1 Safety . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
2 Checking the usage . . . . . . . . . . . . . . . . . . . . . 2
3 Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
4 Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
5 Adjustment. . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
6 Commissioning . . . . . . . . . . . . . . . . . . . . . . . . 5
7 Maintenance. . . . . . . . . . . . . . . . . . . . . . . . . . . 5
statistics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
10 Technical data . . . . . . . . . . . . . . . . . . . . . . . . 9
11 Designed lifetime . . . . . . . . . . . . . . . . . . . . . . 9
12 Safety instructions . . . . . . . . . . . . . . . . . . . . . 9
13 Accessories . . . . . . . . . . . . . . . . . . . . . . . . . 10
14 Logistics . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
15 Certification . . . . . . . . . . . . . . . . . . . . . . . . . 11
16 Disposal . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
oPeRAtInG InstRUCtIons
Cert. Version 12.20 · Edition 01.24 · EN · 03251460

1 sAFetY

1.1 Please read and keep in a safe place
Please read through these instructions
carefully before installing or operating. Following the
installation, pass the instructions on to the operator.
This unit must be installed and commissioned in
accordance with the regulations and standards in
force. These instructions can also be found at www.
docuthek.com.
1.2 explanation of symbols
1  , 2  , 3  , a  , b  , c  = Action
➔ = Instruction
1.3 Liability
We will not be held liable for damage resulting from
non-observance of the instructions and non-com-
pliant use.
1.4 safety instructions
Information that is relevant for safety is indicated in
the instructions as follows:
DAnGeR
Indicates potentially fatal situations.
WARnInG
Indicates possible danger to life and limb.
CAUtIon
Indicates possible material damage.
All interventions may only be carried out by qualified
gas technicians. Electrical interventions may only be
carried out by qualified electricians.
1.5 Conversion, spare parts
All technical changes are prohibited. Only use OEM
spare parts.

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the UVC 1 and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for krom schroeder UVC 1

  • Page 1: Table Of Contents

    UV flame detector UVC 1 oPeRAtInG InstRUCtIons Cert. Version 12.20 · Edition 01.24 · EN · 03251460 1 sAFetY 1.1 Please read and keep in a safe place Please read through these instructions carefully before installing or operating. Following the installation, pass the instructions on to the operator. This unit must be installed and commissioned in accordance with the regulations and standards in force.
  • Page 2: Checking The Usage

    2 CHeCKInG tHe UsAGe In industrial thermoprocessing systems, the UV flame detector UVC 1 is designed to monitor flames which emit UV radiation. The UV flame detector is suitable for intermittent or continuous operation in conjunction with Kromschröder burner control units BCU 370..U, BCU 4xx..U, PFU 7xx..U or BCU 5xx..
  • Page 3: Wiring

    – Dropping the device can cause permanent – Screw terminals for wire cross-sections damage. In this event, replace the entire device > 0.5 mm to ≤ 1.5 mm (AWG 26 to AWG 16). and associated modules before use. – Max. cable length as specified for burner control units BCU or PFU.
  • Page 4: Adjustment

    4.1 Burner control unit connection diagrams BCU 570..U0 BCU 370..U 13 14 15 16 UVC 1 PFU 760..U UVC 1 L (L1) N (L2) BCU 460..U 230 V UVC 1 9 10 11 UVC 1 PFU 780..U L (L1) N (L2) L1 N PE BCU 480..U...
  • Page 5: Commissioning

    6 CoMMIssIonInG WARnInG Only use the UV flame detector UVC 1 in con- junction with burner control units BCU 370..U, BCU 4xx..U, PFU 7xx..U or BCU 5xx..U0. For BCU 5xx, set parameter 04 to flame control with a UV sensor for continuous operation. Otherwise, the safety time may be evaluated incorrectly.
  • Page 6: Assistance In The Event Of Malfunction

    • Increase the switch-off threshold using BCSoft. 8 AssIstAnCe In tHe eVent oF ! The UV tube is defective. MALFUnCtIon • Replace the UV tube, see page 5 (7 Main- tenance). WARnInG ? the yellow LeD “Flame signal” is not lit Electric shocks can be fatal! although there is a flame.
  • Page 7 ? the BCsoft error history on the statistics • Check the wiring, see page 4 (4.1 Burner tab displays errorcode 1 = 30 or 31. control unit connection diagrams). ! Abnormal data change in the value range set for ! Fuse defective. the adjustable UVC 1 parameter.
  • Page 8: Reading Or Setting Flame Signal, Parameters, Statistics

    Reading/setting using BCsoft • Disconnect the UVC 1 from the mains supply and then switch it on again after approx. 10 s. Using an optionally available opto-adapter PCO, it • Check mains voltage and frequency. is possible to set parameter 01 and read analysis •...
  • Page 9: Technical Data

    This procedure applies to heating systems. For ther- 10 teCHnICAL DAtA moprocessing equipment, observe local regulations. Ambient conditions Condensation and dew in and on the unit are not 12 sAFetY InstRUCtIons permitted. Scope of application: Avoid direct sunlight or radiation from red-hot sur- as set out in “Industrial thermoprocessing equip- faces on the unit.
  • Page 10: Accessories

    13.4 BCsoft 13 ACCessoRIes The current software can be downloaded from our 13.1 nozzle for cooling air adapter Internet site at www.docuthek.com. To do so, you need to register in the DOCUTHEK. Rp ¼ 13.5 opto-adapter PCo 200 Including BCSoft CD-ROM, Order No.: 74960625.
  • Page 11: Certification

    Underwriters Laboratories UL 60730 – Automatic 15 CeRtIFICAtIon Electrical Controls Certificates – see www.docuthek.com 15.5 AGA approved 15.1 Declaration of conformity Australian Gas Association, Approval No.: 8586 We, the manufacturer, hereby declare that the www.aga.asn.au product UVC 1 complies with the requirements of 15.6 UKCA certified the listed Directives and Standards.
  • Page 12: Disposal

    16 DIsPosAL Devices with electronic components: Weee Directive 2012/19/eU – Waste electrical and electronic equipment Directive At the end of the product life (number of operat- ing cycles reached), dispose of the packaging and product in a corresponding recycling centre. Do not dispose of the unit with the usual domestic refuse.