ICM Controls ICM550-ENC Quick Start Manual

ICM Controls ICM550-ENC Quick Start Manual

Multi-functional timer

Advertisement

Quick Links

Applications
• Commercial defrost timer
• Pool & spa circulation pumps
Specifications
Inputs:
• Nominal voltage range: 120-240 VAC
• Frequency: 60Hz
Outputs:
• Type: Relay
Contact Ratings:
• Compressor: [2]&[4]: 30A R, 1HP @ 120 VAC, 2HP @ 240 VAC
• Electric heat: [1]&[3]: 40A R, 1HP @ 120 VAC, 2HP @ 240 VAC
• Fan: [1]&[F]: 30A R, 1HP @ 120 VAC, 2HP @ 240 VAC
Environmental
• Operating temperature: -40 to +131°F
• Operating humidity: 0-95%, non-condensing
Mechanical
• Construction: Open board (plastic bracket mounted). The
ICM550-ENC comes packaged in a NEMA Type
4X rated weatherproof enclosure
• Mounting: Vertical or horizontal orientation
Timing
• Minimum cycle time: 15 minutes
• Maximum cycle time: 23 hours 45 minutes
• Terminate cycle: Cycle can be terminated by shorting "X to N"
Status LED
• Cycle mode: (Red LED)
• Normal mode: (Green LED)
Replaces
• Grasslin: 010-0011B, DT040, DT140, DTAV40, DTMV, DTSX
• Paragon: 8041, 8045, 8047, 8141, 8143, 8145, 8245, 8247
• Precision: 6041, 6045, 6047, 6141, 6145
Package Contents
ICM550 control module, bracket mount, installation guid, terminal
block & wiring diagram label sheet, #8 x 1/2" sheet metal screws
(3), #6 x 1/2" hex head screws (4)
> > > CAUTION < < <
ELECTRICAL SHOCK HAZARD!
power at the main service panel by removing the fuse or
switching the appropriate circuit breaker to the OFF position
before working on a high voltage control.
Installation of the ICM550 shall be performed by
CAUTION!
trained technicians only. Adhere to all local and national electric
codes.
Never turn the dial backward, always turn the dial
WARNING!
clockwise to adjust. Do not attempt to touch or adjust the hands of
the clock as this may cause permanent damage to the clock.
Terminal Block
"USE COPPER WIRES ONLY"
Tightening torque 15 in-lb.
Sample Wiring Diagram (for defrost application)
L1
120
VAC
L2
To Set the Current Time
The following example shows the
clock set to 2:30 PM.
Turn the outer dial clockwise
until the inner clock hands
point to the correct time.
Each tick mark on the outer
dial represents 15 minutes.
The inner dial is representative
of conventional clock, with the
printed "hand" showing the hour
and the physical hand showing the
minute. The time displayed on the inner dial will always
correspond with the time on the outer dial.
To Set Defrost Time
Determine the appropriate cycle
time for your application. Next,
set the switches for each 15
minute interval you require
by moving the switch to the
outer position.
Each switch represents a 15
minute interval and there are
4 intervals per hour.
In this example, the system will
begin one timed cycle at 5:00 PM,
Turn off
which will last for 45 minutes (3 intervals).
The unit will resume normal operation at 5:45 PM.
If multiple cycles are required, please select the appropriate
dipswitches to represent each 15 minute interval throughout
the 24 hour period where desired.
ICM
Multi-Functional Timer
K
K
1
2
F
3
1
2
4
T-Stat
Defrost
Heater
Compressor
Contactor Coil
Solenoid Valve
550-ENC
Switch Position
Mode A
N
X
Defrost
Thermostat
w/ Fan Delay
Fan
LIAF304

Advertisement

loading

Summary of Contents for ICM Controls ICM550-ENC

  • Page 1 Turn the outer dial clockwise Mechanical • Construction: Open board (plastic bracket mounted). The until the inner clock hands ICM550-ENC comes packaged in a NEMA Type point to the correct time. 4X rated weatherproof enclosure Each tick mark on the outer •...
  • Page 2 Mode Selection Switch The Mode selection switch is used to set up the condition of relay K2 based on the model you are replacing (See Table 1). When set up in Position A, relay K2 is normally closed and will open during the timed cycle. When set up in position B, relay K2 is normally open and will close during the timed cycle.