Download Print this page

Secutron MRI-4003-R Installation Instructions

Relay base

Advertisement

Quick Links

INSTALLATION AND MAINTENACE INSTRUCTIONS 
MRI‐4003‐R        Relay Base
ABOUT THIS MANUAL 
This manual is included as a quick reference for installation 
and should be left with the owner/operator of this 
equipment. For further information on the use of this 
device with a FACP, please refer to the panel's manual. 
Note: This manual should be left with the owner/operator 
of this equipment. 
RELAY BASE DESCRIPTION 
The MRI‐4003‐R relay base is designed to meet UL268/ULC 
S529 requirements for smoke detector, UL521/ULC S530 
requirements for heat detector. 
The MRI‐4003‐R must be used with a compatible Secutron 
control panel. The device can control one independent 
circuit while using one address.   
The MRI‐4003‐R provides one form C (SPDT) contact rated 
at 2A at 30Vdc, or 0.5A at 125Vac and a compatible panel 
can switch discrete contacts by code command. Circuit 
connections to the relay contacts are not supervised by the 
base. MRI‐4003‐R supports group activation capability for 
fast reaction time.  
LT‐6697SEC Rev 0 March 14 2023 
25 Interchange way, Vaughan, Ontario. L4K 5W3 
Phone: 905.660.4655; Fax: 905.660.4113 
CAUTION / ATTENTION
DO NOT PAINT OR ALTER  
FACTORY APPLIED FINISH IN ANY WAY 
NE PAS PEINDRE OU MODIFIER 
LA FINITION ORIGINALE
Figure 1 MODEL FRONT AND SIDE VIEW 
WITH MRI‐4000 SERIES DETECTOR 
Table 1 SPECIFICATION 
Operating temperature 
Humidity range 
SLC Standby Current 
SLC Alarm Current 
Base Diameter 
Base Height 
Terminal wire gauge 
Web: www.secutron.com 
 
 
0⁰C to 49⁰C  
(32⁰F to 120⁰F) 
0% to 93% 
1.16 mA 
1.18 mA 
182mm [7‐3/16 in] 
32mm [ 1‐1/4 in] 
12‐22 AWG 

Advertisement

loading
Need help?

Need help?

Do you have a question about the MRI-4003-R and is the answer not in the manual?

Questions and answers

Summary of Contents for Secutron MRI-4003-R

  • Page 1 25 Interchange way, Vaughan, Ontario. L4K 5W3  Phone: 905.660.4655; Fax: 905.660.4113  Web: www.secutron.com  INSTALLATION AND MAINTENACE INSTRUCTIONS    CAUTION / ATTENTION DO NOT PAINT OR ALTER   MRI‐4003‐R        Relay Base FACTORY APPLIED FINISH IN ANY WAY  NE PAS PEINDRE OU MODIFIER    LA FINITION ORIGINALE ABOUT THIS MANUAL  Figure 1 MODEL FRONT AND SIDE VIEW  WITH MRI‐4000 SERIES DETECTOR  This manual is included as a quick reference for installation  and should be left with the owner/operator of this  equipment. For further information on the use of this  device with a FACP, please refer to the panel’s manual.  Note: This manual should be left with the owner/operator  of this equipment.  RELAY BASE DESCRIPTION  The MRI‐4003‐R relay base is designed to meet UL268/ULC  S529 requirements for smoke detector, UL521/ULC S530  requirements for heat detector.  The MRI‐4003‐R must be used with a compatible Secutron  control panel. The device can control one independent  circuit while using one address.    Table 1 SPECIFICATION  0⁰C to 49⁰C   Operating temperature  The MRI‐4003‐R provides one form C (SPDT) contact rated  (32⁰F to 120⁰F)  at 2A at 30Vdc, or 0.5A at 125Vac and a compatible panel  0% to 93%  Humidity range  can switch discrete contacts by code command. Circuit  1.16 mA  SLC Standby Current  connections to the relay contacts are not supervised by the ...
  • Page 2 Figure 4 WIRING TABS  KEY COMPONENT  Figure 2 RELAY BASE ASSEMBLY COMPONENTS  Mounting plate  #8‐32 x 3/4"  screws (x2)  Sounder base  enclosure  M3 x25 mm  screws (x2)  Figure 3 MRI‐4000 SEREIS DETECTOR  MRI‐4000 series  detector  A mounting plate in figure 2 is mounted first on the  electrical box and all wiring is done on integral screw  connectors. The connections are apparent and can be  visually inspected before the sounder base itself is  Use  the  mounted. Then, the enclosure containing the electronics,  the sounder and the detector base can plugged‐in and  information in this document to determine the total  secured.   current draw of the devices. The total current draw of the  devices must not exceed the NAC output capacity of the  Note: This device should be installed as per applicable  panel. In all cases, the installer should consider the voltage  requirements of the authorities having jurisdiction.  drop to ensure that the last device on the circuit operates  WIRING  within its rated voltage. Please consult fire panel  Before installing this device seek guidance from the  installation manual for guidance on wire resistance and  compatible control panel instructions for the device  length. For maximum strobe operating current, please  operation modes and the configuration requirements. It is  refer to Table 4.   recommended to remove power from SLC and NAC lines  before performing installation.  Do not loop signal circuit field wires around terminals.  Electrical supervision requires wire run to be broken at ...
  • Page 3 Figure 5 DEVICE CONNECTION  Note: Wiring must be in accordance with CSA C22.1,  Figure 6 MOUTING DIAGRAM Canadian Electrical Code, Part I, Safety Standard for  Electrical Installations, section 32 and/or NFPA 70.  CAUTION  FOR SYSTEM SUPERVISION, FOR ALL TERMINAL TAPS, DO  NOT USE LOOPED WIRE UNDER TERMINALS. BREAK WIRE  RUN TO PROVIDE SUPERVISION OF CONNECTIONS.   ATTENTION  NE PAS UTILISER DE FILS EN BOUCLE SOUS LES BORNES.  POUR FOURNIR UN BON SUIVI DES CONNEXIONS.  INTERROMPRE LA CONTIUITÉ DES CÂBLES.  Step 1  MOUNTING  Secutron recommends spacing speaker strobe appliances  in compliance with CAN/ULC S524 and/or NFPA72.   Step 2  The mounting plate is compatible with 3” by 2” single gang  device boxes, 3-3/4” by 4” double gang boxes, 4” by 2”  single gang utility boxes, standard 4” by 4” boxes, and  standard 4” octagon boxes.  1. Attach the mounting plate to electrical box with two mounting #8‐32 x 3/4" screws. Step 3  2. Slide down the sounder base enclosure until the connection blades touch the clips on the mounting plate. 3. Secure the mounting plate with securing M3 x25 mm screws.
  • Page 4 MOUNTING DETECTOR  Figure 9 DETECTOR ALIGNMENT MARK If the detector type and address has be visible from the  Alignment  outside, break the address tab inside the detector base  mark  and insert it in the outer rim of the base. See figures 7.  Figure 7 ADDRESS TAB INSERT  Breakaway  Insert  address tab  The detector can then be placed on the top base using the  following steps (figure 8):  1. Position the detector centrally on its adapter base ensuring it is level. 2. Rotate clockwise applying gentle pressure. The detector will drop into its keyed location. 3. Continue to rotate clockwise a few degrees until the detector has fully engaged in the adapter base. 4. When the detector is firmly engaged, check the alignment of the raised reference marks on the detector and on the base (figure 9). Figure 8 MOUNTING DETECTOR  Model Numbers  MRI‐4003‐R 4000 SERIES RELAY BASE  Accessories  4000 SERIES DETECTORS:  Non‐isolated photoelectric detector   MRI‐4010  Non‐isolated photoelectric detector Rev7  MRI‐4011  MRI‐4010‐ISO  Isolated photoelectric detector  MRI‐4011‐ISO  Isolated photoelectric detector Rev7  MRI‐4020    Non‐isolated photoelectric/heat detector  MRI‐4021    Non‐isolated photoelectric/heat detector Rev7 ...