Three phase transformer speed controllers

Advertisement

Quick Links

OPERATION AND
MAINTENANCE
INSTRUCTIONS
THREE PHASE
TRANSFORMER
SPEED CONTROLLERS
IMPORTANT – PLEASE READ THESE INSTRUCTIONS FULLY
BEFORE COMMENCING INSTALLATION.
These instructions refer to the following models:
403095: 3N 400 V a. c. 50Hz Maximum Operating Current: 1.0A (max line fuse 4A)
403096: 3N 400 V a. c. 50Hz Maximum Operating Current: 2.0A (max line fuse 4A)
403097: 3N 400 V a. c. 50Hz Maximum Operating Current: 4.0A (max line fuse 8A)
403098: 3N 400 V a. c. 50Hz Maximum Operating Current: 7.0A (max line fuse 16A)
403099: 3N 400 V a. c. 50Hz Maximum Operating Current: 14.0A (max line fuse 25A)
SAFETY
All electrical installation must be undertaken by a suitably qualified and competent person and must be carried
out in accordance with all relevant Statutory Requirements. Please check the details on the unit rating plate to
ensure that the correct power supply (Voltage, Frequency and Phase) is available. Do not use the speed
controllers with an incorrect power supply, overheating and failure of the circuit board will occur.
The controller must not be used when the ambient air temperature may exceed 40ºC and where it is liable to be
subjected to water spray.
INSTALLATION
The controller is suitable for surface mounting only. Remove front cover and ensure back box is securely fixed
to wall in a well-ventilated area. Route supply and load cables through `Knock-out` holes provided. If the
controller is mounted on a conductive (metal) surface, that surface must be earthed.
GENERAL WIRING
Warning: The Control Equipment Must Be Isolated From The Power Supply During Installation And / Or
Maintenance. The Equipment Must Be Earthed.
Connect the power supply from the local isolator (via any appropriate controls if fitted) and the load supply to the
back box via an appropriate cable gland. Refer to the wiring diagram and select the appropriate connections for
the controller and / or other devices as being installed. Ensure that all earth connections have been made.
Transformers within these controllers are not short circuit proof and the necessary short circuit and overload
protection must be provided.
L-BAL-E176-GB 1240 Index 001
Part. No. 00163613-30
Page 1 / 4
VA Ref. 403147A 0912

Advertisement

loading

Summary of Contents for Vent-Axia 403095

  • Page 1 BEFORE COMMENCING INSTALLATION. These instructions refer to the following models: 403095: 3N 400 V a. c. 50Hz Maximum Operating Current: 1.0A (max line fuse 4A) 403096: 3N 400 V a. c. 50Hz Maximum Operating Current: 2.0A (max line fuse 4A) 403097: 3N 400 V a.
  • Page 2 After completing and checking the connections to the controller replace the front cover ensuring that it is correctly seated in place. Ensure that all cable gland / grommet fixings and lid fixings are tightened correctly to prevent water ingress. Transformers within these controllers are not short circuit proof and the necessary short circuit and overload protection must be provided WIRING DETAILS Wiring details up to 7.0 Amps...
  • Page 3 Wiring details 14.0 Amp unit only Motor without external thermal contacts 400V 3PH 50Hz supply  CHECK LIST 1) Are all links and wiring complete (refer to wiring diagram)? 2) Are all fixings secured? 3) Are all protective circuit devices fitted and wired correctly? 4) Are all covers and gland fittings secure? 5) Are all earth connections secured? 6) Check that no hazard exists for persons in the locality of the fan.
  • Page 4 TECHNICAL SUPPORT: Tel: 0844 8560595 Fax: 01293 539209 For details of the warranty and returns procedure please refer to www.vent-axia.com or write to Vent-Axia Ltd, Fleming Way, Crawley, RH10 9YX L-BAL-E176-GB 1240 Index 001 Part. No. 00163613-30 VA Ref. 403147A 0912...

This manual is also suitable for:

403096403097403098403099