Download Print this page

ABB Stanilite Series Installation Manual page 2

Weatherproof ip65 3cct led batten

Advertisement

Installation instructions
1. Always switch OFF the mains supply befor installation or servicing.
2.
3. Avoid drilling any hole through the base housing. If a sealing compound is used, it must be of the
neutral cure type. It is the responsibility of the installer to install the luminaire correctly
to maintain the batten's IP integrity.
Mains
SA
Switch Active
PE
Green/Yellow (Earch)
Blue (Neutral)
N
Connect battery
This applies for emergency batten
Dia
6mm
Emergency
A
Active
SA
Switch Active
PE
Green/Yellow (Earch)
N
Blue (Neutral)
Set the current on LED driver by DIP
switch, ensure mains is OFF.
**350mA and 700mA current setting
only applies for Mains AC battens
and are not to be use for emergency
batten
2ft Current
4ft Current
200mA
400mA
250mA
500mA
300mA
600mA
350mA**
700mA**
Nexus LX Emergency Batten
- Connect the data cable
to the green connector on
the power pack.
- When correctly installed
no fitting should have
more than 2 data cables
connected to it.
- If you have more than 2 data cables at any 1
fitting, the installation is incorrect.
- If this fitting is at the end of a data cable run, a
terminator needs to be wired parallel across the 2
data lines.
- If there is an in and out data cable, then the
shields should be wound together, folded back
and taped up.
- Consult the Nexus user and technical guide for
further detail, including product commissioning.
Emergency Batten LED Indicator Status - on initial power ON
Non-monitored
Nexus LX
Nexus RF
As installer, it is your responsibility to conduct the initial discharge testing of the installed emergency
fitting. Refer to AS/NZS 2293.
Note, 16 hrs min. require (24 hrs recommended) to allow the fitting re-chargable battery to reach
full capacity, prior to a discharge test.
Microwave ON/OFF Motion Sensor Settings
Operating Frequency: 5.8 GHz ±75 MHz,ISM Band.
Transmitting power: 0.5mW Max.
Hold time: 5s//30s/90s/5min/20min/30min
Pin 1
Pin 2
Detection Sensitivity: 100%/75%/50%/25%
OFF
OFF
Daylight Sensor: 2Lux/10Lux/30Lux/50Lux/Disable
ON
OFF
Detecting Radius: 3-10m (mounting height 3-4m), 2-8m (mounting height 6m)
OFF
ON
Mounting Height: 6m Max.
Detecting Angle: 150° (Wall mounted), 360° (Ceiling mounted)
ON
ON
2700K 4000K 6500K
Nexus RF Emergency Batten
- Collect the MAC address, by removing the peel
off sticker section and locating it on your floor
plan or spreadsheet.
- Consult the Nexus user and technical guide for
further detail, including product commissioning.
Antenna
Solid green
Blinks Red-Red-Green until it is commisioned
Blinks Red-Red-Red-Green/Red-Red-Green until joined network
Cable
Turn ON
Power

Advertisement