ICM Controls ICM495-30A Installation, Operation & Application Manual
ICM Controls ICM495-30A Installation, Operation & Application Manual

ICM Controls ICM495-30A Installation, Operation & Application Manual

Disconnect with internal surge protection

Advertisement

Quick Links

INSTALLATION, OPERATION & APPLICATION GUIDE
For more information on our complete range of American-made products – plus wiring
diagrams, troubleshooting tips and more, visit us at www.icmcontrols.com
ELECTRICAL SHOCK HAZARD – Before installing this unit, turn
off power at the main service panel by removing the fuse or
switching the appropriate circuit breaker to the OFF position.
• WARNING — Shock hazard — Do not open (ATTENTION – RISQUE
DE CHOC – NE PAS OUVRIR).
FEATURES
• UL Listed Electrical Disconnect including both enclosure & surge
protector
• 120VAC single-phase, 240VAC split-phase
• Features an internal surge protective device (SPD)
• Maximum Surge Current Rating of 100kA
• Highest UL rating for nominal discharge current (In 20kA),
for increased longevity & durability of the SPD
• Constructed with 2 high-quality thermally protected MOV's (TFMOV)
• Completely factory wired for quick and easy installation
• NEMA type 3R rated powder coated metal enclosure for
indoor/outdoor use
• Fully accessible mounting holes, no disassembling required
• Braided strap thoroughly grounding both the enclosure and cover
• LED indicator light showing when Surge Protection is operational
• 30A Fused & 60A non-fused models available
• Made in the USA
• Limited lifetime product. Up to a 3-year $10,000 connected
equipment warranty.
MODE OF OPERATION
The ICM495 is a UL Listed Electrical Disconnect with an Internal Surge
Protective Device built-in. The ICM495 is available in two models 30A
Fused and 60A Non-Fused.
The included Type 2 SPD is intended for 240 VAC Split Phase
configurations. When a surge occurs, the ICM495 will absorb the surge
up to the limits expressed in the specifications section in this guide.
The ICM495 incorporates thermal protection on the surge elements
(TMOV's) which allows for safe disabling of the surge elements when
a surge exceeds the thermal limits of the device. The ICM495 has a
status light on the control which identifies operational status when
illuminated. The ICM495 can be installed as a Type 2 device for both
indoor and outdoor applications. Suitable for use on a circuit capable
of delivering not more than 10kA RMS symmetrical amperes (Convient à
des circuits produisant au plus 10kA eff.).
REPLACES
30A: Mars: 83916, RectorSeal: RSH-50 96417
60A: Mars: 83915, RectorSeal: RSH-50 96419
All standard disconnect boxes rated for equal voltage and current
configurations
ICM495-30A/60A
Disconnect with Internal Surge Protection
Please follow all State, Local and National electrical codes when
installing this product. Installation should only be done by a licensed
HVAC technician for Type 2 devices.
SPECIFICATIONS
Service Voltage: Single Phase 120 / Split Phase 240 VAC; 30A at -40°C
min. and 25°C max., 240 VAC; 25A at -40°C min. and 55°C max., 240VAC;
60A at -40°C min. and 55°C max.
Short Circuit Current Rating (SCCR): 10 kA
Maximum Surge Current: 100 kA
Nominal Discharge Current (In): 20 kA
SPD Type: Type 2 applications only
Surge Protection Technology: TFMOV
Protection Mode: L1-L2, L1-G, L2-G
Maximum Continuous Operation Voltage (MCOV):
L-L: 300 VAC, L-G: 150 VAC
VPR (Vpk): Mode: L-L = 1200, L-G = 700
Input Power Frequency: 50/60 Hz
Diagnostics: Green LED indicates surge protection present
Enclosure Rating: NEMA/Type 3R metal enclosure for outdoor and
indoor installation
Installation Point: Located within sight of the motor controller/
equipment
Dimensions: 9.0" L x 5.25" W x 2.50" D
Operating Temperature: -40°F to 131°F (-40°C to 55°C)
Operating Humidity: Less than 85%, non-condensing
Operating Altitude: Less than 2000 meters
Agency Certification and Approvals: ANSI/UL1449 5th Edition cULus
Listed Device
DIAGNOSTICS AND MAINTENANCE
Periodically check the status on the SPD. If the green light is OFF, the
protection is no longer available and the unit needs to be replaced
immediately. This device features an internal protection that will
disconnect the surge protective component at the end of its useful life
but will maintain power to the load - now unprotected. 14 AWG stranded
copper wire or larger required. If any of the 30 Amp fuses blow on the
fused model, please replace the fuse or fuses with the appropriate 30
amp fuses. Note: the ICM495-60A model does not accommodate fuses.
E347279

Advertisement

loading

Summary of Contents for ICM Controls ICM495-30A

  • Page 1 ICM495-30A/60A Disconnect with Internal Surge Protection INSTALLATION, OPERATION & APPLICATION GUIDE For more information on our complete range of American-made products – plus wiring diagrams, troubleshooting tips and more, visit us at www.icmcontrols.com E347279 ELECTRICAL SHOCK HAZARD – Before installing this unit, turn...
  • Page 2 INSTALLATION INSTRUCTIONS ICM495-30A (FUSED) ICM495-60A (NON-FUSED) SPD MODULE SPD MODULE Load Load LOAD LOAD LINE LOAD LINE LOAD Use 14 AWG stranded copper wire rated for the appropriate voltage Use 8 - 14 awg wire for ground and 2-14 awg wire for Line and Load.