENTHERM WI-FI SMART REMOTE CONTROL ® FOR HEAT GENERATORS USE AND INSTALLATION MANUAL...
Page 2
OPENTHERM WI-FI SMART REMOTE CONTROL ® FOR HEAT GENERATORS Dear customer, thank you for purchasing the Fantini Cosmi smart remote control model C800WIFIOTRQ suitable for OpenTherm heat generators for the management ® of heating systems and sanitary hot water. This manual holds all the information required for a correct installation and configuration.
C800WIFIOTRQ 1 - TECHNICAL DATA 230 V - 50 Hz (Power supply unit C800AL) Power supply 2 AA 1.5 V alkaline batteries Battery life > 1 year Communication protocol OpenTherm Max. mains power consumption 5 / 10 s from last press; always ON LEDS switch-off (only with 230V mains supply) Temperature adjustment scale...
C800WIFIOTRQ 2 - INSTALLATION Installation and maintenance operations must be carried out with the system’s electrical voltage switched off and by qualified personnel, in compliance with the regulations in force. 2.1 - POWER SUPPLY Separate the front cover from the base by pressing the button on the bottom edge of the cover and releasing the housing upwards, as shown in the figure.
Page 6
C800WIFIOTRQ LOW BATTERY WARNING • 1 flash per minute on display in Stand-by: the batteries are running low and it is still possible to operate the device but they need to be replaced. • 1 flash per minute and Low Bat appears on the display in Stand- by: the batteries are exhausted the device can no longer be operated and will go to OFF.
Page 7
C800WIFIOTRQ Hook the C800AL up to the 4 tabs of the base, making sure that the fixing is secure. Connect the cables to the terminal block, as shown in the table. Black Purple Grey Orange Close and screw on the terminal block cover.
C800WIFIOTRQ 2.2 - CONNECTION TO THE SYSTEM Installation and maintenance operations must be carried out with the system’s electrical voltage switched off and by qualified personnel, in compliance with the regulations in force. For a correct installation, prepare a dedicated line for the bus connection. CONNECTION WITH BATTERY POWER SUPPLY Unscrew the screw as shown in the drawing and lower the plas-...
Page 9
C800WIFIOTRQ Close and screw the terminal box cover. Hang up the front cover to the base. CONNECTION WITH MAINS POWER SUPPLY 230V - 50HZ If supplied with 230V, connect the C800AL terminals to the electrical and heating systems as follows: 4: Boiler input contact 2: Boiler input contact 1: Not used...
C800WIFIOTRQ 2.3 - WALL FASTENING For an optimal operation of the device, it is advisable to install the remote control at a height of approx. 1.5 mt above the floor, in a suitable position to correctly detect the room temperature (see the example in the drawing). 1,5 m WALL MOUNTING (for battery power supply only) The tabs on the back of the base must be removed for the wall mounting.
Page 11
C800WIFIOTRQ FIXING ON FLUSH-MOUNTED BOXES The remote control is supplied with a square and a rectangular bases to allow the fixing on flush-mounted boxes type 500-502-503. 11 -...
Page 12
C800WIFIOTRQ Hang up the front cover. It is now possible to restore power to the system. When switching on for the first time, wait for the device to communicate with the boiler. When the display LEDs switch off, the device is ready. - 12...
C800WIFIOTRQ 3 - USE FROM THE DEVICE From the device it is possible to select the regulation type of the heating system, the operating modes and the desired current temperatures, along with the management of the sanitary hot water. To customize the program and choose the temperatures of the heating system, it is necessary to pair the device with the Intelliclima+ App and proceed with the relevant configuration (see page 25 and/or APP manual on pdf.fantinicosmi.it).
5°C 8:00 22:00 24:00 h C800WIFIOTRQ 3.2 - OPERATING MODE SELECTION JOLLY ritorno a AUTO With the display switched on, press the central MODE button to view the current operating mode. Press the central MODE button again to select the desired 17°C operating mode: 7:00...
Page 15
19°C C800WIFIOTRQ 20°C 19°C - “AUTO” WEEKLY PROGRAM * 5°C The device follows the weekly profile set in PROGRAMS. It is possible to associate one of the three programmable temperatures (off/antifreeze, comfort temperature and 24:00 h 7:00 8:00 17:00 22:00 24:00 h economy temperature) every quarter of an hour, for every day of the week (see the APP manual on pdf.fantinicosmi.it).
Page 16
C800WIFIOTRQ 20°C - SANITARY HOT WATER PROGRAM (DAILY) ** 19°C This function is available only if the boiler board is configured to manage the production 5°C of sanitary hot water. If the ACS operating mode is enabled (see page 21), during SUMMER or WINTER 8:00 22:00 24:00 h...
20°C 19°C C800WIFIOTRQ 5°C - “JOLLY” TEMPORARY PROGRAM *** 8:00 22:00 24:00 h It is possible to maintain a certain temperature for a certain number of hours (from 1 up to 240); after the system will revert to the previously active program. JOLLY revert to AUTO JOLLY...
C800WIFIOTRQ 3.4 - BASIC SETTINGS To modify the basic settings you can access to the basic menu: 1 sec. 3 sec. Use the central Press MODE Press and hold Use the arrows MODE button to lightly to MODE again to change the scroll through the reactivate the for more than 3...
Page 19
C800WIFIOTRQ Current day setting It allows to set the current day necessary to manage the weekly program (AUT mode). Default value at startup = 1 Settable values = 1 ÷ 7 1=Monday; 2=Tuesday; 3=Wednesday; 4=Thursday; 5=Friday; 6=Saturday; 7=Sunday; Current time setting (hour) It allows to set the current hour necessary to manage the daily and weekly program (AUT, HOL and ACS mode).
Page 20
C800WIFIOTRQ Sanitary hot water T It allows set the sanitary hot water temperature in “comfort” mode for a regulation suitable to the moments spent at home. Default Setpoint value = 40°C Settable values = Automatic update with boiler limits Note: t >...
C800WIFIOTRQ 3.5 - ADVANCED FUNCTIONS Further remote control settings can be changed in the Advanced Functions menu: 1 sec. 3 sec. Use the arrows Press MODE Press and hold Use the central to change the lightly to both the UP and MODE button to settings of the reactivate the...
Page 22
C800WIFIOTRQ ADVANCED FUNCTIONS MENU Communication protocol This function displays the protocol used to communicate with the boiler. PLS = OpenTherm Plus ® ACS Enabling This function enables the sanitary hot water (ACS) management. Default value = OFF OFF Disabled Enabled Heating water temperature with fixed point regulation This function allows to set the delivery hot water temperature with the fixed point regulation.
Page 23
C800WIFIOTRQ Regulation type It is possible to select the type of adjustment you want to use. - Fixed point: the delivery water fixed temperature is set according to the selected system type: Radiators, Fan Coils, Radiant Panels (see also page 21 - parameter P03);...
C800WIFIOTRQ 4 - USE FROM APP It is possible to proceed with the system parameters configuration only without the need to configure the device to the final WiFi home network (see the APP manual on pdf.fantinicosmi.it). 4.1 - APP INSTALLATION Download the Intelliclima+ APP, available free of charge from Google Play Store and Apple Store.
C800WIFIOTRQ 4.2 - DEVICE PAIRING Enable the device in AP mode from the user menu: 1 sec. 3 sec. Press MODE Press and hold Use the arrows to lightly to MODE again select ON. reactivate the for more than 3 remote control.
C800WIFIOTRQ Note: for further specifications on the device operation via Intelliclima+ APP, please refer to the relevant manual, available in digital format and in several languages by framing the QR code below and typing in product code C800WIFIOTRQ. C800WIFIOTRQ pdf.fantinicosmi.it For further information and assistance, contact your trusted installer or write to indicating the model in use and the problem found.
Page 28
FANTINI COSMI S.p.A. Via dell’Osio, 6 - 20049 Caleppio di Settala, Milano - ITALY Ph. +39 02 95682.222 - export@fantinicosmi.it www.fantinicosmi.com...
Need help?
Do you have a question about the OPENTHERM C800WIFIOTRQ and is the answer not in the manual?