TE Connectivity W6 Series Manual

Magnetic hydraulic p&b circuit breakers

Advertisement

Quick Links

Designed for the international market. UL Recognzied (UL1077 and
n
UL1500), CSA Accepted and VDE approved.
Ratings to 50 amps.
n
Heavy duty #10-32 stud connections. (W9)
n
Quick-connect or screw terminals. (W6)
n
Several delay curve options.
n
Trip-free operation.
n
Agency Approvals
UL:
Recognized as Supplementary Protector under UL 1077. Available
models meet Ignition Protection requirements in accordance with
UL1500. File E69543
CSA: Accepted as a Supplementary Protector. File LR15734.
VDE: Approved to VDE 0642/EN 60 934 (Circuit Breakers for Equipment)
License No. 73782
Users should thoroughly review the technical data before selecting a product part number.
It is recommended that users also seek out the pertinent approvals files of the agencies/
laboratories and review them to confirm the product meets the requirements for a given
application.
Electrical Data
Calibration:
Breakers will hold 100% of rated current.
Breakers may trip between 101% and 124% of rated load (134% for AC/
DC units).
Breakers must trip at 125% of rated load and above (135% for AC/DC
units).
Dielectric Strength: 50/60 Hz., 1500V: DC, 1100V
Insulation Resistance: 100 Megaohms at 500VDC
Endurance:
10,000 on/off cycles - 6000 at rated load, 4000 at no load.
Units tested at six cycles per minute, 1 second on and 9 seconds off at
25°C ambient.
Typical Resistance and Impedance
Current
DC
(Amps.)
Resistance
(Ohms)
0.2
90
1.0
1.2
2.0
0.28
5.0
0.04
10.0
0.013
20.0
0.004
30.0
0.0027
40.0
0.002
50.0
0.0015
Tolerance: 0.1 - 4.99 ± 15%; 5 - 9.99 ± 20%; 10 - 15 ± 25%; 16 - 30 ± 50%.
Mechanical/Environmental Data
Operating Temperature: -40°C to +85°C.
Humidity: Meets requirements of Mil-STD-202 method 103.
Shock: Tested per Mil-STD-202, method 213, test condition C
(100g @ 6 ms)
Vibration: Tested per Mil-STD-202, method 201, 10-55 Hz., 0.06"
(1.52mm) total excursion in 2 planes.
11-2015, Rev. 1115
www.te.com
© 2014 Tyco Electronics Corporation,
a TE Connectivity Ltd. company
General Purpose Relays
Industrial Relays
W6/W9 Series Magnetic Hydraulic P&B Circuit Breakers
50/60
Impedance
(Ohms)
90
1.2
0.28
0.04
0.013
0.005
0.004
0.002
0.0015
Datasheets and product specification
according to IEC 61810-1 and to be used
only together with the 'Definitions' section.
Mechanical/Environmental Data
Fungus and Moisture Resistance:
Special moisture resistant finish applied to all ferrous parts.
Plastic parts are made of inherently fungus resistant material.
Marking:
International "1" and "0" symbols are marked on the toggle for both W6 and
W9. W9 units have "ON" and "OFF" molded into the area at the base of the
toggle.
Mounting:
Units are mounted with two #6-32 screws from the front of the panel.
Metric models for use with M3 x 0.5 screws are available. To maintain
published performance specifications, units should not be mounted more
than 90° from their normal upright position.
Weight: Approximately 2.5 ounces per pole.
Approvals and Ratings Table 1
W6 Series
UL1077/CSA (All Circuit Functions)
Maximum
Frequency
Voltage
(Hz)
65
DC
277
50/60
277
50/60
277/480
50/60
W9 Series
UL1077/CSA (All Circuit Functions)
Maximum
Frequency
Voltage
(Hz)
65
DC
277
50/60
277/480
50/60
W6 or W9 Series
VDE (Circuit Function X)
Maximum
Frequency
Voltage
(Hz)
65
DC
250
50/60
250
50/60
415/240
50/60
W6 or W9 Series
UL1500 (Circuit Function X)
Maximum
Frequency
Voltage
(Hz)
48
DC
125/250
50/60
250
50/60
Datasheets and product data is subject to the
terms of the disclaimer and all chapters of
the 'Definitions' section, available at
http://relays.te.com/definitions
Potter & Brumfield
(continued)
Current
Interrupting
Phase
Rating
Capacity
(Amps)
(Amps)
-
0.2 - 50
2,000
1
0.2 - 20
5,000
1
21 - 50
2,500
3Ø-Wye
0.2 - 20
5,000
Current
Interrupting
Phase
Rating
Capacity
(Amps)
(Amps)
-
0.2 - 50
2,000
1
0.2 - 50
5,000
3Ø-Wye
0.2 - 20
5,000
Current
Interrupting
Phase
Rating
Capacity
(Amps)
(Amps)
-
0.2 - 50
2,000
1
0.2 - 30
5,000
1
31 - 50
2,000
0.2 - 30
5,000
Current
Interrupting
Phase
Rating
Capacity
(Amps)
(Amps)
-
0.2 - 50
3,000
1
0.2 - 50
1,000
3Ø-Wye
0.2 - 50
1,000
Datasheets, product data, 'Definitions' sec-
tion, application notes and all specifications
are subject to change.
1

Advertisement

loading

Summary of Contents for TE Connectivity W6 Series

  • Page 1 © 2014 Tyco Electronics Corporation, only together with the ‘Definitions’ section. the ‘Definitions’ section, available at are subject to change. a TE Connectivity Ltd. company http://relays.te.com/definitions...
  • Page 2: General Purpose Relays

    General Purpose Relays Industrial Relays Potter & Brumfield W6/W9 Series Magnetic Hydraulic P&B Circuit Breakers (Continued) Time vs Current Trip Curves For W6 Series and W9 Series AC 50/60 Hz. DC & 50/60 Hz. CURVE 3 SHORT DELAY 50/60 Hz. 400 Hz.
  • Page 3 © 2014 Tyco Electronics Corporation, only together with the ‘Definitions’ section. the ‘Definitions’ section, available at are subject to change. a TE Connectivity Ltd. company http://relays.te.com/definitions...
  • Page 4 © 2014 Tyco Electronics Corporation, only together with the ‘Definitions’ section. the ‘Definitions’ section, available at are subject to change. a TE Connectivity Ltd. company http://relays.te.com/definitions...
  • Page 5 29° 1.660 (42.16) 1.048 1.520 (26.62) 30° (38.61) Ø .156 LOAD [2 PLACES PER POLE] (3.96) W6 Series - One Actuator Per Pole 1 Pole 2 Pole 3 Pole 4 Pole Ø .590 (15.00) 2.250 3.000 .750 1.500 (19.05) (57 .15) (76.20)
  • Page 6 © 2014 Tyco Electronics Corporation, only together with the ‘Definitions’ section. the ‘Definitions’ section, available at are subject to change. a TE Connectivity Ltd. company http://relays.te.com/definitions...
  • Page 7: Outline Dimensions

    © 2014 Tyco Electronics Corporation, only together with the ‘Definitions’ section. the ‘Definitions’ section, available at are subject to change. a TE Connectivity Ltd. company http://relays.te.com/definitions...