Gateway Spare Part Kit
DIRECT CONNECT ANTENNA
100473
Installation and servicing of Danfoss Turbocor® compressors by qualified and product trained personnel only.
Follow these instructions and sound refrigeration/electrical/servicing practices relating to installation,
commissioning, maintenance, and service.
Consult the appropriate
Danfoss LLC Service Manual
on www.turbocoroem.com
for detailed service
instructions.
1 - Introduction
Page 1 of 3
Never power compressor
without covers in place and
secured.
Removing the mains input
cover will expose you to a
voltage hazard of up to 575V.
Ensure the mains input power
is off and locked out before
removing cover.
Before removing top cover,
wait at least 20 minutes after
isolating AC power to allow
the high voltage capacitors to
discharge.
Figure 1 – Direct Connect Antenna
Document number: 720076 REV A
Classified as Business
ENGINEERING
TOMORROW
Always wear appropriately
rated safety equipment when
working around equipment
and/or components
energized with high voltage.
This equipment contains
hazardous voltages that
can cause serious injury or
death.
© Copyright Danfoss | 2023.5
Recover all refrigerant
from compressor in
accordance with local
codes and ensure pressure
is fully vented before the
removal of refrigerant
containing components.