Solar water heating system

Advertisement

Quick Links

T.124.00 Solar Water Heating System
Instruction Manual
CAUTION:
1. Turn off all electrical devices (e.g. boiler,pump) that are connected to
the unit before installation and maintenance.
2. The installer must be a trained service personnel
3. Disconnect the power supply before maintenance.
4. It must be mounted on a dry clean indoor place.
5. Do not expose this unit to moisture.
6. Do not expose this unit to dipping or splashing.
Wiring diagram:
Output 1
Output 2
Sensor connection
Terminal:
L
230Vac Live
N
230Vac Neutral
P
Output1 (Pump)
COM
230Vac Live Input
NC
Normally Closed Output2
NO
Normally Open Output2(Boiler or 2
Sensor Terminal:
T1
PT1000 sensor to solar collector panel
T2,T3
NTC sensor to water tank
Rating:
Input voltage: 230Vac +10% ~ 230Vac -15%
Output1: 5A, 230Vac
Output2: 5A, 230Vac
Mounting:
Open the thermostat at bottom
side by a flat screw driver
Unplug the 10 pins connector
between the top and the base
housing
1.
Base housing
i.
Adjust the base on the wall or junction box and ensure that the base is at
surface level and cover the junction box comfortably.
ii.
Pull the cables out through the middle hole of the base.
iii.
If necessary, place 2 pcs of wall anchors in the wall.
iv.
Fasten the base with 2 pcs of long screws.
v.
Place the cables at the hole near the terminal block.
2.
Hold the thermostat on the base.
3.
Connect 10 pins connector betweeb top and base PCB
4.
Push the thermostat straight onto the base until it snaps into place.
Dimension in mm
nd
pump)
User interface:
Normal page:
Press "Up/Down" key to check T1 to T3 temperature.
(T3 is not available in Sys1)
o
If T1 temperature over 200
C , thermostat shows HI
o
If T1 temperature below 0
C, thermostat shows LO
o
If T2 or T3 temperature over 100
C , thermostat shows HI
o
If T2 or T3 temperature below 0
C thermostat shows LO

Advertisement

loading
Need help?

Need help?

Do you have a question about the T.124.00 and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Antares T.124.00

  • Page 1 Rating: User interface: Input voltage: 230Vac +10% ~ 230Vac -15% Output1: 5A, 230Vac T.124.00 Solar Water Heating System Output2: 5A, 230Vac Instruction Manual Mounting: Open the thermostat at bottom CAUTION: side by a flat screw driver 1. Turn off all electrical devices (e.g. boiler,pump) that are connected to the unit before installation and maintenance.
  • Page 2 Press “Up/Down” to adjust the T2 set point Mode selection Press “Set” key to confirm and go to T2 span setting Press Mode key to select the setting modes The sequence is: Output1 setting-> Output2 Setting (Not available in Sys1)-> High/Low limit setting->Program Timer(Sys2 and Sys3 only) Press “Set”...
  • Page 3 Internal Setting: Hold and press “Set” key to enter internal setting Press Up/Down to select time scale. Press “Set” key to confirm and start this function. If Fill system on is selected, it will go to time setting Press” Up/Down” to set the test duration Press “Up/Down”...
  • Page 4 System selection System 4: 3 sensors with 2 tanks T1: Solar Collector temperature sensor System 1: 2 sensors and 1 tank T2: Lower storage tank temperature sensor T1: Solar Collector temperature sensor T3: Differential sensor T2: Lower storage tank temperature sensor ∆T12 T1 Low limit T2 Set point...