SFR-M Series Low-voltage Harmonic Suppression Reactive Compensation Module User’ Manual JIANGSU SFERE ELECTRIC CO., LTD.
Page 2
Thank you for choosing SFR-M series low voltage harmonic suppression reactive compensation module. In order to make it convenient for you to purchase and use the meter safely, correctly and efficiently, please read this manual carefully before using the product, and pay attention to several points as follows.
JB/T 9663-1999 Low-voltage reactive power automatic compensation controller 1.2 Overview SFR-M series low voltage intelligent power capacitor modules take two △ type compensation capacitors or one Y type compensation capacitor as main body and are highly integrated with compound switch, microprocessor and other function modules. Due to their modularity structure, they have such advantages as small volume and easy maintenance.
Remarks Compensation Capacity mode (kvar) 20+20 Two channel total compensation 20+10 Two channel total compensation 10+10 Two channel total compensation 10+5 Two channel total compensation Single channel Three phase total total compensation compensation Single channel total compensation Single channel total compensation Single channel total...
AC 380V±20%, distortion rate≤5% Working voltage 1.35*In Max. working current Compensation Switching inrush ≤ operation current 100 万次 Switching times 1.2*Un (can be set) Over voltage 0.8*Un(can be set) Host protection Under voltage can be set Harmonic exceeding can be set Over current 55℃(can be set)...
4.3.3 Secondary Current Transformer is an optional unit which is used for primary current (5A) sampling in bus line of incoming cabinet. The transformer is necessary when customer only use SFR-M series low voltage harmonic suppression reactive compensation module. Usually SFR-M series modules are defaulted to be equipped with reactive power compensation controller (...
Page 8
WGK-31-203-G compensation controller is suitable, otherwise, please equip WGK-31-203-F compensation controller in that system. SFR-M series modules are connected with WGK-31-203 compensation controller by specialized pluggable data line. One WGK-31-203 controller can be connected up to 32 SFR-M series modules.
Secondary current Secondary of cabinet current (≤5A) transformer SFR series SFR series Pluggab le data (total (total line interface compensation) compensation) Capacitor status indication light(380V) Wiring diagram for total compensation module and separate compensation module combined system without controller 5. Operation 5.1 Using method of buttons on digital display panel This interface is composed of the following three buttons.
Page 10
5.3 Programming examples (1) The following operation process shows and example for system setting. ( 2 ) The following operation process shows and example for setting internal network address. Note: there should not be same network addresses in a control system.
(3) The following operation process shows an example for module switching parameters (Usually it is not needed to set these parameters only if there is no controller.) 6. Panel description and measurement information display...
Page 12
1. C1 and C2 indication lights show the switching and running status of two capacitor modules; if Fault indication light is on, that means the power capacitor module is in protection status. 2. Three-row code segment LCD shows measured electrical information such as present status of power capacitor module, capacity, temperature and electrical parameters.
Page 13
The left picture shows the temperature of separate compensation module. Three phase The left picture shows the value current of current in compensation status. Three phase The left picture shows the value voltage of bus line voltage. The left picture shows the Input current current of incoming cabinet (only effective in host module).
Page 14
The left picture shows the Reactive power reactive power of incoming cabinet (only effective in host module). The left picture shows the total Total apparent apparent power of incoming cabinet power (only effective in host module). The left picture shows the power Power factor factor of incoming cabinet (only effective in host module).
automatically; Er 06: Three phase unbalance protection, need to be reset; Er 07: Harmonic voltage protection THDu%, return to normal automatically; Er 08: Harmonic current protection THDi%, return to normal automatically; Er 09:Internal fault, need to be reset. 7. Common problems and solutions 7.1 Automatic switch in after power on The compound switch inside a module is defaulted to be open, but it may become closed because of vibration in transportation.
in; if the indication light is off, that means the capacitor module is switched off. ② Controller normal switching test 1) Change the dial switch on the capacitor module to Work; 8.Change the power factor of circuit. Controller will control the real switching of capacitor modules according to power factor.