Condair AX 02 Installation And Operating Manual

Reverse osmosis system
Table of Contents

Advertisement

Quick Links

CONDAIR AX
Reverse osmosis system
INSTALLATION AND OPER-
ATING MANUAL
Condair AX reverse osmosis system
08/11/2023
Air humidification, dehumidification
and evaporative cooling

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the AX 02 and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Condair AX 02

  • Page 1 CONDAIR AX Reverse osmosis system INSTALLATION AND OPER- ATING MANUAL Condair AX reverse osmosis system 08/11/2023 Air humidification, dehumidification and evaporative cooling...
  • Page 2 Non-compliance with this is punishable by law and will result in compensation for damages. Liability Condair GmbH does not accept any liability due to incorrect installation or operation of the equipment or due to use of parts/components/equipment that are not authorised by Condair AG. Copyright notice...
  • Page 3: Table Of Contents

    Contents General safety instructions Explanations of symbols and instructions Operator obligations Personnel obligations Training of personnel Intended use Hazards when handling the equipment Protective devices and safety measures to avert hazards 1.7.1 Protective devices 1.7.2 Informational safety measures Safety instructions for maintenance work Disposal of system parts and operating materials 1.10 Unauthorised modification and replacement parts...
  • Page 4 Operations log for reverse osmosis systems Maintenance 9.3.1 Maintenance plan for reverse osmosis systems Appendix 10.1 Assembly layout (schematic) 10.2 P&I diagram 10.3 Dimensions of AX 02 10.4 Dimensions of AX 05, 12 and 20 10.5 Dimensions of AX 30 and 50 Contents...
  • Page 5: General Safety Instructions

    General safety instructions Explanations of symbols and instructions This operating manual contains important information on the safe operation of the system. This operating manual, in particular the chapter “Safety instructions” must be observed by all persons working on the system. This applies to the installation company as well as to the system operator.
  • Page 6: Personnel Obligations

    Personnel obligations All persons who are commissioned to work on the system or who carry out such work inde- pendently undertake the following before commencing work:  T o read the chapter on safety and the warnings in this operating manual and to acknowl- edge with their signature that they have understood them.
  • Page 7: Protective Devices And Safety Measures To Avert Hazards

     C heck the electrical equipment of the installation regularly. Remove loose connections and scorched cables immediately.  T he switch cabinet must be kept locked at all times. Access is only allowed to authorised person- nel.  I f work on live parts is required, a second person must be called in who can switch off the main switch if necessary.
  • Page 8: Safety Instructions For Maintenance Work

    Safety instructions for maintenance work  T he operator must ensure that all maintenance, inspection, and assembly work is carried out by authorised, qualified technicians who have sufficiently informed themselves by studying the operating manual in detail.  B efore carrying out any repair or maintenance work, the system must be switched off and secured against being accidentally put into operation. The procedures for shutting down the system described in section “Commissioning and decommissioning”...
  • Page 9: Safety Instructions For Storage

    1.12 Safety instructions for storage CAUTION! The reverse osmosis system is protected by a preservative against microbial contamination and against risk of frost down to -10°C. At room temperature (< 25°C), this preservative must be purged and replaced within 6 months at the latest. At higher temperatures, the protection period is correspondingly shorter (3 months at 30°C).
  • Page 10: Principles Of Reverse Osmosis Systems

    Principles of reverse osmosis systems Calculation equations The permeate output, the concentrate output and the permeate conductivity are determined by read- ing the corresponding measuring equipment on the system. If no indicating instruments (e.g. variable area flow meter) are present, the permeate output and the concentrate output are determined by manual volumetric measurement. Feed water output permeate output + concentrate output (permeate output [l/h]) Yield [%]...
  • Page 11: Conductivity Of First Permeate

    CAUTION! If the system is operated at a feed water temperature higher than the design temperature, the maxi- mum permeate output specified on the nameplate and in the technical data must not be exceeded! Permeate capacity [l/h] At temperature T[°C] = Nominal power * Correction factor Temperature T in °C Information Correction factor 1.30 1.28 1.25 If the actual permeate output 1.21...
  • Page 12: Transport And Storage

    Transport and storage Transport to the customer CAUTION! During transport, all units must be secured against slipping and falling over! Tipping from a fixed position is not permitted! If parts of the equipment protrude from the base area of the pallet, then such protruding parts must not be damaged when further parts/equipment are loaded.  T he transport weight corresponds to the tare weight and can be found in the technical data.  H owever, the system may be damaged by extreme frost. The units are filled with a preservative/ antifreeze mixture prior to delivery.
  • Page 13: Technical Data / Product Description

    Technical data / Product description Technical data Type AX Recommended quality of the feed Soft water 0˚dH water Ratings 1) Permeate output at 3 bar Permeate output at 1 bar Yield when taking in - Soft water - Hard water 35–40 Desalination rate 96 / 98 Intake pressure (min./max.) 2 / 6...
  • Page 14: Application Limits

    Application limits The membranes are wear parts in the longer term. Their service life depends on the feed water qual- ity and the operating conditions. In order to achieve a projected membrane service life of 3 years, the reverse osmosis systems should be operated with softened water or with hard water according to the system type, in each case in the same quality as drinking water according to the German Drinking Water Ordinance and according to the following additional specification: Parameter...
  • Page 15: Product Description

    Product description 4.3.1 Layout The following P&I diagram shows the structure of an AX reverse osmosis system: Supply limit Feed Permeate water F-01 P-01 M-01 Supply limit D-01 Supply limit MSR point list Actuators Local display of pump pressure and Shut-off valve for feed water, manu- PI 1 working pressure...
  • Page 16: Function

    4.3.2 Function The RO feed water reaches the HP pump via a residual hardness monitor (optional accessory, only when using softened water) and a protective cartridge filter (grade of filtration 5 µm). This pump con- veys the water at high pressure (level depends on the size of the system and the desired permeate pressure) through the semi-permeable membranes. Water largely freed from salts passes through the membranes and forms the permeate (desired product).
  • Page 17: Installation And Assembly

    Installation and assembly Installation 5.1.1 Requirements of the installation site  T he space required for the unit is derived from the dimensions specified in the technical data. In addition, there should be 0.8 m of space in front of the unit to allow access for operation and 1.0 m of space to the side for maintenance.  T he place of installation must comply with the ambient conditions as specified in the technical data.
  • Page 18: Water Connections

    Water connections 5.2.1 Required qualification of assembly personnel NOTE The water connection must only be carried out by trained specialist personnel. General directives (DIN, DVGW, SVGW, ÖKGW) and local installation regulations must be observed when installing the system. 5.2.2 Establishing the water connections Feed water  Remove the sealing disk from the screw connector in the feed water inlet and keep it.
  • Page 19: Electrical Connection

    Electrical connection 5.2.1 Required qualification of assembly personnel DANGER! The electrical installation must be carried out by an electrician in compliance with the installation guidelines of the VDE, utility suppliers, factory standards, etc. according to the valid country-specific regulations. 5.3.2 Establishing the electrical connections DANGER! Before connecting the system to the power supply, make sure that the corresponding on-site main switch is switched off.
  • Page 20: Terminal Connection Table

    5.3.5 Terminal connection table Kl.Nr. Usage Descr. Function Phase, supply 230V AC Neutral conductor, supply Protective conductor Protective conductor Protective conductor Neutral, consumer UO High Pressure Relay, normally open contact, supply switching 230V Neutral, consumer Relay, normally closed contact, supply switching Input solenoid valve 230V AC Relay, normally open contact, supply switching 230V...
  • Page 21 Protective UO pump Input valve Concentrate Collective alarm conductor 230 VAC 230 VAC valve for consumers with 230 VAC Forced stop Tank full Pressure switch input Conductivity Tank level Temperature sensor Supply 230 VAC Installation and assembly...
  • Page 22: Commissioning And Decommissioning

    Commissioning and decommissioning Commissioning 6.1.1 Qualification of commissioning personnel CAUTION! The system must be commissioned by qualified specialist personnel. NOTE Before commissioning the system, all screw connections must be tightened. 6.1.2 Flushing out the preservative WARNING! The preservative solution contains 1.5% sodium bisulphite and 20% glycerine. The flushed-out pre- servative solution must be discharged into the sewage system in accordance with the locally applica- ble discharge regulations.
  • Page 23: Decommissioning

    Setting the permeate outlet pressure 6.1.5 The permeate outlet pressure may be preselected in the range 1 to 3 bar at pressure switch PS 2. The factory setting is 3 bar. If a lower outlet pressure is required, the precharge pressure in the dia phragm pressure vessel must also be adjusted by inflating or deflating according to the according to the following table: Permeate outlet pressure at which production...
  • Page 24: Control Panel

    Control Panel Control and display element 7.1.1 Control panel Type of menu item displayed Context-sensitive controls DOWN Enter Button Button Button Button 7.1.2 Context sensitive menu elements The display shows elements that are in context to the current display content: Main menu or submenu of it Input for logical parameter, setting with UP or DOWN keys.
  • Page 25: User Menu

    7.1.4 Buttons The control panel includes the following four keys: In the main menu, a submenu can be exited with the ESC key without accepting changes, or the main menu can be exited completely. The UP key is needed for moving up in menus. It is also used to change parameters: Numerical parameters → Press once = increase the value by 1.
  • Page 26 Control panel...
  • Page 27 7.2.2 Insulation 7.2.2/1 Retry time Main menu → Settings → Input → Retry time NAfter opening the inlet valve K1, a short delay time (60s are set in the factory) is active, during which the pressure must build up. If pressure has not yet built up after this delay, the inlet valve K1 is closed.
  • Page 28 Select minimum limit values for a warning Min(Warning) or for an alarm Min(Alarm) as well as maximum limit values for a warning Max(Warning) or for an alarm Max(Alarm) for the case that these conductivity values are exceeded or undershot. For each message (warning or alarm) it is also possible to set separately a delay, a hysteresis Hyst.
  • Page 29 Control panel...
  • Page 30 7.3.2 Displays during pause flushing The design of the tank (without or with overflow) determines whether during a pause rinsing (this is an interval operation during production pauses due to a full tank). UO pump P-01 may be switched on. If the tank has an overflow, the P-01 HP pump is switched on, with the additionally pro duced permeate draining off via the overflow. If there is no overflow (as when using a diaphragm pressure vessel), the pause rinsing takes place without switching on the P-01 UO pump. NOTE The time displays in the example masks have no logical value, they are without meaning. NOTE The permeate tank without overflow setting is preset by default in the systems of the two AX series. The following table contains the possible displays of the AX series during pause rinsing:...
  • Page 31 7.3.3 Disturbed operation 7.3.3/1 Display color scheme In case of a warning, the background of the display appears completely in orange. Call the cause of the warning with the ESC key under the magnifying glass icon auf! In the event of an alarm, the background of the display appears completely in red. Call the cause of the alarm with the ESC key under the magnifying glass icon auf! 7.3.3/2...
  • Page 32: Parameters

    7.3.3/3 Possible alarms NOTE Depending on the selection of the „Reaction system“ parameter, production is stopped or not in case of an alarm! Below you will find an overview of all possible alarms: Alarm acknowledgement if alarm cause persists If an alarm is acknowledged whose cause has not been eliminated, then the alarm appears again when the delay time assigned to the alarm reason assigned to the alarm reason has expired.
  • Page 33 Control panel...
  • Page 34 Control panel...
  • Page 35 Control panel...
  • Page 36: Fault Elimination

    Fault elimination General information By using high-quality individual components and due to the built-in safety and monitoring devices, a very high degree of operational reliability is achieved. S hould a malfunction nevertheless occur, the fault can be easily identified and the cause eliminated using the fault table set out below. If serious malfunctions occur, please contact the manufacturer (see nameplate). WARNING! Fault elimination may only be carried out by qualified and instructed personnel in compliance with the safety regulations in chapter A of this operating manual!
  • Page 37 Fault/message Possible causes Remedy Display unlit Mains supply interrupted Establish mains supply 230VAC/6.3 AT fuse defec- Replace fuse concerned tive Controller defective Replace controller Alarm display Forced stop Residual hardness sensor  Check soft water quality triggered (if present)  Check sensor and replace it, if required Display shows “Low inlet Feed water pressure too low...
  • Page 38 speed due to the increase in the concentrate volume flow and, due to the associated increase in shear forces, easily detachable deposits are removed and flushed out. Flushing the concentrate should last at least 60 minutes and should be carried out as follows:  Log the actual values (enter in operations log according to chapter 9.2.2)  Open the concentrate control valve completely or remove the concentrate screen (depending on the type of system).
  • Page 39: Inspection And Maintenance

    Inspection and maintenance Inspection and maintenance work 9.1.1 Safety instructions CAUTION! The operator must ensure that all inspection, maintenance, and assembly work is carried out by authorised, qualified technicians. Before carrying out any repair or maintenance work, the system must be shut down and secured against being accidentally put into operation.
  • Page 40: Logging The Operating Parameters

    Logging the operating parameters 9.2.1 List of parameters to be logged The following parameters must be checked weekly and entered in the operations log for reverse osmosis systems: Parameter Measuring point / remarks Operating hours of the RO system Display/menu of the control panel Residual hardness in the feed water Check with hardness test kit in feed water Conductivity of feed water...
  • Page 41: Operations Log For Reverse Osmosis Systems

    9.2.2 Operations log for reverse osmosis systems Customer:_________________________________________________________________________ System type: ______________________________________________________________________ Order No.: ________________________________________________________________________ Commissioned on: __________________________________________________________________ At com- Date Date Date Date Date Measured variable Unit mission- Operating hours of the RO system Residual hardness in the °d feed water Conductivity of feed water µS/cm Temperature of feed water...
  • Page 42: Maintenance

    Maintenance NOTE Maintenance work for the system must be carried out globally after 4000 operating hours (a maintenance message is sent) and for each system part separately as required, no later than the specified maintenance intervals or described situations (column “No later than as per operating time or described situation”)! 9.3.1 Maintenance plan for reverse osmosis systems In the user menu you can query the operating time remaining until the next maintenance (see chapter 7 - Control panel).
  • Page 43 Conductivity permeate (QI 1) daily   Working pressure (PI 1) daily   Total hardness feed water weekly   Temperature feed water weekly   Control parameters pH value monthly   Conductivity feed water According to demand ...
  • Page 44: Appendix

    Appendix 10.1 Assembly layout (schematic) System separator Fine filter 1“ Untreated water 1“; 3–6 bar Drain water Test valve Drain water Drain water 13 mm Water softener Soft 60 - 400 1“ connections 230V power point Hardness monitor Limitron (optional) Already installed in AX 12/20/30/50 Reverse osmo- sis system...
  • Page 45: P&I Diagram

    10.2 P&I diagram Supply limit Supply limit PERMEATE UNTREATED WATER MSR units and actuators MSR point list PI 1 Local display of pump pressure and working pressure PI 2 Local display of permeate pressure PS 1 Pressure switch to signal pressure loss in intake PS 2 Pressure switch to signal pressure in permeate QI 1...
  • Page 46 C = Abwasser (G1/2" aus) D = Anschluß (Flexibeler Schlauch 1/2'') 10.3 Dimensions Elektrischer Anschluß: 230V. 50Hz. AX 02 Connections: Side view A = Input (G ½“ in) B = Permeat (G ½“ out) C = Drain water (G ½“ out) D = Connection (flexible hose ½‘‘)
  • Page 47 10.4 Dimensions AX 05, 12 and 20 Connections: Side view A = Untreated water (PVC Ø 25 mm) B = Permeate (PVC Ø 20 mm) C = Drain water (hose sleeve Ø 16 mm) D = Permeate connection (flexible hose) Electrical connection: 230V / 50Hz Top view p405 Front view...
  • Page 48 10.5 Dimensions AX 30 and 50 Connections: Side view A = Untreated water (PVC Ø 25 mm) B = Permeate (PVC Ø 20 mm) C = Drain water (hose sleeve Ø 16 mm) Electrical connection: 230V / 50Hz Top view 1710 Front view 1217...
  • Page 49 Notizen Appendix...
  • Page 50 A-1230 Wien Tel. +43 (0) 1 / 60 33 111-0 Fax +43 (0) 1 / 60 33 111 399 Condair GmbH Parkring 3, 85748 Garching Tel. +49 (0) 89 20 70 08-0, Fax +49 (0) 89 20 70 08-140, www.condair.de...

This manual is also suitable for:

Ax 05Ax 12Ax 20Ax 30Ax 50