OmniSense S-26 Quick Start Manual

Wireless ultrasonic flow meter

Advertisement

Quick Links

S-26 Wireless Ultrasonic Flow Meter
Thank you for your purchase of OmniSense S-26 Wireless Ultrasonic
Flow Meter. Follow the steps below to install your sensor and view data
readings.
1
Create a new account if you do not already have one
You will need a monitoring account and a "online" gateway to see live
data on your job site
see "Monitoring quick start guide" for instructions on creating your
account
2
Mount Meter Enclosure
Use the 4 supplied mounting ears to mount the enclosure in a suitable location close to the pipe
whose flow is to be monitored.
Enclosure is a waterproof NEMA Enclosure designed to IP66 of IEC 529 and NEMA 1, 2, 4 and
4x specifications
Ultrasonic transducer cables are approximately 16 feet long
3
Connect to 100-240 VAC power
The meter is supplied with a 8 ft power cord and a 3 prong US power plug and requires a
suitable AC power source from 100-240 VAC at 1 watt
4
Using the keypad and navigating the controller menu
The controller is highly programmable, do not change any settings other than those detailed in
this document or the meter may cease to function.
The controller menu is organized as a series of uniquely numbered menu screens. On most,
but not all, menu screens the current screen number will be displayed and on all screens there
will be text describing that menu screen. Use the right arrow key to advance to the next menu
screen or the up arrow to go back to the previous menu screen. You can also enter the menu
item number directly by using blue menu key, then the up arrow to set the first digit, then the
right arrow to advance to the next digit, then the up arrow again to set the next digit then the red
"ent" button
To change the value of a setting use the red "ent" button to go into edit mode and then the up
arrow to modify the current character (can be "0-9" or a "." decimal point), then the right arrow to
move to the next character position and repeat until you have entered the desired value. To
save the value hit the red "ent" key again. Note that settings are NOT permanently saved
until you use menu screen 26 to "solidify" or permanently save the settings. Any settings
not permanently saved will be lost when power is turned off.
5
Program Pipe Dimensions
Note only two of "Pipe Inner Diameter", "Pipe Outer Diameter" or "Pipe Wall Thickness" are required
and the third will be automatically computed by the controller.
Pipe Inner Diameter - Menu screen 13
Pipe Outer Diameter - Menu screen 11
Pipe Wall Thickness - Menu screen 12
OmniSense LLC ● 72 Sams Point Road ● Ladys Island, SC 29907
quick start guide
For more information contact OmniSense Technical Support
Phone (805)-340-9625
www.omnisense.com ● E-mail:info@omnisense.com

Advertisement

loading

Summary of Contents for OmniSense S-26

  • Page 1  Pipe Outer Diameter - Menu screen 11  Pipe Wall Thickness - Menu screen 12 For more information contact OmniSense Technical Support OmniSense LLC ● 72 Sams Point Road ● Ladys Island, SC 29907 Phone (805)-340-9625 www.omnisense.com ● E-mail:info@omnisense.com...
  • Page 2 100% full of water with no air bubbles or debris in the pipe and make sure sensors are in line with each other and mounted on the top of the pipe. For more information contact OmniSense Technical Support OmniSense LLC ● 72 Sams Point Road ● Ladys Island, SC 29907 Phone (805)-340-9625 www.omnisense.com ● E-mail:info@omnisense.com...
  • Page 3 "R"eady state. 12 Viewing sensor data  see "Monitoring quick start guide" for instructions on viewing data through your OmniSense monitoring account For more information contact OmniSense Technical Support OmniSense LLC ● 72 Sams Point Road ● Ladys Island, SC 29907 Phone (805)-340-9625 www.omnisense.com ●...