Checking Connections; Switching On The Device; Switching Off The Device; Integrated Protective Features - ebm-papst R3G175-RD53-08 Operating Instructions Manual

Table of Contents

Advertisement

R3G175-RD53-08

4.5 Checking connections

; Ensure isolation from supply (all phases).
; Make sure a restart is impossible
; Check the cables for proper fit.

4.6 Switching on the device

The device may only be switched on if it has been installed properly and
in accordance with its intended use, including the required safety
mechanisms and professional electrical hookup. This also applies for
devices which have already been equipped with plugs and terminals or
similar connectors by the customer.
WARNING
Hot motor housing
Risk of fire
→ Ensure that no combustible or flammable materials are
located close to the fan.
; Before switching on, check the device for visible external damage
and make sure the protective devices are functional.
; Check the fan's air flow paths for foreign matter and remove any
foreign matter found.
; Apply the nominal supply voltage.
; Start the device by changing the input signal.
NOTE
Damage to the device from vibration
Bearing damage, shorter service life
→ Low-vibration operation of the fan must be ensured over the
entire speed control range.
→ Severe vibration can arise for instance from inexpert
handling, transportation damage and resultant imbalance or
be caused by component or structural resonance.
→ Speed ranges with excessively high vibration levels and
possibly resonant frequencies must be determined in the
course of fan commissioning.
→ Either run through the resonant range as quickly as
possible with speed control or find another remedy.
→ Operation with excessively high vibration levels can
lead to premature failure.

4.7 Switching off the device

; Disconnect the device from the power supply at the supply line's
main switch.
; When disconnecting, be sure to disconnect the ground connection last.
Item no. 56686-5-9970 · ENU · Change 223088 · Approved 2020-11-09 · Page 10 / 12
ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · info1@de.ebmpapst.com · www.ebmpapst.com
Operating instructions

5. INTEGRATED PROTECTIVE FEATURES

The integrated protective functions cause the motor to switch off
automatically in the event of the faults described in the table.
Fault
Rotor position detection error
Blocked rotor
6. MAINTENANCE, MALFUNCTIONS, POSSIBLE
CAUSES AND REMEDIES
Do not perform any repairs on your device. Send the device to ebm-
papst for repair or replacement.
Malfunction/fault
Impeller not
running smoothly
Motor not turning
Safety feature description/
function
An automatic restart follows.
; After the blockage is
removed, the motor restarts
automatically.
WARNING
Live terminals and connections even with device
switched off
Electric shock
→ Wait five minutes after disconnecting the voltage at all poles
before opening the device.
CAUTION
If control voltage or a stored speed set value is applied,
the motor will restart automatically, e.g. after a power
failure.
Risk of injury
→ Keep out of the device's danger zone.
→ When working on the device, switch off the line voltage
and ensure that it cannot be switched back on.
→ Wait until the device comes to a stop.
→ After working on the device, remove any tools or other
objects from the device.
If the device is out of use for some time, e.g. when in storage,
we recommend switching it on for at least two hours to allow
any condensation to evaporate and to move the bearings.
Possible cause
Imbalance in rotating
parts
Mechanical blockage
Line voltage faulty
Faulty connection
Possible remedy
Clean the device;
replace it if imbalance
persists after cleaning.
Make sure no
weight clips are
removed during
cleaning.
Switch off, isolate
from supply and
remove mechanical
blockage.
Check line voltage,
restore power
supply, apply control
signal.
Isolate from supply,
correct connection;
see connection
diagram.