Akd-5-Multi-Source Ground Fault - ABB EntelliGuard AKD-5 Installation Manual

600-2000a retrofill circuit breakers
Hide thumbs Also See for EntelliGuard AKD-5:
Table of Contents

Advertisement

Sensor window cross section conforms to criteria as found in the table below
Table 9. Frame Ratings and Sensor Areas
The Frame 3 neutral sensor is implemented as two separate sensors, similarly to the phase sensors
in the circuit breaker. Frame 3 neutral bus assemblies provide two independent parallel conductors
in the neutral bus such that the neutral current is divided between the two sensors.
A special neutral bus section is provided within the switchgear to accommodate the specific form
factor of each Rogowski—this is not the design responsibility of the Rogowski vendor.
Encapsulation materials are UL recognized and suitable for operation at 130C.
Neutral sensors of a given rating match all characteristics of the phase sensors.
AKD-5—Multi-Source Ground Fault
Retrofills can be used in the following ground fault applications:
Single source feeder breakers, 3-wire or 4-wire
Main circuit breakers, 3-wire or 4-wire
When multi-sources are present with the ground fault detection on the trip unit desired, then an
external GF summing CT scheme must be implemented. This applies to Main—Tie—Main systems or
systems with a main source and then a back-fed generator source.
Contact factory for MSGF applications.
44 EntelliGuard R Circuit Breaker Retrofill AKD-5 Installation Manual
Frame & Rating
Frame 1 / 2000A
Frame 2 / 3200A
Frame 3 / 6400A
(Table 9):
Sensor Window minimum area (in
2.0
3.2
6.4
)
2
DEH-41547