Uppf Power Factor Controller Please read this manual carefully before installing, wiring, operating, maintaining or checking this equipment. Please keep this manual within easy reach for quick reference. Safety Operation Warning 1.Before powering on, carefully check whether the device is reliably grounded.
Uppf Power Factor Controller 3. Wiring according to the wiring diagram. 4. Please connect the protective grounding to the PE contact on the metal shell of the equipment. 5. Please remove the CT short connector. 1. Product Overview Uppf power factor controller is a new type of distribution, measurement and control equipment that integrates functions such as data collection, reactive power compensation, and grid parameter analysis.
Uppf Power Factor Controller erosion, and the installation site cannot be violently vibrated. 3. Model Description LPF 230 Usage W: control thyristor switch, J: control contactor Output circuit: 12, 18, 24 Voltage(V): 230V Product Name: Uppf power factor controller Note: The above models are only reflected in the label 4.
Uppf Power Factor Controller 4.2 Reactive Power Compensation The sampling physical quantity is reactive power, without switching oscillation Mixed compensation: Y type compensation method Pure co-complementation: Δ type compensation method Δ type compensation method Y+Δ comprehensive compensation method 5. Technical Parameter 5.1 Basic Parameter AV 380V±20% (I generation co-compensate and II generation co- compensate 16/18/24 channels)
Uppf Power Factor Controller Harmonic Current Exceed Limit 00.0%~100% Steplength 0.5% 6. Display and Operation 6.1 Automatic Operation After the system is powered on, it will automatically enter the main menu (Chinese/English optional) after 30 seconds, and enter the automatic operation state after a delay of about 30 seconds.
Page 8
Uppf Power Factor Controller 24 channel as an example. First screen, display power factor, real-time voltage, current, capacitor switching status. This picture shows the 7 channel is invested. Second screen, display active power, reactive power, grid frequency, capacitor switching status. Third screen, display voltage and current harmonic total distortion rate, ambient temperature, capacitor switching status.
Uppf Power Factor Controller key to select "manual control", and operate the "Ent" key to enter the manual state. If the capacitance value of a certain channel is reversed, it means it has been put in, otherwise it means it has not been put in.
Page 11
Uppf Power Factor Controller Note: If it is used for the first time, parameters such as transformation ratio and capacitance must be reset according to the actual site needs. Press the Esc key to enter the main menu, operate the “▲” and “▼”...
Page 12
Uppf Power Factor Controller compensation without B and C items). 4) Protection Parameter Press the “Ent” key to enter, select the parameter item to be set. A total of two screens for protection parameters. Mark Factor preset Usage Range Communication device 001-255 address Confirm parameter...
Page 13
Uppf Power Factor Controller B-PH sequence setting C-PH Co-compensation 430V Cut off capacitors when Mixed 0-980 grid overvoltage compensation 250V Co-compensation 330V Cut off capacitors when Mixed 0-980 grid under-current compensation 190V Cut off capacitors when 0000 0000-9999 grid overcurrent Overcurrent cancellation 000-999 alarm return difference...
Uppf Power Factor Controller 1. The value of TK “switching threshold” refers to the “threshold coefficient of input”, and the sum of it and “threshold coefficient of cutting” is 1.2. When TK is set to 1.0: Hysteresis state, if grid reactive power > input threshold (1.0) × pre-investment capacitor capacity, then input the capacitor;...
Uppf Power Factor Controller capacitance parameters according to the number of output channel); C1-C16: 16-channel capacitance (display the corresponding capacitance parameters according to the number of output channel) C1-C18: 18-channel capacitance (display the corresponding capacitance parameters according to the number of output channel) C1-C24: 24-channel capacitance (display the corresponding capacitance parameters according to the number of output...
Uppf Power Factor Controller B、C voltage loss phase 7. Installation and Testing 7.1 Inspection and wiring diagram before installation Before opening the package of the device and preparing for installation, carefully check whether there is any damage and the accessories and instructions are complete. If you find any problems, please contact the supplier in time.
Uppf Power Factor Controller 7.2 Installation Dimension Dimensions: 144*144*95mm Hole opening size:138*138mm Embedding depth: 49mm 7.3 Wiring Instructions When considering the installation plan, please follow the principles of easy installation, convenient observation and collection, and good wiring for signals, power and grounding. 7.3.1 Working Power The working power of this device is multiplexed with the phase A voltage sampling channel, AC220V±...
Uppf Power Factor Controller 8.3 COSØ value does not change with the switching of the capacitor Please check whether the position of the sampling current transformer is correct (sampling current = load current + capacitor current). 8.4 COSØ value is wrong Please check whether the sampling voltage signal and the sampling current signal are in the corresponding phase, and the two cannot be in the same phase.
Uppf Power Factor Controller replace a controller and make another judgment, or contact the dealer directly for help. 9. Wiring Diagram 9.1 24 channels dynamic mixed compensation (no external power supply required)
Uppf Power Factor Controller channels dynamic three-phase compensation (external power supply is required) Note: 12 channels and 18 channels are only different in the number of control output circuits, and the other wiring is the same.
Uppf Power Factor Controller 9.3 24 channels static three-phase compensation (external power supply is required) Note: 12 channels and 18 channels are only different in the number of control output circuits, and the other wiring is the same.
Uppf Power Factor Controller After-sale Service The products of our company are guaranteed for 1 year, and the warranty period starts from the date of product sale. If the product faults or the parts are damaged during the warranty period, our company will provide free maintenance after it is identified by our technicians as occurring under normal use.
Page 24
Jiangsu Lafaelt Electric Co.,Ltd Hotline: 400-882-1973 Tel: +86 0510-81811717 Email: marketing@lafaelt.com Sales Center Add: 2nd Floor, No. 268, Tongxie Road, Changning District, Shanghai, China Factory Add: No. 79, Qunxing Road, Xinwu District, Wuxi City, Jiangsu Province, China Net: www.lafaelt.cn...