MB-LS-1
Lighting brightness
level transducer
with Modbus RTU output
Do not dispose of this device in the trash along with other waste!
According to the Law on Waste, electro coming from households free of charge and can
give any amount to up to that end point of collec� on, as well as to store the occasion of
the purchase of new equipment (in accordance with the principle of old-for-new, regard-
less of brand). Electro thrown in the trash or abandoned in nature, pose a threat to the
environment and human health.
Purpose
The transducer continuously measures the brightness level (light
intensity) in the range of 1÷9500 lx and exchanges data using
the RS-485 port in accordance with the Modbus RTU protocol.
Features
» Measurement of light intensity;
» Operating status of the sensor.
Functioning
The module continuously measures brightness with a built-in
sensor at a frequency of 1Hz (once per second). Readout of valu-
es, setting of all measurement, communication and data exchan-
ge parameters are carried out through the RS-485 port using the
Modbus RTU communication protocol. The result saved in the
module register is an average value from the set number of last
samples from the range 1÷30 (for example setting the value
of 30 means that the result will be the average of the last 30
seconds).
F&F Filipowski L.P.
Konstantynowska 79/81, 95-200 Pabianice, POLAND
phone/fax (+48 42) 215 23 83 / (+48 42) 227 09 71
www.fif.com.pl; e-mail: biuro@fif.com.pl
v2
- 1 -

Advertisement

loading

Summary of Contents for F&F MB-LS-1 v2

  • Page 1 F&F Filipowski L.P. Konstantynowska 79/81, 95-200 Pabianice, POLAND phone/fax (+48 42) 215 23 83 / (+48 42) 227 09 71 www.fif.com.pl; e-mail: biuro@fif.com.pl MB-LS-1 Lighting brightness level transducer with Modbus RTU output Do not dispose of this device in the trash along with other waste! According to the Law on Waste, electro coming from households free of charge and can give any amount to up to that end point of collec�...
  • Page 2: Transducer Design

    The module is able to signal sensor operation and overheating (status of register 512). Exceeding the critical temperature of 80°C may cause incorrect operation of the measuring system. Transducer design Transducer in special, compact-sized plastic box, connected thro- ugh a PG7 cable gland with circular cables of any length, maxi- mum diameter ø7.
  • Page 3 Separation No galvanic isolation between power supply, RS-485 line and sensor inputs. Mounting It is recommended to use shielded twisted-pair cables to connect the module to another device. When using shielded cables, ground the screens only on one side and as close to the device as possible. Do not route signal cables in parallel in close proximity to high and medium voltage lines.
  • Page 4 Installing the transducer in direct sunlight may cause the system to overheat on hot summer days. 1. Before installing the module, set the selected Modbus com- munication parameters and measurement options. 2. Disconnect the power supply. 3. Unscrew the cover fixing screws. 4.
  • Page 5 Command codes (cont.) code code description name (dec) (hex) Setting the value of 0x06 Write Single Register a single register Setting the value of 0x10 Write Multiple Registers multiple registers Reading and setting Read/Write Multiple 0x17 the value of multiple Registers registers Register types...
  • Page 6 Variable types name acr. description range 16 bit variable -32768÷32767 with sign 16 bit variable unsigned int uint 0÷65535 without sign Measurement and status registers address description reg. variable Brightness level [lx] uint Operating status of measurement sensor: 0 – normal operation; uint 1 –...
  • Page 7 Configuration registers (cont.) address description reg. variable Read current and write new parity uint value: 0:NONE/1:EVEN/2:ODD Number of samples of measurement averaging (range 1÷30). uint Entering 0 deactivates the sensor (OFF state) Restore factory setting of communication parameters. uint Specify value: 1. Status registers address description...
  • Page 8: Technical Data

    Technical data power supply 9÷30 V DC maximum current consumption 40 mA measuring range 1÷9500 lx maximum temperature measurement error ±2% port RS-485 communication protocol Modbus RTU operating mode Slave communication parameters baud rate (adjustable) 1200÷115200 bit/s data bits stop bits parity bits EVEN/ODD/NONE address...