Page 1
User Manual IP Interface with Secure and Cloud_V1.0 BNIPC-00/00.S KNX/EIB Home and Building Control System...
Page 2
Attentions 1. Please keep devices away from strong magnetic field, high temperature, wet environment; 2. Please do not fall the device to the ground or make them get hard impact; 3. Please do not use wet cloth or volatile reagent to wipe the device; 4.
KNX/EIB IP Interface with Secure and Cloud Chapter 1 Summary The IP Interface with Secure and Cloud is designed for an intelligent building control system, which is used for facilitating communication between the Ethernet network and the KNX system. KNX telegram can be sent to or received from other devices via the network.
Page 5
KNX/EIB IP Interface with Secure and Cloud This manual provides detail technical information on the function as well as assembly and programming of the device for users, and the operation and usage of KNX Engineering Assistant Management Platform and KNX Project Assistant, and explains how to use the interface device by the application examples.
KNX/EIB IP Interface with Secure and Cloud Chapter 2 Technical Data Power supply Operation voltage 21-30V DC, via the KNX bus Current consumption <5mA, 24V; <4mA, 30V Power consumption <120mW Auxiliary voltage 12-30V DC Auxiliary current <60mA, 24V; <50mA, 30V Auxiliary power consumption <1.5W Connections...
KNX/EIB IP Interface with Secure and Cloud Chapter 3 Dimension and Connection Diagram 3.1. Dimension diagram 3.2. Connection diagram Cloud button: Press disable/Enable ① commissioning via cloud ② LAN LED: Always ON-enable ETS commissioning via cloud Single flashing-disable ETS commissioning via cloud Double flashing-abnormal connection to cloud OFF-unconnected or abnormal Network ③...
KNX/EIB IP Interface with Secure and Cloud Chapter 4 Parameter setting description in the ETS 4.1. Parameter window “General” Parameter window “General” is shown in fig. 4.1.1. The device information,including company name, project name,DNS server can be set here. Fig 4.1.1 “General” parameter window Parameter “Company Name (30 char.)”...
Page 9
KNX/EIB IP Interface with Secure and Cloud Configure the IP parameters of the IP device in the properties window of ETS. Device name: Device-->Properties-->Settings-->Name The device name can be entered in the Settings Properties window. The device name loaded into the device can be changed in the Name field, as shown in Figure 4.1.2 below.
Page 10
KNX/EIB IP Interface with Secure and Cloud Fig. 4.1.3 IP Obtain an IP address automatically:In the default setting the IP Interface with Secure expects the assignment of an IP address by a DHCP (dynamic host configuration protocol) server. This server responds to a request by assigning a free IP address to the device.
KNX/EIB IP Interface with Secure and Cloud 4.2. Use of the integrated tunneling servers The IP Interface with Secure offers 5 additional physical addresses, which can be used for a tunneling connection, shown in fig. 4.2.1. These so-called tunneling servers can be used with the ETS as a programming interface or with another visual display client, with smartphone, with tablet, with bus tool etc.
Page 12
KNX/EIB IP Interface with Secure and Cloud In addition, the tunneling servers can also be encrypted with KNX Secure. First activate Secure Commissioning, and then activate Secure Tunneling, as shown in Figure 4.2.3. After activating Secure Tunneling, the password for each Tunneling connection can be set in ETS, as shown in Figure 4.2.4, and users can change this password as needed.
KNX/EIB IP Interface with Secure and Cloud Fig.4.2.5 Set project password 4.3. KNX Secure The IP Interface with Secure is a KNX device according to the KNX Secure standard. In other words, the device can run in secure mode, and the tunneling connection are encrypted. Therefore, the following information must be taken into account during device commissioning: It is essential to assign a project password as soon as a KNX Secure device is imported into a ...
Page 14
KNX/EIB IP Interface with Secure and Cloud Fig.4.3.1 Add Device Certificate window Alternatively, the certificates of all Secure devices can be entered in the ETS beforehand. This is done on the “Security” tab on the project overview page, as shown in Figure 4.3.2 below. The certificates can be also added to the selected device in the project, as shown in Figure 4.3.3.
Page 15
KNX/EIB IP Interface with Secure and Cloud Without the FDSK, it will no longer be possible to operate the device in KNX Secure mode after a reset. The FDSK is required only for initial commissioning. After entering the initial FDSK, the ETS will assign a new key, as shown in Figure 4.3.4 below.
Page 16
KNX/EIB IP Interface with Secure and Cloud Whether the device is replaced in the same project, or the device is replaced in a different project, the processing is similar: Reset the device to the factory settings, then reassign the FDSK. After the device is downloaded successfully, the label Add Device Certificate turns gray, indicating that the key for this device has been assigned successfully, as shown in Figure 4.3.6 below.
Page 17
KNX/EIB IP Interface with Secure and Cloud Fig. 4.3.8 IP tunneling connection In Figure 4.3.8, if Secure Tunneling is not activated, , the commissioning password and authentication code are not required when the device is connected as an interface; if Secure Tunneling...
KNX/EIB IP Interface with Secure and Cloud is activated, ETS will prompt you to enter the commissioning password and authentication code when connecting. The IP Interface can be reset to its factory settings if necessary, see chapter 5, Factory setting Note: Any USB interface used for programming a KNX Secure device must support “long frames”.
KNX/EIB IP Interface with Secure and Cloud The key assigned by the ETS will be retained. In other words, the FDSK will not be needed for reprogramming The physical address will be retained Unloading the physical address and the application The device will be reset to the factory state ...
KNX/EIB IP Interface with Secure and Cloud Chapter 5 Factory setting The IP Interface is delivered with the following default factory settings: Physical address 15.15.254 15.15.241 15.15.242 Tunneling Addresses 15.15.243 15.15.244 15.15.245 IP configuration IP address 192.168.2.200 Subnet mask 255.255.255.0 Default gateway 192.168.2.1 The reset to factory settings can also be performed directly on the device.
KNX/EIB IP Interface with Secure and Cloud Chapter 6 Web Configuration Web configuration is typically used to modify IP addresses and device description, and upgrade devices. Note: If KNX security is enabled, device description and network configuration cannot be modified via the web configuration. Enter the IP the device in the web browser to enter the web configuration interface address of...
Page 22
KNX/EIB IP Interface with Secure and Cloud Device Description: ① MAC Addr.: Display the MAC address. ② Device Name: Display or set the device name. ③Project Name: Display or set the project name. ④Company Name: Display or set the company name. ⑤Software Version: Display the firmware (linux software.fwp) version and date.
Page 23
KNX/EIB IP Interface with Secure and Cloud Note: If the user does not know or forget the IP address, reset the IP address of the device to the default address of 192.168.2.200 via restore factory setting (See Chapter 5 for details), and then enter this IP address in the browser to enter the web configuration window of the device and change the IP settings and then save.
KNX/EIB IP Interface with Secure and Cloud Chapter 7 KNX Engineering Assistant Management Platform Login address of KNX Project Management Platform: https://assistant.gvs-icloud.com/, as shown as Fig.7.1. Select the role to login:System administrator, Enterprise Fig.7.1 Login window KNX Project Management Platform is used for assisting IP interface for remote debugging of KNX projects, including System client (login as System administrator), Enterprise client (login as Enterprise administrator / engineer).
KNX/EIB IP Interface with Secure and Cloud 7.1. Enterprise management 7.1.1. Login Fig.7.1.1.1 Login window Please contact the manufacturer to obtain account and password of enterprise client, that is, contact the system administrator to provide it. Then input correct enterprise name, user name and password to login.
KNX/EIB IP Interface with Secure and Cloud Fig.7.1.1.2 Password change 7.1.2. Home Home page shows an overview, including number of projects, engineers and devices, enterprise name, enterprise code, account status and etc. It provides the password changing and logout in the upper right corner of the interface.
KNX/EIB IP Interface with Secure and Cloud 7.1.3. Project management Interface of project management is shown as Fig.7.1.3.1, you can add, delete, view, search and sort the projects. Fig.7.1.3.1 Project management The instructions for the items in the figure are as follows: (1) Add new project Click “+ Add project”...
Page 28
KNX/EIB IP Interface with Secure and Cloud (2) Detail Click “Detail” on interface of project management, you can view the detail information of project, as show as Fig.7.1.3.3. View or edit project information, and view the device information and device status of the project, including device name, device ID, MAC address, online status.
Page 29
KNX/EIB IP Interface with Secure and Cloud (3) Delete Click “Delete” on interface of project management, pop up a window as following figure, click “Delete” button and the devices in this project are deleted synchronously. When re-add a new project with the same information (the name of the enterprise and project coincide), the devices of original project will be associated automatically.
KNX/EIB IP Interface with Secure and Cloud 7.1.4. Engineer management Interface of engineer management is shown as Fig.7.1.4.1, you can add, delete, view, search and sort engineer, as well as authorize device to engineers. Fig.7.1.4.1 Engineer management The instructions for the items in the figure are as follows: (1) Add new engineer Click “+ Add”...
Page 31
KNX/EIB IP Interface with Secure and Cloud Remark (optional): 0-200 characters, all blank strings are prohibited. (2) Detail Click “Detail” button on interface of engineer management, you can view the detail information of engineer, as show as Fig.7.1.4.3. View or edit engineer information, and view / edit authorized devices. Fig.7.1.4.3 Engineer detail ①Edit basic information, as following figure: Edit basic information of engineer...
Page 32
KNX/EIB IP Interface with Secure and Cloud ②Edit authorized devices, as following figure: Click “Device Authorization”, enter the interface of device authorization: Fig.7.1.4.4 Device authorization Support precise search of device name, device ID, and MAC address; Support the filter of the device online / offline status and the project to which it belongs; ...
Page 33
KNX/EIB IP Interface with Secure and Cloud (4) Delete Click “Delete” on interface of engineer management, pop up a window as following figure, click “Delete” button and remove the authorization between devices and engineer, and the personnel will not be able to use KNX Project Assistant to remotely debug the device. Fig.7.1.4.5 Delete engineer (5) Delete in batches Choose multiple engineers and delete together.
KNX/EIB IP Interface with Secure and Cloud 7.1.5. Device management Device management interface is shown as Fig.7.1.5.1, you can search device information ( device name, device ID, MAC address, online status and project), as well as manage authorization code of IP device in the project.
Page 35
KNX/EIB IP Interface with Secure and Cloud (3) Generate authorization code Click “Code” on interface of device management, pop up the window for authorization code, as show as Fig.7.1.5.2. Each device only has a authorization code, if it already has a authorization code, the original code will be replaced by the new one.
Page 36
KNX/EIB IP Interface with Secure and Cloud Fig.7.1.5.3 Device details...
KNX/EIB IP Interface with Secure and Cloud 7.1.6. Additional Instructions Enterprise administrator create account for engineers, and engineers also can login KNX Engineering Assistant Management Platform with created user name and initial password. The interface as shown as Fig.7.1.6 after login. It is different to enterprise administrators is that engineers can only view two interfaces: project management and device management.
KNX/EIB IP Interface with Secure and Cloud Chapter 8 KNX Project Assistant KNX Project Assistant is a tool for assisting IP interface to debug KNX program remotely. Connect IP device remotely via local PC, then you can operate a remote debugging and no need to go to the scene.
KNX/EIB IP Interface with Secure and Cloud After login successfully, you can operate IP device, such as connect IP device remotely, test the response time and so on. 8.3. Device connection The interface of device connection as shown as Fig.7.3.1, you can view the online status of all IP device, the connection status and so on.
Page 40
②Click “Language”, change software language. As following figure: ③ Click “About”, display manufacturer logo, software version, date and etc., as shown as following figure. Click “Enter page of official website” and then it will jump to GVS official website automatically.
Page 41
KNX/EIB IP Interface with Secure and Cloud (2) Search&Sort&Refresh ①Search: support search of keywords, such as company name, device name, device ID (complete). ②Select the project to which device belongs. ③Refresh: refresh the interface display when there is update. (3) Remote assistance When other engineers need you to assist with debugging remotely, please click “Remote assistance”, then pop-up a dialog box as following, input authorization code of remote IP device.
Page 42
KNX/EIB IP Interface with Secure and Cloud (4) Online status Device is online or offline status is that device whether connect network normally. (5) Remote access Display the remote access status (enable / disable). When it is enabled, you can connect a remote device to debug project remotely;...
Page 43
KNX/EIB IP Interface with Secure and Cloud Click “Disconnect”, then disconnect the connection with the device. If the device is not operated for a long time, it will be disconnected automatically. The same device can only be connected by one engineer, the other engineers request a connection will be prompted the device is being used by engineer.
Page 44
KNX/EIB IP Interface with Secure and Cloud Fig.7.3.2 Remote connection building...
KNX/EIB IP Interface with Secure and Cloud Chapter 9 Remote Commissioning Steps 1. After obtaining the product from the manufacturer, check the product for abnormalities. 2. Connect to KNX system, auxiliary supply and network, then check the LED display, confirm power supply, KNX and network are already connected.